9021-60391

PM-9G
Description
PM-9G Power Supply
and Battery Charger
The Gamewell-FCI, PM-9G Power Supply is a 220/240
VAC, 50/60 Hz switching power supply. It provides power
to the Fire Alarm Control Panel, INCC Command Center,
INX Transponder assemblies, and all the E3 Series® components. The PM-9G is a component of the following systems.
• E3 Series Expandable Emergency Evacuation System
• E3 Series Combined Fire Alarm and Mass Notification Systems
• E3 Series Broadband Voice Evacuation System
• NetSOLO® System
It includes 9 amperes of filtered and regulated 24 VDC
FWR. In addition, it has an internal battery charging circuit
that is capable of maintaining up to 55 A/H batteries.
Installation
Typically, the PM-9G Module can be mounted in the
following E3 Series cabinets:
• Cabinet B, Fire Alarm Control Panel
• Cabinet C, Command Center
• Cabinet C, Transponder
• Cabinet D, Command Center
• Cabinet D, Transponder
For information on the PM-9G installation, refer to the following documents:
- E3 Series Installation/Operation Manual, P/N: 9020-0574
- PM-9G Installation Instructions, P/N: 9001-0055
- Mass Notification System Installation/Operation
Manual, P/N: LS10013-000GF-E.
PM-9G
Features
•
Listed under UL® Standard 864, 9th Edition
•
Listed under UL Standard UL2572 for Mass
Notification
•
Includes 9 ampere, filtered, regulated power
supply
•
Provides 1 ampere battery charging current
•
Offers energy and space saving switching
technology
•
Contains an integral battery charger capable of
recharging up to 55 A/H batteries
(Batteries not furnished)
Specifications
Input Voltage:
Input Current:
Output Voltage:
Output Current:
Output Current:
Output Current:
220/240 VAC @ 50/60 Hz
2.4 amps max.
24 VDC FWR
9 amperes Alarm max. continuous
5 amps max. continuous Standby
(when the PM-9G is used with the ILIE3 or the ILI95-E3 Series) (See Note 1)
4 amps max. continuous Standby
(when the PM-9G is used with any
AM-50 Series amplifier) (See Note 1)
1 amp battery charging current
0.050 amp
Output Current:
Alarm Current:
Operating
Temperature:
32° to 120° F (0° to 49° C)
Relative Humidity: 0 to 93% (non-condensing) at 90° F (32° C)
Dimensions:
27 W x 13 H x 5 D cm
(10 1/2” W x 5” H x 2” D)
Supervised and Non Class 2 Power-Limited
Note 1: Continuous standby loads in excess of .560 Amps
up to 5 Amps or 4 Amps may require a Generator Backup
or load shedding during an AC power failure.
Ordering Information
Part Number
PM-9G
29229
®
®
E3 Series and NetSOLO are registered trademarks of Honeywell International Inc.
®
UL is a registered trademark of Underwriters Laboratories Inc.
Description
Power supply and battery charger
AC Line Filter Kit
SIGNALING
MEA
Approved
S1869 Vol. 14 FDNY: 7165-1703:0125
S1949 Vol. 19 COA #6077
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9021-60391 Rev. H page 1 of 1