SCE-95 Signal Control Element

SCE-95
Description
Signal Control Element
The Gamewell-FCI Signal Control Element (SCE-95) is the
interface between the 600 Series and ILI95-E3 Series®, fire
alarm control panels’ (FACPs) analog circuits and building
functions. The SCE-95 connects to the panel via the SLC
circuit. The SCE-95 provides a means to remotely locate a
fully supervised circuit for the operation of signaling appliances such as horns, strobes, and horn/strobes. For
annunciation and feedback at the panel, Gamewell-FCI
offers a Signal Control Display (SCD). The SCD is only
available with the IdentiFlex 632 and IF650 FACPs.
The SCE-95 is capable of switching 24 VDC. When used
as a remote signaling circuit, the SCE-95 provides all the
necessary supervision of the circuit and trouble reporting
via the analog circuit.
SCE-95
The Signal Control Element (SCE-95) can be surface or
flush mounted and has an integral LED which annunciates
upon device activation.
Features
Operation
•
The Signal Control Element connects to the SLC of the fire
alarm control panel (FACP) via two-wires. In its standby
mode, the SCE-95 monitors its internal circuitry for status
of the device itself and supervises the external control circuit for faults. In the event that a fault is detected, the SCE95 will report a trouble to the FACP.
When an event is reported to the fire alarm control panel
(FACP) that requires the activation of the SCE-95, the control panel communicates via the analog circuit to the SCE95 and the signaling circuit is actuated. The integral LED is
also lit for annunciation at the device.
•
•
•
•
•
•
•
•
•
Compatible with the Gamewell-FCI, 600 Series and
ILI95-E3 Series, analog addressable fire alarm control
panels (FACPs)
Supervises and operates the notification appliance
circuit
Supervises DC power-in
Provides LED annunciates activation
Is fully supervised
Contains surface or flush mounted
Field programmable
Style 4, 6, or 7 wiring
Includes screw terminals for field wiring connections
Supports 24V 2.0A output
Programming
The SCE-95 is programmed by setting a single DIP switch
easily accessible on the printed circuit board. The SCE95’s DIP switch is used to set the address of the device.
All other programming is accomplished at the fire alarm
control panel (FACP), using either a laptop computer or the
control panel operator’s display. (600 Series only).
E3 Series® is a registered trademark of Honeywell International Inc.
Microsoft® Windows® is a registered trademark of Microsoft® Corporation.
SIGNALING
FM
S521
APPROVED
MEA
Approved 7300-1703:0135
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
CS-2047 Rev. C page 1 of 2
©2013 Honeywell International Inc. All rights reserved.
Mounting
Ordering Information
The SCE-95 is designed to mount in a standard 4.688"
(11.908 cm) electrical backbox. The SCE-95 should be
mounted in an easily accessible location so that the built-in
LED indicators may be easily seen and display the proper
connection and device activation.
Part Number Description
SCE-95
70839
SCD
Engineer’s Specifications
A programmable electronic device shall be provided for the
remote control of notification appliances. The device shall
communicate with the main FACP via the SLC circuit. It
shall supervise its notification appliance circuit and include
an LED for circuit activation annunciation. It shall be
Gamewell-FCI SCE-95.
Signal control element device. XP95
protocol compatible.
Trim ring for flush mounting the SCE-95.
Optional signal control display; provides
annunciation of the SCE-95 control element devices at the FACP. One needed
for every eight (8) SCE Modules. Compatible with only the IF632 and IF650 FACP.
Specifications
Normal Current (Circuit): 8 µA
Alarm Current (Circuit): 1.7 mA
Normal Current (± 24V): 0.0065A
Alarm Current (± 24V): 0.00635A + Signal Load
Operating
Temperature:
32°F to 120°F (0°C to 49°C)
Relative Humidity:
93% non-condensing
P+, P- Power:
24 VDC from control panel or
UL Listed for fire power supply
Fuse:
2 amp PTC
NAC Circuit Rating:
2 amp power-limited steady
signaling for DC appliances
Output Rating:
0.2 amp DC signal circuit
Auxiliary input Power: 24 VDC signaling power
Dimensions:
4 11/16” x 4” x 1 1/2”
(10.44 x 10.16 x 3.8 cm)
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
CS-2047 Rev. C page 2 of 2