PID-95P, PID-95

PID-95P, PID-95
Description
Point Identification Device
The Gamewell-FCI PID-95P addressable point identification device is the interface between the non-powered, normally open, dry-contact devices and Gamewell-FCI’s 600
Series and ILI95-E3 Series® of analog addressable Fire
Alarm Control Panels (FACPs). Point identification devices
monitor a single Style B circuit, and are designed for concealed mounting in an electrical backbox. The PID-95P can
be surface or flush mounted and has a visible LED for
alarm/annunciation.
Operation
The point identification device connects to the Signaling
Line Circuit (SLC) via two wires. The PID-95 will monitor,
via a two-wire supervised SLC circuit, contact-type devices
such as a waterflow switch or a manual station. Upon activation of the monitored device, the PID-95 will report its
address to the 600 Series and ILI95-E3 Series FACP via
the analog SLC. The control panel will then activate into all
alarm programmed outputs related to the PID-95.
Programming
The PID-95 is programmed by setting a single DIP switch,
easily accessible on the device’s printed circuit board. The
DIP switch sets the address of the device and the priority
interrupt (DIP SW #8). All other programming is accomplished at the FACP through a laptop computer or the control panel operator’s display. (600 Series only).
PID-95P
PID-95
Features
•
Compatible with the Gamewell-FCI, 600 Series and
•
Monitors dry-contact devices
•
Includes an LED for alarm annunciation
•
Field programmable
•
Provides priority interrupt
•
Offers a plate-mounted version available for surface or
ILI95-E3 Series Systems
flush mounting in a 4" x 4.688" (10.16 cm x 11.908 cm)
double gang backbox or 4” x (10.16 cm) square backbox
Standard Application
The PID-95 is the interface between the dry-contact type
devices and the SLC of the control panel. The PID-95 is a
means of connecting and identifying monitor points without
the use of conventional input modules at the main control
panel. The use of PID-95s can dramatically reduce the field
wiring required on many projects.
SIGNALING
FM
E3 Series® is a registered trademark of Honeywell International Inc.
Microsoft® Windows® is a registered trademark of Microsoft® Corporation.
S521
APPROVED
MEA
Approved 7300-1703:0135
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
CS-2044 Rev. C page 1 of 2
©2013 by Honeywell International Inc. All rights reserved.
Ordering Information
Engineer’s Specifications
Addressable interface devices shall be provided for the
monitoring and supervision of contact type devices connected to the Fire Alarm Control Panel. The devices shall
monitor a normally open dry contact. The addressable
interface devices shall communicate to the main control
panel via the analog addressable circuit. The interface
device shall be Gamewell-FCI PID-95P or PID-95.
Part Number Description
PID-95
PID-95P
70839
Addressable point identification device
for monitoring contact devices
Addressable input interface device
mounted on 4.688" (11.908 cm) plastic plate
Trim ring for flush-mounting on the PID-95P
Specifications
PID-95P
Standby Current:
Alarm Current:
Operating
Temperature:
Relative Humidity:
Dimensions:
0.0005A, 0.0008A
0.0015A
32°F to 120°F (0°C to 49°C)
93%, non-condensing
4" x 4.688" (10.16 cm x 11.908 cm),
double gang backbox
PID-95
Standby Current:
Alarm Current:
Operating
Temperature:
Relative Humidity:
Dimensions:
0.0005A, 0.0008 A
0.0015A
32°F to 120°F (0°C to 49°C)
93%, non-condensing
4" (10.16 cm) square backbox with
blank cover plate
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
CS-2044 Rev. C page 2 of 2
www.gamewell-fci.com