Data Sheet

SpectrAlert®
Advance
Description
SpectrAlert® Advance selectable-output chimes and chime/
strobes are private-mode notification appliances used to
alert trained personnel to investigate possible emergency
situations and to take appropriate action. Security guard
and nurse workstations are ideal locations for chime products.
SpectrAlert Advance chimes and chime/strobes are rich
with features guaranteed to cut installation times and maximize profits. The SpectrAlert Advance series of notification
appliances is designed to simplify your installations, with
features such as: plug-in designs, instant feedback messages to ensure correct installation of individual devices,
and seven (7) field-selectable candela settings for chime/
strobes.
More specifically, when installing Advance products, first
attach a universal mounting plate to a four-inch (10.16 cm)
square, four-inch octagonal, single-gang, or double-gang
junction box. Then, connect the notification appliance circuit wiring to the SEMS terminals on the mounting plate.
Finally, attach the chime or chime/strobe to the mounting
plate by inserting the product’s tabs in the mounting plate’s
grooves. The device will rotate into position, locking the
product’s pins into the mounting plate’s terminals. The
device will temporarily hold in place with a catch until it is
secured with a captive mounting screw.
Selectable Output CHR, CHW Chimes
and CHSR, CHSW Chime/Strobes
7089pho2.tif
7089pho1.tif
Chime/Strobe (CHSR)
Chime (CHW)
Features
• Plug-in design
• Shorting spring on mounting plate for pre-installation
continuity check
• Captive mounting screw
• Torx screw for tamper resistance
• Field-selectable candela settings: 15, 15/75, 30, 75, 95,
110, 115
• Automatic selection of 12- or 24-volt operation at 15 and
15/75 candela
• Minimal intrusion into the backbox
• Rotary switch for tone selection
SpectrAlert Advance products offer the following options:
• 12 or 24 volts DC.
• Two volume settings
• At 24 volts, 15, 15/75, 30, 75, 95, 110, or 115 candela by
• Electrically compatible with existing SpectrAlert®
products
way of rear-mounted slide-switch and front-view window.
• Chime tones and volume by way of rotary switch.
An ISO 9001-2000 Company
SIGNALING
MEA
Sync•Circuit™ is a trademark, and SpectrAlert® and System Sensor are registered trademarks of Honeywell International Inc. ©2012.
Approved
S4011
452-05-E 7125-1643:0188
7125-1643:0189
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
CS-2540 Rev. A page 1 of 3
©2012 Honeywell International Inc. All rights reserved.
Engineering Specifications
Specifications
SpectrAlert® Advance chimes and chime/strobes shall
mount on a standard 4.0" x 4.0" x 1.5" (10.16 x 10.16 x 3.81 cm)
backbox, 4.0" (10.16 cm) octagonal backbox, single-gang
2.0" x 4.0" x 1.875" (5.08 x 10.16 x 4.763 cm) backbox, or double-gang backbox. A universal mounting plate shall be
used for mounting products. The notification appliance circuit wiring shall terminate at the universal mounting plate.
Also, SpectrAlert Advance products, when used with the
Sync•Circuit™ Module accessory, shall be powered from a
non-coded notification appliance circuit output and shall
operate on a nominal 12 or 24 volts DC. When used with
the Sync•Circuit Module, 12-volt rated notification appliance circuit outputs shall operate between 9 and 17.5 volts;
24-volt rated notification appliance circuit outputs shall
operate between 17 and 33 volts. Indoor SpectrAlert
Advance products shall operate between 32°F and 120°F
(0°C and 49°C) from a regulated DC, or full-wave-rectified,
unfiltered power supply. Chime/strobes shall have fieldselectable candela settings of 15, 15/75, 30, 75, 95, 110,
and 115.
Standard operating
temperature:
32°F to 120°F (0°C to 49°C).
Humidity range:
10% to 93% non-condensing
(indoor products).
Strobe flash rate: 1 flash per second.
Nominal voltage: Regulated 12 VDC/FWR or regulated
24 VDC/FWR.
NOTE: Full Wave Rectified (FWR)
voltage is a non-regulated, time-varying power source that is used on
some power supply and panel outputs.
Operating voltage
range:
8 V to 17.5 V (12 V nominal); or 16 V
to 33 V (24 V nominal).
NOTE: CHS products will operate at
12 V nominal only for 15 cd and 15/
75 cd.
Input terminal wire
gauge:
12 to 18 AWG
(3.31 to 0.821 mm²).
Chime/Strobe Combination
The chime/strobe shall be a System Sensor SpectrAlert
Advance Model _______ Listed to UL Standards 1638 and
464. The chime/strobe shall comply with the Americans
with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating
voltage range. The strobe light shall consist of a xenon
flash tube and associated lens/reflector system. The chime
shall have two audibility options and an option to switch
between a temporal three-pattern and a non-temporal
(continuous) pattern. These options are set by a multiple
position switch.
Synchronization Module
The module shall be a System Sensor Sync•Circuit
_______ Listed to UL STD 464 and shall be approved for
fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz and chimes at Temporal 3. Also,
while operating the strobes, the module shall silence the
chimes on chime/strobe models over a single pair of wires.
The module shall mount to a 4.688" x 4.688" x 2.125"
(11.906 x 11.906 x 5.398 cm) backbox. The module shall also
control two Style Y (Class B) circuits or one Style Z (Class
A) circuit. The module shall synchronize multiple zones.
Daisy-chaining two or more synchronization modules
together will synchronize all the zones they control. The
module shall not operate on a coded power supply.
Chime/strobe
dimensions
(including lens):
Chime
dimensions:
5.6" H x 4.7" W x 2.5" D
(14.2 cm H x 11.9 cm W x 6.4 cm D).
5.6" H x 4.7" W x 1.3" D
(14.2 cm H x 11.9 cm W x 3.3 cm D).
Ordering Information:
Part Number
CHR:
CHW:
CHSR:
CHSW:
BBS-2:
BBSW-2:
Description
Chime, red.
Chime, white.
Chime/strobe, red.
Chime/strobe, white.
Backbox skirt, wall, red.
Backbox skirt, wall white.
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
CS-2540 Rev. A page 2 of 3
www.gamewell-fci.com
Current Draw, UL Maximum (mA RMS)
8 - 17.5 Volts
15 cd 15/75 cd
Input, Pattern, dB Out
DC, 1-Second Chime, HIGH
DC, 1-Second Chime, LOW
DC, 1/4-Second Chime, HIGH
DC, 1/4-Second Chime, LOW
DC, Temporal Chime, HIGH
DC, Temporal Chime, LOW
DC, 5-Second Whoop, HIGH
DC, 5-Second Whoop, LOW
DC, One-Time Chime
FWR, 1-Second Chime, HIGH
FWR, 1-Second Chime, LOW
FWR, 1/4-Second Chime, HIGH
FWR, 1/4-Second Chime, LOW
FWR, Temporal Chime, HIGH
FWR, Temporal Chime, LOW
FWR, 5-Second Whoop, HIGH
FWR, 5-Second Whoop, LOW
FWR, One-Time Chime
131
131
129
129
125
129
133
130
127
128
127
129
128
128
125
136
132
127
15 cd
15/75 cd
30 cd
65
64
66
64
64
65
70
66
64
72
71
72
71
71
71
84
77
72
76
75
75
74
74
75
81
77
76
82
81
82
81
81
81
93
86
82
94
92
95
91
91
92
99
95
93
98
97
99
97
97
97
110
102
97
142
142
142
142
142
141
145
143
141
150
150
149
149
148
147
152
150
147
Tone Selection
Chime tone selection is accomplished by using the rotary
switch on the back of the product. The current draw and
sound measurements for various chime tones are listed in
the following tables.
1-Second Chime
1-Second Chime
1/4-Second Chime
1/4-Second Chime
Temporal Chime
Temporal Chime
5-Second Whoop
5-Second Whoop
One Test Chime
dB
HIGH
LOW
HIGH
LOW
HIGH
LOW
HIGH
LOW
HIGH
Setting
1
2
3
4
5
6
7
8
9
8-17.5 Volts 16 - 33 Volts
DC FWR DC FWR
34 mA
30 mA
34 mA
31 mA
30 mA
30 mA
32 mA
30 mA
48 mA
50 mA
51 mA
51 mA
51 mA
50 mA
47 mA
52 mA
40 mA
49 mA
58 mA
51 mA
50 mA
50 mA
48 mA
50 mA
34 mA
34 mA
50 mA
51 mA
54 mA
50 mA
52 mA
54 mA
51 mA
54 mA
52 mA
50 mA
160
157
159
155
156
155
165
160
156
158
157
160
154
157
156
170
161
157
185
183
184
181
181
180
189
186
182
183
182
183
179
179
180
193
184
181
110 cd
115 cd
207
203
205
204
205
200
210
206
203
202
202
203
196
199
200
212
203
200
213
212
212
211
211
209
217
214
210
210
210
211
205
206
206
220
214
210
Chime Patterns
Chime Current Draw,
UL Maximum (mA RMS)
Sound Pattern
16 - 33 Volts
75 cd
95 cd
Repetition Rate
1-Second Chime
1-Second Chime
1/4-Second Chime
1/4-Second Chime
Temporal Chime
Temporal Chime
5-Second Whoop
5-Second Whoop
One Test Chime
dB Out
HIGH
LOW
HIGH
LOW
HIGH
LOW
HIGH
LOW
HIGH
SpectrAlert Advance Chime/Strobe Dimensions:
Sound Output (dBA), Chime and Chime/Strobe
Switch
Setting Sound Pattern
1 1-Second Chime
2 1-Second Chime
3 1/4-Second Chime
4 1/4-Second Chime
5 Temporal Chime
6 Temporal Chime
7 5-Second Whoop
8 5-Second Whoop
9 One Test Chime
dB
HIGH
LOW
HIGH
LOW
HIGH
LOW
HIGH
LOW
HIGH
DC
58 dBA
53 dBA
63 dBA
58 dBA
62 dBA
55 dBA
68 dBA
62 dBA
57 dBA
FWR
59 dBA
54 dBA
64 dBA
59 dBA
64 dBA
57 dBA
71 dBA
64 dBA
55 dBA
DC
61 dBA
55 dBA
66 dBA
60 dBA
68 dBA
60 dBA
75 dBA
67 dBA
61 dBA
FWR
61 dBA
55 dBA
66 dBA
60 dBA
69 dBA
60 dBA
77 dBA
68 dBA
57 dBA
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
www.gamewell-fci.com
CS-2540 Rev. A page 3 of 3