GAMEWELL-FCI ASD-IL2F

Velociti® Series
ASD-IL2F
Description
Analog, Addressable Ionization
Smoke Sensor
The Gamewell-FCI Velociti® Series, analog addressable plug-in smoke sensors with integral communication provide features that surpass conventional
sensors. Sensor sensitivity can be programmed in
the control panel software. Sensitivity is continuously monitored and reported to the panel. Point ID
capability allows each sensor’s address to be set,
providing exact locations for selective maintenance
when the chamber contamination reaches an unacceptable level. The ASD-IL2F ionization sensor
incorporates a unique single-source, dual-chamber
design to respond quickly and dependably to a
broad range of fires.
The Velociti® Series use a communication protocol
that substantially increases the speed of communication between the sensors and certain GamewellFCI analog addressable fire alarm controls. These
devices operate in a grouped fashion. If one of the
devices in the group has a status change, the
panel’s microprocessor stops the group poll and
concentrates on the single device. The net effect is
response speed up to five times greater than earlier
designs.
ASD-IL2F
Features
• Sleek, low-profile design
• Visual rotary switch addressing
• Built-in functional test switch activated by an external
magnet
• Bicolor LEDs flash green whenever the sensor is
addressed, and light steady red on alarm*
• Optional relay, isolator, or sounder bases
• Low standby current
• Addressable-analog communication
• Stable communication technique with noise immunity
Ordering Information
• Optional remote, single-gang LED accessory RA400Z
• Suitable for installation in ducts
Model
ASD-IL2F
Description
Analog, Addressable Ionization Smoke
Sensor
Note: *Only the red LED is operative in panels that do not operate
in Velociti® mode.
An ISO 9000-2000 Company
SIGNALING
®
®
Velociti and E3 Series are registered trademarks of Honeywell International Inc.
UL® is a registered trademark of Underwriters Laboratories Inc.
FM
S1913
MEA
Approved
3023594 219-02-E Vol.VI 07271-0694:199
APPROVED
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9020-0619 Rev. B3 page 1 of 2
©2008 by Honeywell International Inc. All rights reserved.
Installation
Specifications
ASD-IL2F plug-in sensors use a separate base to simplify
installation, service, and maintenance. A special tool
allows maintenance personnel to plug-in and remove the
sensors without using a ladder.
Size
Mount the base on a box which is at least 1.5" (3.8 cm)
deep. Suitable mounting base boxes include:
• 4.0" (10.2 cm) square box.
• 3.5" (8.9 cm) or 4.0" (10.2 cm) octagonal box.
• Single-gang box (except relay or isolator base).
• With B501BH or B501BHT base, use a 4.0" (10.2 cm)
square box.
• With B224RB or B224BI base, use a 3.5" (8.9 cm) octagonal box, or a 4.0" (10.2 cm) octagonal or square box.
Shipping Weight
Operating
Temperature
2.1” (5.1 cm) high x 4.1” (10.4 cm)
diameter installed in B501 base,
6.1” (15.5 cm) diameter installed in
ADB-FLF base
5.4 oz. (154 g)
32° F to 120° F (0 to 49° C)
®
UL -Listed
0-1200 ft./min. (365.8 m/min.)
Velocity Range
Relative Humidity 10-93% (non-condensing)
Electrical Specifications
Voltage Range
Standby Current
15 – 32 volts DC peak.
.0003A @ 24 VDC
(One communication every 5 seconds
with LED enabled)
NOTE: Because of the inherent supervision provided by
the SLC, end-of-line resistors are not required. Wiring “Ttaps” or branches are permitted for Style 4 (Class “B”)
wiring.
Maximum Alarm
Current
Sensor Spacing
Bases and Options
Gamewell-FCI recommends spacing sensors in compliance with NFPA 72. In low airflow applications with
smooth ceilings, space detectors 30 feet (9.144 m). For specific information regarding sensor spacing, placement, and
special applications, refer to NFPA 72.
ADB-FLF
B501
B501BH or
B501BHT
B224RB
Relay Base
B224RB
Relay Base
Dimensions
B524BI
Isolator Base
Dimensions
RA-400Z
BCK-200
GAMEWELL-FCI
.0065A @ 24 VDC (LED lit)
6.1” (15.5 cm) diameter
4.1” (10.4 cm) diameter
Sounder base assembly (B501BHT
produces a Temporal Pattern)
Includes B501 base
Screw terminals:
Up to 14 AWG (2.0 mm2)
Relay type: Form-C
Rating:
2.0A @ 30 VDC resistive
0.3 A @ 110 VDC inductive
1.0 A @ 30 VDC inductive
6.2” x 1.2” (15.7 x 3.0 cm)
6.2” x 1.2” (15.7 x 3.0 cm)
Maximum: 25 devices between
isolator bases.
Remote alarm indicator, LED
Black detector covers (box of 10)
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9020-0619 Rev. B3 page 2 of 2
www.gamewell-fci.com