FCI-CHG-120

FCI-CHG-120
Battery Charging System
Description
The FCI-CHG-120 is the compatible battery charging system that is designed for use with the AA-100 and the AA120 bulk amplifiers. It is used to charge lead-acid batteries
between 25 and 120 ampere-hours (A/H).
Construction and Application
The FCI-CHG-120 consists of a PC board and a mounting
chassis.
Applications
Use the FCI-CHG-120 Battery Charging System when the
batteries are required for standby between 25 to 120 A/H.
The FCI-CHG-120 has the capability to charge two (2), 26
A/H batteries or two (2) 50 A/H batteries.
Installation
You can install the FCI-CHG-120 within 20 ft. (6.096 m)
from the main fire alarm control panel. There are a variety
of mounting options available for the FCI-CHG-120. The
FCI-CHG-120 can be mounted in the following two backboxes:
• CAB-4 Series backbox
• FCI-LBB Battery backbox (used for remote installations)
CAB-4 Series Backbox Installation
To mount the FCI-CHG-120 to the CAB-4 Series backbox,
do the following:
1. Mount the FCI-CHG-120 in the main power supply
position on the lower left corner of the CAB-4 Series
backbox.
2. Position the FCI-CHG-120 in the lower right location
(usually located where the batteries are mounted) of
the CAB-4 Series backbox.
3. To secure the FCI-CHG-120 to the CAB-4 Series backbox, use self-tapping screws.
FCI-LBB Backbox Remote Installation
To mount the FCI-CHG-120 to the FCI-LBB Series backbox, do the following:
1. Mount the FCI-CHG-120 in the left side of the FCI-LBB
backbox.
2. To secure the FCI-CHG-120 to the FCI-LBB Series
backbox, use self-tapping screws.
Note: Only one (1) 55 A/H battery or two (2) A/H batteries
will mount with the charger board in the BB-FF/FCI-LBB
cabinet. The following list the types of batteries:
- Up to two (2) 26 A/H batteries.
- Up to two (2) 55/60 A/H batteries.
- One (1) 100 A/H battery.
FCI-CHG-120
Features
• Complies with the following UL Standards for fire alarm
systems:
- UL Standard 864 for control units
- UL Standard 1481 for power supplies
• Conforms to NFPA 72 National Fire Alarm Code.
• Operates on any 24-volt FACP that requires the specified batteries and can disable the local charger.
• Charges sealed lead-acid batteries.
• Includes an automatic float-type battery charger.
• Obtains a full float voltage within 48 hours.
• Supports AC fail delay (central station applications) per
the latest NFPA Standards.
• Is rated for batteries of 25 to 120 ampere-hours.
• Provides Form-C Trouble contact and dual outputs for
easy load distribution.
• Offers an optional FCI-LBB battery cabinet.
• Contains the following Diagnostic LEDs:
- Primary AC ON
- Lo Charge
- Charger Trouble
- Battery Voltage Level (3 LEDs)
- Ground Fault
- Low Battery
- Hi Charge
• Produces the following charge amperes hours:
- 24 AH batteries within 9 hours.
- 55/60 AH batteries within 20 hours.
- 120 AH batteries within 38 hours.
SIGNALING
FM
APPROVED
S674
MEA FDNY
Approved Approved
195-97-E, 6026 7165-1703:0125 CS118/
345-02-E,
6911-1703:0118 CS733
Vol. 9
317-01-E
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9021-60722 Rev. C page 1 of 2
©2013 by Honeywell International Inc. All rights reserved.
Installation (Continued)
With the FCI-CHG-120 mounted internally, the following
batteries can be used.
- Up to two 26 A/H batteries
- One 55/60 A/H battery
- One 100 A/H battery
Note: When 100 A/H batteries are required, use an FCILBB to mount each 100 A/H battery. The FCI-CHG-120 can
mount in either of the following backboxes:
- CAB-4 Series backbox
- Third FCI-LBB backbox in this configuration
Ordering Information
Part Number
FCI-CHG-120
BAT-12260
BAT-1250
BAT-121000
FCI-LBB
Specifications
Primary AC
(TB1):
115 VAC, 60 Hz, 2 A. 230 VAC, 50 Hz 1
Form-C Relay
(TB3):
5 A @ 30 VDC
Float Charge
Voltage:
27.6 VDC
Maximum
charging current: 4.5 A
Fuses F1-F3: 15 A
Battery sizes: 25 A/H to 120 A/H
Charging time
(to charge two (2) fully discharged batteries):
25 A/H battery 9 hours charging time
55 A/H battery 20 hours charging time
120 A/H battery 38 hours charging time
Dimensions:
FCI-LBB
Backbox
Door
Description
Battery charger circuit board and
mounting chassis (Includes mounting
hardware and installation instructions)
26 A/H, 12-volt, sealed lead-acid battery
55 A/H, 12-volt, sealed lead-acid battery
100 A/H, 12-volt, sealed lead-acid battery
Battery backbox (black)
The battery backbox holds the following:
- two (2) BAT-12550 55 A/H batteries or
- one (1) BAT-121000 100 A/H battery
24” W x 14” H x 7.75” D
(61 W x 35.6 H x 19.7 D cm)
24.125” W x 14.25” H x 0.063” D
(61.3 W x 36.2 H x 0.16 D cm)
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9021-60722 Rev. C page 2 of 2
www.gamewell-fci.com