PID-95P, PID-95 Description Point Identification Device The Gamewell-FCI PID-95P addressable point identification device is the interface between the non-powered, normally open, dry-contact devices and Gamewell-FCI’s 600 Series and ILI95-E3 Series® of analog addressable Fire Alarm Control Panels (FACPs). Point identification devices monitor a single Style B circuit, and are designed for concealed mounting in an electrical backbox. The PID-95P can be surface or flush mounted and has a visible LED for alarm/annunciation. Operation The point identification device connects to the Signaling Line Circuit (SLC) via two wires. The PID-95 will monitor, via a two-wire supervised SLC circuit, contact-type devices such as a waterflow switch or a manual station. Upon activation of the monitored device, the PID-95 will report its address to the 600 Series and ILI95-E3 Series FACP via the analog SLC. The control panel will then activate into all alarm programmed outputs related to the PID-95. Programming The PID-95 is programmed by setting a single DIP switch, easily accessible on the device’s printed circuit board. The DIP switch sets the address of the device and the priority interrupt (DIP SW #8). All other programming is accomplished at the FACP through a laptop computer or the control panel operator’s display. (600 Series only). PID-95P PID-95 Features • Compatible with the Gamewell-FCI, 600 Series and • Monitors dry-contact devices • Includes an LED for alarm annunciation • Field programmable • Provides priority interrupt • Offers a plate-mounted version available for surface or ILI95-E3 Series Systems flush mounting in a 4" x 4.688" (10.16 cm x 11.908 cm) double gang backbox or 4” x (10.16 cm) square backbox Standard Application The PID-95 is the interface between the dry-contact type devices and the SLC of the control panel. The PID-95 is a means of connecting and identifying monitor points without the use of conventional input modules at the main control panel. The use of PID-95s can dramatically reduce the field wiring required on many projects. SIGNALING FM E3 Series® is a registered trademark of Honeywell International Inc. Microsoft® Windows® is a registered trademark of Microsoft® Corporation. S521 APPROVED MEA Approved 7300-1703:0135 GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. www.gamewell-fci.com CS-2044 Rev. C page 1 of 2 ©2013 by Honeywell International Inc. All rights reserved. Ordering Information Engineer’s Specifications Addressable interface devices shall be provided for the monitoring and supervision of contact type devices connected to the Fire Alarm Control Panel. The devices shall monitor a normally open dry contact. The addressable interface devices shall communicate to the main control panel via the analog addressable circuit. The interface device shall be Gamewell-FCI PID-95P or PID-95. Part Number Description PID-95 PID-95P 70839 Addressable point identification device for monitoring contact devices Addressable input interface device mounted on 4.688" (11.908 cm) plastic plate Trim ring for flush-mounting on the PID-95P Specifications PID-95P Standby Current: Alarm Current: Operating Temperature: Relative Humidity: Dimensions: 0.0005A, 0.0008A 0.0015A 32°F to 120°F (0°C to 49°C) 93%, non-condensing 4" x 4.688" (10.16 cm x 11.908 cm), double gang backbox PID-95 Standby Current: Alarm Current: Operating Temperature: Relative Humidity: Dimensions: 0.0005A, 0.0008 A 0.0015A 32°F to 120°F (0°C to 49°C) 93%, non-condensing 4" (10.16 cm) square backbox with blank cover plate GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 CS-2044 Rev. C page 2 of 2 www.gamewell-fci.com