ETC ATV312HD11N4

Product data sheet
Characteristics
ATV312HD11N4
variable speed drive ATV312 - 11kW - 25kVA 397 W - 380..500 V - 3-phase supply
Range of product
Altivar 312
Product or component
type
Variable speed drive
Product destination
Asynchronous motors
Product specific
application
Simple machine
Assembly style
With heat sink
Component name
ATV312
Motor power kW
11 kW
Motor power hp
15 hp
[Us] rated supply
voltage
380...500 V (- 5...5 %)
Supply frequency
50...60 Hz (- 5...5 %)
Network number of
phases
3 phases
Line current
28.4 A for 500 V
37.2 A for 380 V, 1 kA
EMC filter
Integrated
Apparent power
25 kVA
Maximum transient
current
41.6 A for 60 s
Power dissipation in W
397 W at nominal load
Speed range
1...50
Asynchronous motor
control profile
Factory set : constant torque
Sensorless flux vector control with PWM type motor
control signal
Electrical connection
Al1, Al2, Al3, AOV, AOC, R1A, R1B, R1C, R2A,
R2B, LI1...LI6 terminal 2.5 mm² AWG 14
L1, L2, L3, U, V, W, PA, PB, PA/+, PC/- terminal 2.5
mm² AWG 14
Supply
Internal supply for logic inputs at 19...30 V <= 100 A
for overload and short-circuit protection
Internal supply for reference potentiometer (2.2 to
10 kOhm) at 10...10.8 V <= 10 A for overload and
short-circuit protection
Communication port
protocol
CANopen
Modbus
IP degree of protection
IP20 on upper part without cover plate
IP21 on connection terminals
IP31 on upper part
IP41 on upper part
Option card
CANopen daisy chain communication card
DeviceNet communication card
Fipio communication card
Modbus TCP communication card
Profibus DP communication card
Complementary
Supply voltage limits
323...550 V
Network frequency limits
47.5...63 Hz
Prospective line Isc
1 kA
Continuous output current
27.7 A at 4 kHz
Speed drive output frequency
0.5...500 Hz
Nominal switching frequency
4 kHz
10/8/2011
1
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Main
Switching frequency
2...16 kHz adjustable
Transient overtorque
150...170 % of nominal motor torque
Braking torque
<= 150 % with braking resistor for 60 s
100 % with braking resistor continuously
150 % without braking resistor
Regulation loop
Frequency PI regulator
Motor slip compensation
Adjustable
Automatic whatever the load
Suppressable
Output voltage
<= power supply voltage
Tightening torque
0.6 N.m Al1, Al2, Al3, AOV, AOC, R1A, R1B, R1C, R2A, R2B, LI1...LI6
0.8 N.m L1, L2, L3, U, V, W, PA, PB, PA/+, PC/-
Insulation
Electrical between power and control
Analogue input number
3
Analogue input type
AI1 configurable voltage 0...10 V, input voltage 30 V max, impedance 30000
Ohm
AI2 configurable voltage +/- 10 V, input voltage 30 V max, impedance 30000
Ohm
AI3 configurable current 0...20 mA, impedance 250 Ohm
Sampling duration
AI1, AI2, AI3 8 ms for analog
LI1...LI6 4 ms for discrete
Response time
AOV, AOC 8 ms for analog
R1A, R1B, R1C, R2A, R2B 8 ms for discrete
Linearity error
+/- 0.2 % for output
Analogue output number
2
Analogue output type
AOC configurable current 0...20 mA, impedance 800 Ohm, resolution 8 bits
AOV configurable voltage 0...10 V, impedance 470 Ohm, resolution 8 bits
Discrete input logic
LI1...LI4 logic input not wired , < 13 V (state 1)
LI1...LI6 negative logic (source), > 19 V (state 0)
LI1...LI6 positive logic (source), < 5 V (state 0), > 11 V (state 1)
Discrete output number
2
Discrete output type
R1A, R1B, R1C configurable relay logic 1 NO + 1 NC, electrical durability 100000
cycles
R2A, R2B configurable relay logic NC, electrical durability 100000 cycles
Minimum switching current
R1-R2 10 mA at 5 V DC
Maximum switching current
R1-R2 on inductive load, 2 A at 250 V AC, cos phi = 0.4, L/R = 7 ms
R1-R2 on inductive load, 2 A at 30 V DC, cos phi = 0.4, L/R = 7 ms
R1-R2 on resistive load, 5 A at 250 V AC, cos phi = 1, L/R = 0 ms
R1-R2 on resistive load, 5 A at 30 V DC, cos phi = 1, L/R = 0 ms
Discrete input number
6
Discrete input type
LI1...LI6 programmable 24 V 0...100 mA with PLC, impedance 3500 Ohm
Acceleration and deceleration ramps
Linear adjustable separately from 0.1 to 999.9 s
S, U or customized
Braking to standstill
By DC injection
Protection type
Input phase breaks drive
Line supply overvoltage and undervoltage safety circuits drive
Line supply phase loss safety function, for three phases supply drive
Motor phase breaks drive
Overcurrent between output phases and earth (on power up only) drive
Overheating protection drive
Short-circuit between motor phases drive
Thermal protection motor
Insulation resistance
>= 500 MOhm at 500 V DC for 1 minute
Local signalling
1 LED red for drive voltage
Four 7-segment display units for CANopen bus status
Time constant
5 ms for reference change
Frequency resolution
Analog input 0.1...100 Hz
Display unit 0.1 Hz
Type of connector
1 RJ45 Modbus/CANopen
Physical interface
RS485 multidrop serial link
Transmission frame
RTU
Transmission rate
10, 20, 50, 125, 250, 500 kbps or 1 Mbps CANopen
4800, 9600 or 19200 bps Modbus
Number of addresses
1...127 CANopen
1...247 Modbus
2
Number of drive
127 CANopen
31 Modbus
Marking
CE
Operating position
Vertical +/- 10 degree
Outer dimension
330 x 245 x 190 mm
390 x 245 x 190 mm
405 x 234 x 268 mm
555 x 234 x 268 mm
Product weight
11 kg
Environment
Dielectric strength
2410 V DC between earth and power terminals
3400 V AC between control and power terminals
Electromagnetic compatibility
1.2/50 µs - 8/20 µs surge immunity test conforming to IEC 61000-4-5 level 3
Electrical fast transient/burst immunity test conforming to IEC 61000-4-4 level 4
Electrostatic discharge immunity test conforming to IEC 61000-4-2 level 3
Radiated radio-frequency electromagnetic field immunity test conforming to IEC
61000-4-3 level 3
Standards
IEC 61800-5-1
Product certifications
CSA
C-Tick
GOST
NOM
UL
Pollution degree
2
Protective treatment
TC
Vibration resistance
1 gn (f = 13...150 Hz) conforming to EN/IEC 60068-2-6
1.5 mm (f = 3...13 Hz) conforming to EN/IEC 60068-2-6
Shock resistance
15 gn for 11 ms conforming to EN/IEC 60068-2-27
Relative humidity
5...95 % without condensation conforming to IEC 60068-2-3
5...95 % without dripping water conforming to IEC 60068-2-3
Ambient air temperature for storage
-25...70 °C
Ambient air temperature for operation
-10...50 °C without derating with protective cover on top of the drive
-10...60 °C with derating factor without protective cover on top of the drive
Operating altitude
<= 1000 m without derating
>= 1000 m with current derating 1 % per 100 m
RoHS EUR status
Compliant
RoHS EUR conformity date
0913
3