INI-VG Series

INI-VG Series
Description
The INI-VG Series (Intelligent Network Interface-Voice
Gateway) is an audio network interface that provides the
connection for the remote microphone, fire fighter telephone, one signaling line circuit. In addition, it supports the
connection for one NGA, and includes the following subassemblies:
• INI-VGC
• INI-VGE
• INI-VGX
The INI-VG Series is used in the following E3 Series Systems.
• E3 Series® Expandable Emergency Evacuation System
• E3 Series Combined Fire and Mass Notification System
• E3 Broadband Audio Evacuation System
INI-VG Series Command Center
Voice Gateway
INI-VG Series
Features
The INI-VG Series include the following features:
INI-VGC
The INI-VGC Voice Gateway Module provides command
and control functions for the INCC Command Center. The
INCC serves as the point of interface between an operator
and the system’s audio evacuation, fire fighter intercom,
and building control circuits.
A typical INCC assembly consists of an Intelligent Network
Interface-Voice Gateway (INI-VGC) Module and one or
more Addressable Switch Modules (ASM-16). Each INIVGC can support up to 16 ANU-48 LED Driver Modules or
ASM-16s for a total of 256 fully programmable switches
and 768 LEDs (red, yellow, and green).
The INI-VGC occupies a single node on the E3 Broadband
network and it is connected by a single pair of twisted,
unshielded wire, fiber-optic cable or any combination of
the two. The INI-VGC-UTP is not equipped with fiber-optic
connectors. The INCC Command Center’s INI-VGC module also provides connections for an optional emergency
voice page microphone and a fire fighter telephone handset.
• Listed under UL® Standard 864, 9th Edition
• Listed under UL Standard UL2572 for Mass Notification
• All communication signals and control-by-event sequences
over twisted, unshielded pair of wires or fiber-optic cable
• Distributed architecture, including Style 7 wiring configuration,
allows system components to continue normal operation with
NO loss of function during single line fault conditions
• Each INI-VGC or INI-VGE supports up to six ANU-48 LED drivers or ASM-16 switch modules for a total of 256 switches
• INI-VGC connects to a voice page microphone and fire fighter’s
handset
• Redundant command centers with microphone and fire
fighter’s handset easily configured by adding INCCs
• Uses advanced digital signal processor (DSP) technology for
efficient audio compression and filtering
• Network data transfer rate at 625K baud
• The INI-VGX includes the following features:
The INI-VGC is a fully digital voice/tone generator using
state-of-the-art Digital Signal Processing (DSP) technology to produce the clearest, most audible signal possible.
The INI-VGC provides an output to a local speaker for
message verification and testing.
The E3 Broadband Audio Evacuation System is a peer-topeer, self regenerating, token ring network comprised of
up to 64 individual nodes. In addition, the Addressable
Node Expander (ANX) board expands the network to 122
nodes. Each E3 Broadband node can be spaced on the
network at a maximum distance of 3,000 feet (914.4 m) or
up to an 8dB loss using fiber-optic cable. Built-in isolation
at each node supports Style 4, 6, and 7 network configurations.
- Software-programmable multi-channel digital audio
applications
- One Style 4 Signaling Line Circuit (SLC) supporting up
to 32 addressable speaker circuits
- AOM-2SF used for single channel and 16 address
able phone circuits (AOM-TELF)
- Supports up to 150 watts of audio power (using the
AM-50 Series amplifiers operating at 50 watts of
power @ either 25VRMS or 70.7VRMS output) installed
in a single, wall-mounted cabinet
- 16 message capacity with up to 3 minute duration per
INX and messages are easily field-configured via a
laptop computer
SIGNALING
FM
®
E3 Series is a registered trademark of Honeywell International Inc.
UL® is a registered trademark of Underwriters Laboratories, Inc.
MEA
Approved
FDNY:
3006578 COA-#6077 7165-1703:0125
APPROVED
S1869
City of
Chicago
Approved
Class1
Class2
High Rise
City of
DENVER
Approved
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9020-0648 Rev. G page 1 of 2
©2013 Honeywell International Inc. All rights reserved.
Description (Continued)
Specifications
INI-VGE
INI-VGC, INI-VGE and INI-VGX
The INI-VGE Voice Gateway Module provides command
and control functions for the INCC Command Center. It
provides bulk amplification. A typical INCC assembly consists of an Intelligent Network Interface-Voice Gateway
(INI-VGE) Module and one or more Addressable Switch
Modules (ASM-16). Each INI-VGE can support up to six
ASM-16s for a total of 96 fully programmable switches and
288 LEDs (red, yellow, and green).
The INI-VGE occupies a single node on the E3 Classic network and is connected by a single pair of twisted,
unshielded wire, fiber-optic cable or any combination of the
two. The INI-VGE-UTP is not equipped with the fiber-optic
connectors. The INCC Command Center’s INI-VGE Module also provides connections for an optional emergency
voice paging microphone as well as a fire fighter telephone
handset.
The INI-VGE is a fully digital voice/tone generator using
state-of-the-art Digital Signal Processing (DSP) technology
to produce the clearest, most audible signal possible. The
INI-VGE provides an output capable of driving up to 20
Model AA-100 or AA-120 amplifiers.
INI-VGX
The INI-VGX Transponder Voice Gateway is a component
of the E3 Broadband Audio Evacuation System and an
optional component of the E3 Series Expandable Emergency Evacuation System. It is a multi-function module that
incorporates:
Operating Voltage: 24 VDC (nominal) from the PM-9/PM9G Power Supply
Operating Current: 0.150 amp. supervisory and alarm
Operating
32° to 120° F (0 to 49° C)
Temperature:
Relative Humidity: 0 to 93% (non-condensing)
Supervised
Class 2 Power-Limited
Protocol:
Asynchronous with half-duplex data
flow
Speed:
RS-232 up to 64 KBps
RS-485 up to 128 KBps
Wiring Specifications
(INI-VG Series & INI-VG-UTP Series):
Copper Wire:
16 to 18 AWG twisted-pair,
unshielded. Up to 3,000 ft. (914.4 m)
between each node.
Fiber-Optic Cable Up to 200 microns (optimized for
62.5/125 microns). Up to 8 dB loss
(INI-VG Series):
between each node.
Ordering Information
Part Number
• Network interface using twisted, unshielded wire or
fiber-optic cable
• Fully digital message generator
• One signaling line circuit for local peripheral devices
• Local fire fighter phone riser
INI-VGC
INI-VGC-UTP
It occupies a single DIP switch selectable address on the
network and provides termination points for the network
connection using either a pair of twisted, non-shielded wire
(12 AWG max.) fiber-optic cable, or a combination of the
two. The INI-VGX-UTP is not equipped with fiber-optic connectors.
INI-VGE
The INI-VGX provides command and control for up to four
AM-50 Series amplifiers, operating at 50 watts of power @
either 25VRMS or 70.7VRMS audio output. The amplifiers are
installed in a single cabinet. The INI-VGX uses advanced
Digital Signal Processing (DSP) technology for audio compression and filtering. This feature allows the E3 Broadband System to produce superior clarity for intelligible LIVE
voice paging. The background noise is automatically filtered during voice paging and fire fighter communications
which increases the audibility and eliminates the need for
Push-to-Talk devices.
Description
INI-VG Series:
Command center voice gateway
Command center—(unshielded
twisted-pair only)
INI-VGE
INI-VGE-UTP
INI-VGX
INI-VGX
INI-VGX-UTP
Command center classic voice
gateway
Command center
(unshielded twisted-pair only)
Transponder voice gateway
Transponder voice gateway
(unshielded twisted-pair)
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9020-0648 Rev. G page 2 of 2
www.gamewell-fci.com