GAMEWELL-FCI PID-95

PID-95, PID-95P
Description
Point Identification Device
CS-2044ph1.wmf
The Gamewell-FCI PID-95-P addressable point identification device is the interface between the non-powered, normally open, dry-contact devices and Gamewell-FCI’s 600
Series of analog addressable Fire Alarm Control Panels
(FACPs). Point identification devices monitor a single Style
B circuit, and are designed for concealed mounting in an
electrical backbox. The PID-95P can be surface-or-flush
mounted and has a visible LED for alarm/annunciation.
Operation
The point identification device connects to the Signaling
Line Circuit (SLC) via two wires. The PID-95 will monitor,
via a two-wire supervised SLC circuit, contact-type devices
such as a waterflow switch or manual station. Upon activation of the monitored device, the PID-95 will report its
address to the 600 Series FACP via the analog SLC. The
control panel will then activate into all alarm programmed
outputs related to the PID-95.
Features
Programming
The PID-95 is programmed by setting a single DIP switch,
easily accessible on the device’s printed circuit board. The
DIP switch sets the address of the device and the priority
interrupt (DIP SW #8). All other programming is accomplished at the FACP through a laptop computer or the control panel operator’s display.
PID-95P
PID-95
•
Monitors dry-contact devices.
•
LED for alarm annunciation.
•
Supervises DC power in.
•
Field programmable.
•
Priority interrupt.
•
Plate-mounted version available for surface or flush
mounting in 4" (11 cm) square, 4.688" (11.908 cm), or
double gang boxes.
Standard Application
The PID-95 is the interface between dry-contact type
devices and the SLC of the control panel. The PID-95 is a
means of connecting and identifying monitor points without
the use of conventional input modules at the main control
panel. The use of PID-95s can dramatically reduce the field
wiring required on many projects.
An ISO 9000-2000 Company
SIGNALING
FM
Microsoft® Windows® is a registered trademark of Microsoft® Corporation.
S521
APPROVED
MEA
Approved 7300-1288:147
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2007 Honeywell International Inc. All rights reserved.
www.gamewell-fci.com
CS-2044 Rev. A page 1 of 2
Ordering Information
Engineer’s Specifications
Addressable interface devices shall be provided for the
monitoring and supervision of contact type devices connected to the Fire Alarm Control Panel. The devices shall
monitor a normally open dry contact. The addressable
interface devices shall communicate to the main control
panel via the analog addressable circuit. The interface
device shall be Gamewell-FCI PID-95 or PID-95P.
Model
Description
PID-95
Addressable point identification device for
monitoring contact devices.
Addressable input interface device mounted
on 4.688" (11.908 cm) plastic plate.
Trim ring for flush-mounting on the PID-95P.
PID-95P
70839
Specifications
PID-95
Standby Current:
Alarm Current:
Operating
Temperature:
Relative Humidity:
Mounting:
0.0005 A
0.0015 A
0° C to 49° C (32°F to 120 °F)
85%, non-condensing
4" (10.16 cm) square backbox with
blank cover plate
PID-95P
Standby Current:
Alarm Current:
Operating
Temperature:
Relative Humidity:
Mounting:
0.0005 A
0.0015 A
0° C to 49° C (32°F to 120°F)
85%, non-condensing
4" (11 cm) 4.688" (11.908 cm), double
gang Backbox.