LEM LF305-S_06

Current Transducer LF 305-S
IPN
=
300 A
For the electronic measurement of currents: DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
16167
Electrical data
I PN
IPM
RM
Primary nominal current rms
Primary current, measuring range
Measuring resistance
with ± 12 V
with ± 15 V
with ± 20 V
ISN
KN
VC
IC
300
0 .. ± 500
RM mini
RM maxi
A
A
0
0
0
0
15
15
Ω
Ω
Ω
Ω
Ω
Ω
@ ± 300 A max
@ ± 500 A max
@ ± 300 A max
@ ± 500 A max
@ ± 300 A max
@ ± 500 A max
Secondary nominal current rms
Conversion ratio
Supply voltage (± 5 %)
Current consumption
39
12
58
22
93
45
150
mA
1 : 2000
± 12 .. 20
V
26 (@ ±20V) + IS mA
Accuracy - Dynamic performance data
XG
ε
Overall accuracy @ IPN , T A = 25°C
Linearity error
L
± 0.4
< 0.1
Typ
%
%
Maxi
± 0.20
mA
IOT
Offset current @ IP = 0, T A = 25°C
Magnetic offset current 1) @ IP = 0 and specified RM,
after an overload of 3 x IPN
Temperature variation of IO
- 10°C .. + 70°C
± 0.08
± 0.1 ± 0.30
mA
mA
tra
tr
di/dt
BW
Reaction time @ 10 % of IPN
Response time 2) to 90 % of IPN step
di/dt accurately followed
Frequency bandwidth (- 1 dB)
< 500
<1
> 100
DC .. 100
IO
I OM
Features
• Closed loop (compensated) current
transducer using the Hall effect
• Isolated plastic case recognized
according to UL 94-V0.
Advantages
•
•
•
•
•
•
•
Excellent accuracy
Very good linearity
Low temperature drift
Optimized response time
Wide frequency bandwidth
No insertion losses
High immunity to external
interference
• Current overload capability.
Applications
• AC variable speed drives and servo
ns
µs
A/µs
kHz
motor drives
• Static converters for DC motor drives
• Battery supplied applications
• Uninterruptible Power Supplies
(UPS)
• Switched Mode Power Supplies
(SMPS)
• Power supplies for welding
General data
TA
TS
RS
m
Notes:
applications.
Ambient operating temperature
Ambient storage temperature
Secondary coil resistance @ T A = 70°C
Mass
Standards
1)
2)
- 10 .. + 70
°C
- 25 .. + 85
°C
25
Ω
95
g
EN 50178: 1997
Application domain
• Industrial.
The result of the coercive field of the magnetic circuit
With a di/dt of 100 A/µs.
page 1/3
061031/7
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Current Transducer LF 305-S
Isolation characteristics
Vd
Vw
Rms voltage for AC isolation test, 50/60 Hz, 1 mn
Impulse withstand voltage 1.2/50 µs
3.8
10
kV
kV
dCp
dCl
CTI
Creepage distance
Clearance distance
Comparative Tracking Index (Group II)
11.9
11.5
175
mm
mm
Application examples
According to EN 50178 and IEC 61010-1 standards and following conditions:
• Over voltage category OV 3
• Pollution degree PD2
• Non-uniform field
EN 50178
IEC 61010-1
Rated isolation voltage
Nominal voltage
Single isolation
1000 V
1000 V
Reinforced isolation
500 V
500 V
dCp, dCI, VW
Safety
This transducer must be used in electric/electronic equipment with respect to
applicable standards and safety requirements in accordance with the manufacturer's
operating instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a built-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
page 2/3
061031/7
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Dimensions LF 305-S
(in mm. 1 mm = 0.0394 inch)
Connection
Bottom view
Right view
Back view
Top view
Mechanical characteristics
Remarks
• General tolerance
• Transducer fastening
• IS is positive when IP flows in the direction of the arrow
• Temperature of the primary conductor should not exceed
Vertical position
Recommended fastening torque
or
Recommended fastening torque
Flat lying position
Recommended fastening torque
or
Recommended fastening torque
• Primary through-hole
• Connection of secondary
± 0.5 mm
2 holes ∅ 4.3 mm
2 steel screws M4
3.2 Nm or 2.37 Lb.-Ft.
4 holes ∅ 1.9 mm, depth : 7 mm
4 screws PTKA 25, length: 6 mm
0.7 Nm or 0.52 Lb.-Ft.
4 holes ∅ 4.3 mm
4 steel screws M4
2.9 Nm or 2.14 Lb.-Ft.
4 holes ∅ 1.9 mm, crossing
4 screws PTKA 25, length:10 mm
0.75 Nm 0.55 Lb.-Ft.
∅ 20 mm
Molex 5045-03/A
100°C
• Dynamic performances (di/dt and response time) are best
with a single bar completely filling the primary hole
• This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...),
please contact us.
page 3/3
061031/7
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.