UL Report for MSP 3RV103 Manual and Group.pdf

File E47705
Project 97ME18400
August 21, 1997
REPORT
on
MOTOR CONTROLLERS, MANUAL
Amberg, FED REP Germany
Copyright © 1997 Underwriters Laboratories Inc.
Underwriters Laboratories Inc. authorizes the above named company to reproduce
this Report provided it is reproduced in its entirety.
File E47705
Vol. 7
Sec. 7
and Report
Page 1
Issued: 1997-08-21
Revised: 2005-08-16
DESCRIPTION
PRODUCT COVERED:
USL, CNL - Type No. 3RV1031, 3RV1131, 3RV1331, 3RV1431 or 3RV1631,
followed by combination of 0, 1 or 4 and a letter A through K, followed by A,
B, C or K followed by 1 or 3. May be followed by additional numbers and
letters for manufacturer’s use.
GENERAL:
The devices 3RV1031 are open type 3-pole manual motor controllers for
starting and stopping motors which may be connected directly across the line.
They are adjusted over a small range as indicated in the setting range table.
They are provided with integral ambient compensated, non replaceable thermal
trip features and are suitable for providing overload protection and motor
disconnect. The trip current is 125 percent of the FLA shown on dial.
Type 3RV1131-..is identical to the standard series device but with no
motor overload function. The internal overload tripping system does not trip
the controller, however it trips the attached trip module for indication to
remote panels.
The devices 3RV1331 are identical to the Types 3RV1031 except the
thermal overload trip is out of function.
The devices 3RV1431 are identical to the Types 3RV1031 except the
instantaneous overcurrent trip is adjusted to 19 x Ie.
The devices 3RV1631 are identical to the Types 3RV1031 except the
thermal overload trip is adjusted to Class 5.
These devices may be provided with certified accessories of Type 3RVl9..
including auxiliary switches, tripping units and short circuit indicators.
RATINGS:
General Purpose Rating
600 V AC, 50 A, FLA max. 54 A
Voltage
115 V
200/208
230/240
460/480
575/600
V
V
V
V
Horsepower
1-ph
3 hp
7 ½ hp
10 hp
-
3-ph
15
20
40
50
hp
hp
hp
hp
Pilot Duty rating for 3RV1131 trip module outputs 1 NO + 1 NC:
R300 opposite polarity.
C600,
File E47705
Vol. 7
Sec. 7
and Report
Page 2
Issued: 1997-08-21
Revised: 2005-05-12
ENGINEERING CONSIDERATIONS (NOT FOR UL REPRESENTATIVE USE):
CNL - Indicates Investigated to Canadian National Standard(s) C22.2
No. 14-M95.
Note: CNL = Canadian National Standards - Listed.
USL = United States Standards - Listed.
These devices are suitable for use on a circuit capable of delivering
not more than 1,000 rms symmetrical amperes up to setting range - 1B, 600 V
maximum and with - 1C and higher 5,000 rms symmetrical amperes, 600 V maximum.
High Capacity Short-circuit rating:
480 V, 3 phase, 65,000 rms symmetrical amperes
600 V, 3 phase, 30,000 rms symmetrical amperes
Enclosure size: 11-1/2 by 11-1/2 by 6 inches, metal
“Suitable for tap conductor protection in group applications” Type
3RV1031 only
These devices are suitable for use as motor disconnect.
These devices are suitable to provide over current protection for
control transformers.
NOMENCLATURE BREAKDOWN
3RV1031I
I.
1A
II
A
III
1
IV
8 V
1B
VI
P0
VII
Basic Type Size S2
3RV1031 - with overload (Class 10 or Class 20) and short-circuit
protection (12 x Ie) 3RV1331 - with short-circuit protection only
(12 x Ie)
3RV1131 – 3 main contacts with short-circuit protection, overload
tripping 12 x Ie is indicated by an attached tripping module.
3RV1431 - with overload and short-circuit protection (19 x Ie)
3RV1631 - with overload (Class 5) and short-circuit protection
(12 x Je)
File E47705
II.
Vol. 7
Sec. 7
and Report
0K
1A
1B
1C
1D
1E
1F
1G
1H
1J
1K
4A
4B
4D
4E
4F
4G
4H
4D
0.9
1.1
1.4
1.8
2.2
2.8
3.5
4.5
5.5
7
9
11
14
18
22
28
36
40
18
To (A)
1.25
1.6
2
2.5
3.2
4
5
6.3
8
10
12.5
16
20
25
32
40
45
50
25
Max. Fuse or CB
6 A
6 A
6 A
10 A
10 A
15 A
20 A
25 A
30 A
40 A
50 A
60 A
80 A
100 A
125 A
150 A
175 A
200 A
100 A
setting
setting
same as
setting
ranges with
ranges with
A but fixed
ranges with
instantaneous tripping, Class 10
instantaneous tripping, Class 20
to maximum range value
instantaneous tripping, Class 5
Type of Terminals
1
3
V.
From
Tripping Class
A
B
C
K
IV.
Issued: 1997-08-21
Revised: 2005-05-12
Setting Ranges
Suffix
III.
Page 3
Screw Terminal
Main terminal have screw terminals
auxiliary contact cage clamp terminals, if provided
Auxiliary Switches and Tripping Units
(Combinations with certified accessories Type 3RV19...)
0
1
2
3
4
5
8
without
1NO + 1NC, side mounted
2NO, side mounted
2NC, side mounted
1 changeover contact, top mounted
1NO + 1NC, top mounted
code No. for further following suffixes under V.
File E47705
VI.
Vol. 7
Sec. 7
and Report
Auxiliary Switches and Tripping Units continued
-1B
-2B
-3B
VII.
Page 4
Undervoltage trip, side mounted
same as -1B + 2NO make-before-break
Remote tripping unit, side mounted
Operating voltage for accessories
24 V through 600 V ac or
12 V through 250 V dc
Issued: 8-21-97
File E47705
Vol. 7
Sec. 7
and Report
Page 5
Issued: 1997-08-21
Revised: 2005-05-12
CONSTRUCTION DETAILS
General: The product shall be constructed in accordance with the
following description and photos.
Spacings: Other than noted below, the spacings between bare live parts
of opposite polarity and between bare live parts and grounded metal parts is
not less than 3/8 in (9.5 mm) measured through air or 1/2 in (12.7 mm)
measured over the surface of insulating material.
The spacings between bare live parts and metal parts of an enclosure or
the mounting surface shall be not less than 1/2 in (12.7 mm) through air or
over surface.
Tolerances:
nominal.
Unless specified otherwise, the indicated dimensions are
Corrosion Protection: All parts are of corrosion resistant material or
are plated or painted as corrosion protection.
Markings: Paper adhesive labels on the device and printed to the cover
including the manufacturer’s name, type and electrical ratings.
The terminal tightening torque must be marked on the device.
markings do not pertain to control circuits.
These
The following statement is also marked on the device:
“MAX. FUSE / CB xx A”
xx = for current rating of the fuse see list on page 2.
The following statement is also marked on the device or in the
instruction manual:
“SUITABLE FOR USE ON A CIRCUIT CAPABLE OF DELIVERING NOT MORE THAN xxxx
RMS SYMMETRICAL AMPERES; 600 V MAXIMUM”.
xxxx = 1,000 up to setting range –1A
5,000 from setting range –1B
“USE 75°C COPPER WIRE ONLY”
Type 3RV1031 marked –
“Suitable for tap conductor protection in group applications” –
“SUITABLE AS MOTOR DISCONNECT”
File E47705
Vol. 7
Sec. 7
and Report
GROUP INSTALLATION:
Edition).
*Page 5A
Issued: 1997-08-21
New: 2003-06-05
(For reference only, in accordance with UL 508, 16th
All setting ranges are suitable for use in group installation for the
following ratings:
*Maximum Short-circuit rating: 480 V, 3 phase, 65,000 rms symmetrical amperes.
600 V, 3 phase, 30,000 rms symmetrical amperes.
Enclosure size:
11-1/2 by 11-1/2 by 6 inches, metal.
Branch Circuit Protective device: The appropriate BCPD needs to be
determined in accordance with the National Electrical Code, NFPA-70 Article
430-53 and the application. The following devices are permitted.
Fuses:
Circuit breakers:
Classes RK1, RK5, J, G, T, CC
Listed Siemens type, with a marked short-circuit
rating equal or larger than the available short
circuit current rating.
These devices were tested for group installation use at the above levels
without any upstream branch circuit device.