Velociti® Series AOM-2SF Addressable Output Relay Supervised Control Module Description The Gamewell-FCI Velociti® Series addressable output supervised control module (AOM-2SF) allows a Gamewell-FCI analog addressable fire alarm control panel to switch an external power supply, such as a DC supply or audio amplifier (up to 80 VRMS) to notification appliances. The AOM-2SF notification appliance circuit can be wired either Class A (Style Z) or Class B (Style Y). It also supervises the wiring to the connected loads and reports their status to the panel as NORMAL, OPEN or SHORT CIRCUIT. The module contains a panel controlled LED. The Velociti® Series use a communication protocol that substantially increases the speed of communication between the SLC devices and certain Gamewell-FCI analog addressable fire alarm control panels. These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel’s microprocessor stops the group poll and concentrates on the single device. The net result is a superior response speed up to five times greater than the earlier designs. The AOM-2SF module is designed for installation in the signaling line circuit of any Gamewell-FCI analog addressable fire alarm control panel. The signaling line circuits of Gamewell-FCI analog addressable fire alarm control panels are designed to accommodate up to 159 modules per circuit. The AOM-2SF is designed to mount in a 4” (10.16 cm) square junction box 2 1/8” (5.5 cm) deep. Table 1 lists the relay contact ratings. Current Maximum Load Rating Voltage Description 3A 30 VDC Resistive 2A 30 VDC Resistive 0.9A 110 VDC Resistive 0.5A 125 VAC Resistive 0.5A 30 VDC Inductive (L/R=5ms) 1A 30 VDC Inductive (L/R=2ms) 0.5A 125 VAC Inductive (PF=.35) 0.7A 75 VAC Inductive Application Non-Coded Coded Non-Coded Non-Coded Coded Coded Non-Coded Non-Coded AOM-2SF Features • Listed under UL® Standard 864 and UL2572 for Mass Notification. • Designed as a compact size to allow easy installation. • Includes Class A, Style Z, or Class B, Style Y notification appliance circuit. • Accommodates audio amplifiers up to 80 VRMS. • FM Listed as suitable for a releasing device service. • Includes a bicolor LED that flashes green whenever the module is addressed, and lights steady red upon activation*. *Note: Only the red LED is operative in panels that do not operate in Velociti® mode. Specifications Supervisory Current: .000375 amps Alarm Current: .0065 amps Operating Temperature: 32° to 120° F (0° to 49° C) Relative Humidity: 10 to 93% relative humidity (non-condensing) Dimensions: 4 1/2” H x 4” W x 1 1/4” D (11.4 H x 10.2 W x 3.2 D cm) Ordering Information Part Number AOM-2SF Description Addressable output supervised control module SIGNALING Table 1: Relay Contact Ratings FM Velociti® is a registered trademark of Honeywell International Inc. UL® is a registered trademark of Underwriters Laboratories Inc. APPROVED MEA Approved S1949 3023594 227-03-E Vol.IV 7300-1703:0102 GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. www.gamewell-fci.com 9020-0627 Rev. G page 1 of 1 ©2014 Honeywell International Inc. All rights reserved.