Data Sheet

Flex Series
GWF402 and GWF404
Two and Four Zone Conventional
Fire Alarm Control Panels
Description
The Flex 402 is a two zone fire alarm control panel (FACP)
and the Flex 404 is a four zone FACP. These control panels provide reliable fire signaling protection for small to
medium-sized retail, office, multi-family, or other similar
commercial or institutional buildings.
The Initiating Device Circuits (IDCs) for the Flex Series
panels are categorized as Class 2 Power-Limited and
operate in Class B (Style B). Each panel is compatible with
the following types of conventional input devices.
• two-wire smoke detectors • water flow devices
• four-wire smoke detectors • tamper switches
• pull stations
In addition, each panel is compatible with other normallyopen contact devices. These devices include the System
Sensor i3™ Series microprocessor-based detectors with
advanced features like drift compensation, maintenance
alert and freeze warning.
Note: For a listing of compatible devices, refer to the
Device Compatibility Document P/N: 52195.
The outputs include one notification appliance circuit
(NAC) on the Flex 402 and two NACs on the Flex 404.
NACs are categorized as Class 2 Power-limited and operate in Class B (Style Y). Each FACP has a Form-C Alarm
and Trouble relay and 24 VDC special applications resettable power. In addition, the Flex 404 has a Form-C Supervisory relay and a special application non-resettable power
output. The FACP supervises wiring, AC voltage and battery level.
The activation of a compatible smoke detector or any normally-open fire alarm initiating device will do the following:
• Activate the audible and the visual signaling devices.
• Illuminate an indicating LED.
• Sound the piezo sounder at the FACP.
• Activate the FACP alarm relay.
• Operate any optional modules used to notify a remote
station.
• Initiate an auxiliary control function.
GWF402/G (left) and GWF404 (right)
Features
• Listed under UL® Standard 864, 9th Edition.
• Flex 402: Two Class B (Style B) IDC zones, one Class B
(Style Y) NACs.
• Flex 404: Four Class B (Style B) IDC zones, two Class B
(Style Y) NACs.
• Optional NAC Class A converter module (Flex 404).
• Offers the following NAC synchronization and
programmability features:
– ADA compliant strobe synchronization.
– ANSI audible signals as required by NFPA 72.
– Silence inhibit, auto-silence, non-silenceable.
– Selective Silence: mute horns, keep strobes lit.
– Temporal or steady signal.
• Displays silent or audible walk test from front keypad.
• Zone disable, alarm verification selectable per zone.
• Includes the following controls:
– Acknowledge
– Silence
– Alarm
– Walk Test
– Reset
– Zone enable/disable
• Contains the following LED indicators:
– Alarm
– NAC fault
– Supervisory
– System/Power Trouble
– Maintenance
– Walk Test
– Trouble (one per zone)
– Alarm Silence
– AC
– Charger/Battery/
– NAC/Zone Disable
Earth Fault (on pcb)
• Provides alarm verification.
• Uses a low AC voltage sense,automatic battery charger.
• Has a Piezo sounder for alarm, trouble, and supervisory.
SIGNALING
MEA
i 3™ is a trademark of Honeywell International Inc.
UL® is a registered trademark of Underwriter’s Laboratories Inc.
Approved
FDNY:
S521 COA-# 366-04-E 7300-1703:0161
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9021-60292 Rev. D page 1 of 2
©2013 Honeywell International Inc. All rights reserved.
Options
Specifications (Continued)
CAC-4
Used to convert Class B (Style B) IDCs to
Class A (Style D) and Class B (Style Y)
NACs to Class A (Style Z).
Mounts in FACP. Flex 404 only.
XRM-24
Second 100VA transformer for maximum
accessory power.
Mounts in FACP. Flex 404 only.
4XTMF
Transmitter module provides output for the
local energy municipal box transmitter and
alarm and trouble reverse polarity.
Mounts in FACP. Flex 402 & Flex 404.
4XZMF
Zone relay module provides Form-C relays:
Alarm Zones 1, 2, 3, 4, System Alarm,
Trouble. Mounts in FACP. Flex 404 only.
4XLMF
LED interface module supports the
GWSAN-404 remote annunciator,
supervises annunciator wiring for open
conditions. Mounts in FACP. Flex 404 only.
411UD
Four input/channel, dual line, digital alarm
communicator/transmitter (DACT). Input/
channels are compatible with normally
open relay contacts, are supervised and
fully programmable. Interfaces with public
switched telephone networks and
compatible with most central station receivers. Flex 404 only.
GWSAN-404 Remote annunciator mounts in single-gang
electrical box, provides LED indication of
Alarm Zones 1, 2, 3, 4; and System
Trouble. Flex 404 only.
Circuits (NAC) (Continued)
Operating Voltage: Maximum signaling current: 2.5 A
total (5.0 A Flex 404 with an optional
transformer).
Maximum Line
Impedance:
1.5 volt drop
Form-C Relays:
Contact Ratings:
Resettable:
Operating voltage: nominal 24 VDC
Power:
Class 2 Power-Limited circuitry
Maximum
Available Current: 500 mA
Non-resettable:
Operating voltage: nominal 24 VDC
Power:
Class 2 Power-Limited circuitry
Maximum
Available Current: 500 mA
Cabinet Dimensions:
Door:
15.3" x 14.7" x 0.3"
(39 x 37 x 1 cm)
Backbox:
15.0" x 14.5" x 3.0"
(38 x 37 x 8 cm)
Ordering Information
GWF402
GWF404
71252
52194
Specifications
AC Power:
Battery:
Initiating Device:
Circuits (IDC):
Operation:
Power:
Operating
Voltage:
Alarm Current:
Short Circuit
Current:
Standby Current:
Maximum Loop
Resistance:
Notification:
120 VAC, 50/60Hz, 2.3 A
Max. charging circuit: 27.6 VDC@
0.8A Max. charger capacity: 18 Ah
(Two 7Ah batteries fit inside the FACP).
Alarm zones 1 & 2
(Flex 402 / Flex 404)
Alarm zones 3 & 4 (Flex 404 only)
All zones Style B (Class B)
Class 2 Power-Limited circuitry
Nominal 20 VDC
15 mA minimum
CAC-4
XRM-24
4XTMF
4XZMF
4XLMF
411UD
Circuits (NAC):
Operation:
Class B (Style Y)
Power:
Class 2 Power-Limited circuitry
Operating Voltage: Nominal 24 VDC
Flex 402 conventional FACP, 2 zones,
120 VAC, red
Flex 404 conventional FACP, 4 zones,
120 VAC, red
EOL resistor, 4.7K ohm, ½ watt
Flex 402 and Flex 404 Installation &
Operation Manual
Options:
40 mA maximum
4 mA
100 ohms
One NAC: Flex 402
Two NACs:Flex 404
Trouble, Alarm
(Supervisory, Flex 404)
2 A @ 30 VAC (resistive)
PRO-411
GWSAN-404
BB-17F
Class A converter for initiating device
circuits and notification appliance circuits (cannot be used on Flex 402).
Transformer, expands NAC circuit
power from 3 to 5 amps.
Transmitter module for remote station
output or municipal box connection.
Relay module, four relays-by-zone,
alarm and trouble contacts, 24VDC.
Remote annunciator driver, 24 VDC,
supports GWSAN-404.
Four channel dual slave programmer
DACT, Form C relay and upload/
download capability; with enclosure,
requires PRO-411.
Programmer, use with 411UD,
411UDAC.
LED remote annunciator for Flex 404,
four alarms, one trouble
(requires 4XLMF).
Battery box, houses 2 batteries
(7-18 Ah max.).