PDRP-1001 Series Pre-Action/Deluge Control Panel

S P R I N K L E R
S Y S T E M S
M O N I T O R I N G
PDRP-1001 Series
Pre-Action/Deluge
Control Panel
Models Available
PDRP-1001 Pre-Action/Deluge Panel
PDRP-1001E (International, 230V)
PDRP-1001
Control Panel
PDRP-1001A (Canadian)
Optional Accessories Available
4XZM Zone Relay Module
4XTM Transmitter Module
4XLM LED Interface Module
4XMM Volt/Amp Meter
RZA-4X Supervised Remote Annunciator
requires LED interface module (4XLM)
NOTI•FIRE 911A Digital Communicator
Product Overview
2 initiating device circuits (Style B/D)
Features. Battery/earth fault supervision and fuse protection on all indicating/
2 notification appliance circuits
(Style Y/Z)
release circuits. Extensive transient protection. 6.5 AH to 15 AH battery
options, up to 90 hours standby. Output circuits protected against false activations by 2-step command sequence and watchdog timer to supervise microprocessor. Last event recall feature to trap intermittent trouble conditions. Nonresettable regulated 24 VDC power output and RMS regulated 24 VDC output
power, 2.25 amperes. 230 VAC, 50 Hz international option. 4-wire smoke
detector power output. Slide-in labels for zone identification.
2 release circuits (Style Y)
Waterflow input (Style B/D)
Dual hazard option
(combined or split release)
Supervisory input option (Style B/D)
Distinct audible indications for: 1 zone
in alarm; 2 zones in alarm; release
Power-limited on all circuits except
municipal box output
Alarm and trouble resound
Battery/earth fault supervision
Last event recall feature to trap
intermittent trouble conditions
Code Compliance. Complies with NFPA 72 Local, Auxiliary, Remote Station,
Control Station, and Proprietary Protective and Central Station Signaling Systems.
Also meets NFPA13 Installation of Sprinkler Systems, NFPA15 Water Spray Fixed
Systems, and NFPA16 Deluge Foam/Water and Foam-Water Spray Systems.
Optional Meters. Voltage and current meters (4XMM): The 4XMM provides a
voltmeter to measure the voltage across the batteries, and an ammeter to measure the charging current to the batteries.
Fuse protection on all indicating/release
circuits
Discharge timer: 0, 10, or 15 minutes
Disable/enable controls per initiating zone
Cross-zone option
S6352
CS733
OV1A8.AY
419-91-E
7165-1209:19
General Specifications
Circuit Specifications
Dimensions
Door: 16.125″H × 14.625″W
Backbox: 16.0″H × 14.5″W × 4.75″D
Cabinet: 16.125″H × 14.625″W ×
5.375″D
Electrical Specifications
120 VAC, 60 Hz, 1.2 A
Input Terminals
14 AWG with 600 V insulation
Output Circuits
(optional auxiliary relays track these
four circuits)
1. Alarm/Waterflow Bell (Style Y/Z)
Initiating Circuit Specifications
General
Power-limited circuitry
Operation: Style B (Class B) / Style D
(Class A)
Electrical Specifications
Standby Voltage
24 VDC (ripple = 10 mV peak-to-peak),
5 mA
Alarm Current
15 mA minimum
Short Circuit Current
40 mA maximum
Maximum Detector Current In Standby
2 mA (peak) per zone
Maximum Loop Resistance
200 ohms
EOL Resistor
4.7 kohms, 1⁄ 2 watt
2. Waterflow/Supervisory Bell (Style
Y/Z)
3. Releasing Circuit 1 (Style Y)
4. Supervisory Bell/Release Circuit 2
(Style Y)
Front Panel Control Switches
Switch 1— Tone Silence
Switch 2— Alarm Silence
Switch 3— Alarm Activate
Switch 4— System Reset
Terminal Specifications
Four-wire Smoke Detector Power
Output Maximum Current
200 mA RMS Regulated 24 VDC Power
Output
Non-resettable 24 VDC Power Output
Maximum DC Current
200 mA (subtracted from four-wire
smoke power).
Maximum Current
0.5 A (subtracted from notification
appliance power dedicated to all output circuits).
Notification/Releasing Circuit Specifications
General
Power-limited circuitry
Total Current
2.25 amps max.
Electrical Specifications
Voltage
24 VDC RMS regulated (not filtered)
Maximum Signaling Current Per Circuit
1.5 amps
Maximum Voltage Drop Due To Wiring
2 VDC
Input Circuits
1. Detector Circuit 1/Manual Release
(Style B/D)
2. Detector Circuit 2 (Style B/D)
3. Waterflow (Style B/D)
4. Supervisory (Style B/D)
Fuses
2 AG, 4 amps
EOL Resistor
4.7 kohms, 1⁄ 2 watt (part no. 71252)
Field Program Selections
6-position DIP-switch To Select:
1. Two-zone, single hazard operation
2. Two-zone, single hazard operation (cross zoned)
3. Two-zone, dual hazard operation (combined release)
4. Two-zone, dual hazard operation (split release)
5. Discharge times: 0, 10, or 15 minutes
NFPA Standard Specified Requirements
Digital Communicator
NOTI•FIRE 911A
For Central Station service
(NFPA 72 Central Station
Protective Signaling System)
or Remote Station Service
(NFPA 72 Remote Station
Protective Signaling System)
Transmitter Module (4XTM)
For Local Energy Municipal
Box service (NFPA-72
Auxiliary Protective Signaling
System):
Supervisory Current
5.0 mA
Trip Current
0.35 amps (subtracted from
indicating appliance power)
Total Wire Resistance
Between Panel And Trip Coil
3 ohms
Coil Voltage
3.65 VDC
Reverse Polarity Output
Voltage
24 VDC
Coil Resistance
14.6 ohms
For Remote Station Service
(NFPA-72 Remote Station
Protective Signaling System)
Maximum current allowed for
both circuits shall not exceed
10 mA per circuit.
Alarm/Trouble Relays
Optional Boards
The PDRP-1001 has mounting slots for two option
boards. Any two of the three option modules may
be installed.
Zone Relay Module (4XZM)
The Zone Relay module provides Form-C general
alarm and trouble contacts and the following
Form-C relays:
Alarm/Waterflow Bell
Waterflow/Supervisory Bell
Releasing Circuit 1
Supervisory Bell/Release Circuit 2
Dry, Form C Contacts rated for:
2.0 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
Relays can be silenceable/non-silenceable by jumper
Transmitter Module (4XTM)
The Transmitter module option provides a supervised
output for local energy municipal box transmitter
(for NFPA-72 Auxiliary Protective Signaling System)
and alarm and trouble reverse polarity (for NFPA-72
Remote Station Protective Signaling System). Also
included is a DISABLE switch and disable trouble
LED. A jumper option allows the reverse polarity
circuit to open with a System Trouble condition if no
alarm condition exists.
LED Interface Module (4XLM):
The module supports the RZA-4X Remote
Annunciator module. The LED Interface Module
mounts to the main board occupying one of the two
option connectors. Annunciator LED wiring is supervised for opens. Faults will activate System Trouble
condition.
Dry Form-C Contacts Rating
2.0 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
Remote Annunciator
RZA-4X
The Remote Annunciator mounts on a standard
single-gang box and provides the following:
System Trouble LED (yellow)
Local Piezo Sounder
Silence Switch (for local sounder)
Alarm/Waterflow Bell LED (red)
Waterflow/Supervisory Bell LED (red)
Releasing Circuit 1 LED (red)
Supervisory Bell/Release Circuit 2 LED (red)
Note: The Remote Annunciator requires the use of an
LED interface module.
System Sensor Sales and Service
System Sensor Headquarters
3825 Ohio Avenue
St. Charles, IL 60174
Ph: 800/SENSOR2
Fx: 630/377-6495
www.systemsensor.com
System Sensor Canada
Ph: 905.812.0767
Fx: 905.812.0771
System Sensor in China
Ph: 86.29.8832.0119
Fx: 86.29.8832.5119
System Sensor – Far East
Ph: 85.22.191.9003
Fx: 85.22.736.6580
System Sensor – India
Ph: 91.124.237.1770 x.2700
Fx: 91.124.237.3118
System Sensor Europe
Ph: 44.1403.891920
Fx: 44.1403.891921
System Sensor in Singapore
Ph: 65.6273.2230
Fx: 65.6273.2610
System Sensor – Australia
Ph: 613.54.281.142
Fx: 613.54.281.172
System Sensor – Russia
Ph: 70.95.937.7982
Fx: 70.95.937.7983
© 2004 System Sensor. The company reserves the right to change product specifications without notice.
A05-0954-004•10/04•#1360