INCC and E3 LOC, INCC CAB-B Description Intelligent Network Command Center The Gamewell-FCI, INCC Intelligent Network Command Center serves as the point of interface between an operator and the system’s audio evacuation, fire fighter intercom, and building control circuits. It is a component of the following systems. • E3 Series® Expandable Emergency Evacuation • E3 Series Combined Fire and Mass Notification System • E3 Series Broadband Audio Evacuation System • NetSOLO® System The INCC occupies a single node along the E3 Broadband network and is connected by a single pair of twisted, unshielded wire, fiber-optic cable or any combination of the two. Each E3 Broadband node can be spaced along the network at a maximum distance of 3,000 feet (914.4 m) or up to an 8dB loss using fiber-optic cable. Built-in isolation at each node permits Style 4, Style 6, and Style 7 network configurations. The E3 Series Broadband Audio Evacuation System is a peer-to-peer, self-regenerating, token ring network comprised of up to 64 individual nodes. in addition, the Addressable Node Expander (ANX) board expands the network to 122 nodes. The E3 Broadband employs proven technology and extends it to accomplish emergency voice evacuation, 2-way fire fighter communications, and building control applications. It is unique in the industry because it requires only a single pair of wires or a fiberoptic cable connection between nodes to convey all fire alarm, digital voice, fire fighter communications, paging, and building control signals. The typical INCC and E3 LOC, INCC-CAB-B sub-assemblies consist of the following: • an Intelligent Network Interface-Voice Gateway (INI-VGC) Module • one or more Addressable Switch Modules (ASM-16) • one Network Graphic Touchscreen Annunciator (NGA) The INCC Command Center’s INI-VGC module also provides connections for an optional emergency Voice Page Microphone as well as a Fire Fighter Telephone Handset. The INI-VGC is a fully digital voice/tone generator using state-of-the-art Digital Signal Processing (DSP) technology to produce the clearest, most audible signal possible. The INI-VGC provides an output to a local speaker for message verification and testing. It is ideal for a wide range of complex System Applications including high-rise or campus installations. INCC Features • Listed under UL® Standard 864, 9th Edition. • Listed under UL Standard UL2572 for Mass Notification. • All communication signals and control-by-event sequences over twisted, unshielded pair of wires or fiber-optic cable including: - Audio Evacuation - Fan Control & Damper Shutdown - Voice Paging - Door Closures - Fire Fighter Intercom - Fire Alarm and Control Devices - Elevator Control - Horn/Strove Circuit Activation • Distributed architecture, including Style 7 wiring configurations, allow system components to continue normal operation with NO loss of function during single line fault conditions. • Integrates with INX transponders and additional INCC command centers to create a complete audio evacuation system with up to 122 nodes. • Each INI-VGC supports up to 16 ASM-16 switch modules for a total of 256 switches. • INI-VGC connects to a Voice Page Microphone and Fire Fighter’s Handset. • Redundant Command Centers with Microphone and Fire Fighter’s Handset can be easily configured by adding additional INCCs. • Advance Boolean logic-based programming such as AND, OR, NOT, NOR, time delay, and calendar functions configurable through computer programming. • Advanced digital signal processor (DSP) technology for efficient audio compression and filtering. Uses network data transfer rate at 625K baud. SIGNALING MEA City of City of Approved Chicago Denver FDNY APPROVED Approved Approved S1869 3025415 COA # 6077 7165-1703:0125 Class 1 FM Class 2 High Rise GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. www.gamewell-fci.com 9020-0542 Rev. J page 1 of 4 ©2013 by Honeywell International Inc. All rights reserved. Description (Continued) Each Addressable Switch Module (ASM-16) has 16 pushbutton switches that can be programmed to serve any function the application demands. An ASM-16 switch can be programmed as any of the following: • Speaker Circuit switch • Fire Fighter Phone switch • Auxiliary Control switch using a bank of 3 switches (1 switch can be used for each On-Off-Auto function) • Switches with the following custom-defined functions” - System Reset - All-Call - System Silence - Phone Patch - System Acknowledge - Lamp Test - Alarm Tone On - Manual Select Each ASM-16 switch also has 3 fully programmable status-indicating LEDs in red, yellow, and green. The NGA LCD Graphic Annunciator is a powerful, yet attractive component of the Gamewell-FCI Emergency Voice Evacuation System. The bright, back-lit 1/4” VGA display is supplemented with an intuitive, easy-to-use touch-screen interface that provides the following features: • Up to 512 user-defined messages may be configured. • Messages may be up to 77 characters in length. • Display font and color may be selected for each message. Figure 1 INCC with MIC and Handset The INCC assembly is enclosed in one or more compact 19” wall-mounted enclosures. Its modular construction provides complete flexibility in system design. Each cabinet can contain the INI-VGC and up to six ASM-16 modules. If more ASM-16 modules are required, they may be mounted in additional INCC cabinets. As many as six ASM-16 modules can fit in the INCC cabinet. If a Microphone module is required, it would take the place of 1 ASM-16 position. A Fire Fighter Handset would take the place of 2 ASM-16 positions. An INI-VGC can support as many as 16 ASM-16s for a total of 256 completely programmable switches. The INCC operates on 24 VDC that can be sourced from the non-resettable auxiliary output of its associated power supply such as the PM-9 or PM-9G. Figure 2 INCC with 6 ASM-16s A complete E3 Series Audio Evacuation System can be assembled from the following 3 different panels. This modular approach greatly simplifies the design and installation process and can be configured to meet the exact needs of the project. • One or more E3 Series fire alarm control panels. • One or more INCC Audio Evacuation Command Centers. • One or more INX Transponders. • One ACU (Autonomous Control Unit). • One LOC (remote Local Operating Console). ® ® E3 Series and NetSOLO are registered trademarks of Honeywell International Inc. ® UL is a registered trademark of Underwriters Laboratories Inc. GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 9020-0542 Rev. J page 2 of 4 www.gamewell-fci.com INCC BACKBOX WITH INI-VGC INCC INNER DOOR SHOWN WITH ASM-16 HANDSET & MICROPHONE INNER DOOR ASSEMBLY Figure 3 INCC and E3 LOC, INCC-CAB-B Assemblies GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 www.gamewell-fci.com 9020-0542 Rev. J page 3 of 4 Specifications Ordering Information INI-VGC Description Part Number Intelligent Network Command Center Operating Voltage: 24 VDC (nominal) Operating 0.150 amp. supervisory and alarm Current: Operating 32° to 120° F (0° to 49° C) Temperature: Relative Humidity: 0 to 93% (non-condensing) Protocol Asynchronous with half-duplex data flow Speed RS-232 up to 64 KBps RS-485 up to 128 KBps St connectors Up to 200 microns (multi-mode), optimized for 62.5/125 microns. INI-VGC ASM-16 INCC-MIC INCC-TEL INCC-IDT INCC-ID INCC-CAB Dimensions: ASM-16 Operating Voltage: 24 VDC (nominal) Operating Current: 0.005 amp supervisory 0.005 amp alarm plus 0.003 amp per LED activated (0.195 amp max.) Operating Temperature: 32° to 120° F (0° to 49° C) Relative Humidity: 0 to 93% (non-condensing) INCC-CABR Dimensions: Command center voice gateway. Programmable switch module (occupies 1 single slot on the inner door). Paging Microphone module. Fire Fighter Telephone module. Inner door with 1 double slot (used for the INCC-TEL Fire Fighter Handset) and 4 single slots. Inner door with 6 single slots. INCC backbox (black) with black outer door. 19” W x 19” H x 4” D (48 W x 48 H x 10 D cm) INCC backbox (black) with red outer door 19” W x 19” H x 4” D (48 W x 48 H x 10 D cm) GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 9020-0542 Rev. J page 4 of 4 www.gamewell-fci.com