S P R I N K L E R S Y S T E M S M O N I T O R I N G PDRP-1001 Series Pre-Action/Deluge Control Panel Models Available PDRP-1001 Pre-Action/Deluge Panel PDRP-1001E (International, 230V) PDRP-1001 Control Panel PDRP-1001A (Canadian) Optional Accessories Available 4XZM Zone Relay Module 4XTM Transmitter Module 4XLM LED Interface Module 4XMM Volt/Amp Meter RZA-4X Supervised Remote Annunciator requires LED interface module (4XLM) NOTI•FIRE 911A Digital Communicator Product Overview 2 initiating device circuits (Style B/D) Features. Battery/earth fault supervision and fuse protection on all indicating/ 2 notification appliance circuits (Style Y/Z) release circuits. Extensive transient protection. 6.5 AH to 15 AH battery options, up to 90 hours standby. Output circuits protected against false activations by 2-step command sequence and watchdog timer to supervise microprocessor. Last event recall feature to trap intermittent trouble conditions. Nonresettable regulated 24 VDC power output and RMS regulated 24 VDC output power, 2.25 amperes. 230 VAC, 50 Hz international option. 4-wire smoke detector power output. Slide-in labels for zone identification. 2 release circuits (Style Y) Waterflow input (Style B/D) Dual hazard option (combined or split release) Supervisory input option (Style B/D) Distinct audible indications for: 1 zone in alarm; 2 zones in alarm; release Power-limited on all circuits except municipal box output Alarm and trouble resound Battery/earth fault supervision Last event recall feature to trap intermittent trouble conditions Code Compliance. Complies with NFPA 72 Local, Auxiliary, Remote Station, Control Station, and Proprietary Protective and Central Station Signaling Systems. Also meets NFPA13 Installation of Sprinkler Systems, NFPA15 Water Spray Fixed Systems, and NFPA16 Deluge Foam/Water and Foam-Water Spray Systems. Optional Meters. Voltage and current meters (4XMM): The 4XMM provides a voltmeter to measure the voltage across the batteries, and an ammeter to measure the charging current to the batteries. Fuse protection on all indicating/release circuits Discharge timer: 0, 10, or 15 minutes Disable/enable controls per initiating zone Cross-zone option S6352 CS733 OV1A8.AY 419-91-E 7165-1209:19 General Specifications Circuit Specifications Dimensions Door: 16.125″H × 14.625″W Backbox: 16.0″H × 14.5″W × 4.75″D Cabinet: 16.125″H × 14.625″W × 5.375″D Electrical Specifications 120 VAC, 60 Hz, 1.2 A Input Terminals 14 AWG with 600 V insulation Output Circuits (optional auxiliary relays track these four circuits) 1. Alarm/Waterflow Bell (Style Y/Z) Initiating Circuit Specifications General Power-limited circuitry Operation: Style B (Class B) / Style D (Class A) Electrical Specifications Standby Voltage 24 VDC (ripple = 10 mV peak-to-peak), 5 mA Alarm Current 15 mA minimum Short Circuit Current 40 mA maximum Maximum Detector Current In Standby 2 mA (peak) per zone Maximum Loop Resistance 200 ohms EOL Resistor 4.7 kohms, 1⁄ 2 watt 2. Waterflow/Supervisory Bell (Style Y/Z) 3. Releasing Circuit 1 (Style Y) 4. Supervisory Bell/Release Circuit 2 (Style Y) Front Panel Control Switches Switch 1— Tone Silence Switch 2— Alarm Silence Switch 3— Alarm Activate Switch 4— System Reset Terminal Specifications Four-wire Smoke Detector Power Output Maximum Current 200 mA RMS Regulated 24 VDC Power Output Non-resettable 24 VDC Power Output Maximum DC Current 200 mA (subtracted from four-wire smoke power). Maximum Current 0.5 A (subtracted from notification appliance power dedicated to all output circuits). Notification/Releasing Circuit Specifications General Power-limited circuitry Total Current 2.25 amps max. Electrical Specifications Voltage 24 VDC RMS regulated (not filtered) Maximum Signaling Current Per Circuit 1.5 amps Maximum Voltage Drop Due To Wiring 2 VDC Input Circuits 1. Detector Circuit 1/Manual Release (Style B/D) 2. Detector Circuit 2 (Style B/D) 3. Waterflow (Style B/D) 4. Supervisory (Style B/D) Fuses 2 AG, 4 amps EOL Resistor 4.7 kohms, 1⁄ 2 watt (part no. 71252) Field Program Selections 6-position DIP-switch To Select: 1. Two-zone, single hazard operation 2. Two-zone, single hazard operation (cross zoned) 3. Two-zone, dual hazard operation (combined release) 4. Two-zone, dual hazard operation (split release) 5. Discharge times: 0, 10, or 15 minutes NFPA Standard Specified Requirements Digital Communicator NOTI•FIRE 911A For Central Station service (NFPA 72 Central Station Protective Signaling System) or Remote Station Service (NFPA 72 Remote Station Protective Signaling System) Transmitter Module (4XTM) For Local Energy Municipal Box service (NFPA-72 Auxiliary Protective Signaling System): Supervisory Current 5.0 mA Trip Current 0.35 amps (subtracted from indicating appliance power) Total Wire Resistance Between Panel And Trip Coil 3 ohms Coil Voltage 3.65 VDC Reverse Polarity Output Voltage 24 VDC Coil Resistance 14.6 ohms For Remote Station Service (NFPA-72 Remote Station Protective Signaling System) Maximum current allowed for both circuits shall not exceed 10 mA per circuit. Alarm/Trouble Relays Optional Boards The PDRP-1001 has mounting slots for two option boards. Any two of the three option modules may be installed. Zone Relay Module (4XZM) The Zone Relay module provides Form-C general alarm and trouble contacts and the following Form-C relays: Alarm/Waterflow Bell Waterflow/Supervisory Bell Releasing Circuit 1 Supervisory Bell/Release Circuit 2 Dry, Form C Contacts rated for: 2.0 amps @ 30 VDC (resistive) 0.5 amps @ 30 VAC (resistive) Relays can be silenceable/non-silenceable by jumper Transmitter Module (4XTM) The Transmitter module option provides a supervised output for local energy municipal box transmitter (for NFPA-72 Auxiliary Protective Signaling System) and alarm and trouble reverse polarity (for NFPA-72 Remote Station Protective Signaling System). Also included is a DISABLE switch and disable trouble LED. A jumper option allows the reverse polarity circuit to open with a System Trouble condition if no alarm condition exists. LED Interface Module (4XLM): The module supports the RZA-4X Remote Annunciator module. The LED Interface Module mounts to the main board occupying one of the two option connectors. Annunciator LED wiring is supervised for opens. Faults will activate System Trouble condition. Dry Form-C Contacts Rating 2.0 amps @ 30 VDC (resistive) 0.5 amps @ 30 VAC (resistive) Remote Annunciator RZA-4X The Remote Annunciator mounts on a standard single-gang box and provides the following: System Trouble LED (yellow) Local Piezo Sounder Silence Switch (for local sounder) Alarm/Waterflow Bell LED (red) Waterflow/Supervisory Bell LED (red) Releasing Circuit 1 LED (red) Supervisory Bell/Release Circuit 2 LED (red) Note: The Remote Annunciator requires the use of an LED interface module. System Sensor Sales and Service System Sensor Headquarters 3825 Ohio Avenue St. Charles, IL 60174 Ph: 800/SENSOR2 Fx: 630/377-6495 www.systemsensor.com System Sensor Canada Ph: 905.812.0767 Fx: 905.812.0771 System Sensor in China Ph: 86.29.8832.0119 Fx: 86.29.8832.5119 System Sensor – Far East Ph: 85.22.191.9003 Fx: 85.22.736.6580 System Sensor – India Ph: 91.124.237.1770 x.2700 Fx: 91.124.237.3118 System Sensor Europe Ph: 44.1403.891920 Fx: 44.1403.891921 System Sensor in Singapore Ph: 65.6273.2230 Fx: 65.6273.2610 System Sensor – Australia Ph: 613.54.281.142 Fx: 613.54.281.172 System Sensor – Russia Ph: 70.95.937.7982 Fx: 70.95.937.7983 © 2004 System Sensor. The company reserves the right to change product specifications without notice. A05-0954-004•10/04•#1360