SpectrAlert Advance

SpectrAlert®
Advance
Description
Selectable Output
Notification Appliances
®
SpectrAlert Advance selectable-output horns, strobes and
horn/strobes are rich with features guaranteed to decrease
installation times and maximize profits. The SpectrAlert
Advance series of notification appliances is designed to
simplify your installations, with features such as the
following:
• Plug-in designs.
• Instant feedback messages to ensure correct installation of individual devices.
• Eleven field-selectable candela settings for wall, ceiling
strobes and horn/strobes.
More specifically, to install the Advance products, do the
following:
1. Attach a universal mounting plate to a four-inch
square, four-inch octagon, or double-gang junction
box.
The two-wire mounting plate attaches to a single-gang
junction box.
2. Connect the notification appliance circuit wiring to the
SEMS terminals on the mounting plate.
3. To attach the horn, strobe, or horn/strobe to the mounting plate, insert the product’s tabs in the mounting
plate’s grooves.
4. Rotate the device into position, locking the product’s
pins into the mounting plate’s terminals.
5. The device temporarily holds in place with a catch until
you secure it with a captured mounting screw.
SpectrAlert Advance products offer the following
options:
• 12 or 24 volts.
• At 24 volts, 15, 15/75, 30, 75, 95, 110, 115, 135, 150,
177, or 185 candela by way of rear-mounted slide
switch and front viewing window.
• Horn tones and volume by way of rotary switch.
The SpectrAlert Advance series includes outdoor notification appliances. Outdoor strobes and horn/strobes (twowire and four-wire) are available for wall or ceiling. Outdoor
horns are available for wall only. All System Sensor outdoor products are rated between –40°F and 151°F (–40°C
and 66°C) in wet or dry applications.
7087pho2.jpg
7087pho1.jpg
Indoor Ceiling Horn/Strobe
7087pho4.jpg
Outdoor Ceiling Strobe
7087pho5.jpg
Indoor Wall Horn
Indoor Ceiling Strobe
7087pho3.jpg
Indoor Wall Horn/Strobe
7087pho6.jpg
Outdoor Wall Strobe
Features
• Plug-in design.
• Same mounting plate for wall- and ceiling-mount units.
• Shorting spring on mounting plate for continuity check
before installation.
• Captive mounting screw.
• Tamper-resistance capability.
• Field-selectable candela settings on wall or ceiling units:
15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, 185.
• Automatic selection of 12 or 24 volt operation at 15 and
15/75 candela.
• Outdoor wall and ceiling products.
• Outdoor products rated from –40°F and 151°F
(–40°C and 66°C).
• Minimal intrusion into the backbox.
• Horn rated at 88+ dbA at 16 volts.
• Rotary switch for tone selection..
• Three horn volume settings
• Electrically compatible with SpectrAlert® products.
Sync•Circuit™ is a trademark, and SpectrAlert® and System Sensor® are registered trademarks of Honeywell International Inc. ©2006 by ADT. All rights reserved. Unauthorized use
of this document is strictly prohibited.
An ISO 9000-2000 Company
SIGNALING
MEA
S4011
Approved
452-05-E 7125-1653:188
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
CS-2539 Rev. C page 1 of 4
©2014 Honeywell International Inc. All rights reserved.
Models available:
Horn/Strobe Combination (Continued)
• Indoor wall-mount: horn, strobe, 2-wire horn/strobe,
flashing at 1 Hz over the strobe’s entire operating voltage
range. The strobe light shall consist of a xenon flash tube
and associated lens/reflector system. The horn shall have
three audibility options and an option to switch between a
Temporal 3 pattern and a Non-Temporal (continuous) pattern. These options are set by a multiple position switch.
On four-wire products, the strobe shall be powered independently of the sounder. The horn on horn/strobe models
shall operate on a coded or non-coded power supply.
4-wire horn/strobe.
• Indoor ceiling-mount: strobe, 2-wire horn/strobe,
4-wire horn/strobe.
• Outdoor wall-mount: horn, strobe, 2-wire horn/strobe,
4-wire horn/strobe.
• Outdoor ceiling-mount: strobe, 2-wire horn/strobe,
4-wire horn/strobe.
Outdoor Products
Engineering Specifications
SpectrAlert Advance horns, strobes, and horn/strobes shall
mount on a standard 4.0" x 4.0" x 1.5" (10.16 x 10.16 x 3.81 cm)
backbox, 4.0" (10.16 cm) octagonal backbox, or a doublegang backbox. Two-wire products shall also mount on a
single-gang 2.0" x 4.0" x 1.875" (5.08 x 10.16 x 4.763 cm) backbox. A universal mounting plate shall be used for mounting
ceiling and wall products. The notification appliance circuit
wiring shall terminate at the universal mounting plate. Also,
SpectrAlert Advance products, when used with the
Sync•Circuit™ Module accessory, shall be powered from a
non-coded notification appliance circuit output and shall
operate on a nominal 12 or 24 volts. When used with the
Sync•Circuit Module, 12-volt rated notification appliance
circuit outputs shall operate between 9 and 17.5 volts; 24volt rated notification appliance circuit outputs shall operate
between 17 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32°F and 120°F (0°C and 49°C)
from a regulated DC, or full-wave-rectified, unfiltered power
supply. Strobes and horn/strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95, 110,
115, 135, 150, 177, 185.
SpectrAlert Advance outdoor horns, strobes and horn/
strobes shall be listed for outdoor use by UL and shall
operate between –40°F and 151°F (–40°C and 66°C). The
products shall be listed for use with a System Sensor outdoor/weatherproof backbox with half-inch and threefourths-inch conduit entries.
Synchronization Module
The module shall be a System Sensor Sync•Circuit
_______ Listed to UL STD 464 and shall be approved for
fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz and horns at Temporal 3. Also, while
operating the strobes, the module shall silence the horns
on horn/strobe models over a single pair of wires. The
module shall mount to a 4.688" x 4.688" x 2.125" (11.906 x
11.906 x 5.398 cm) backbox. The module shall also control
two Style Y (Class B) circuits or one Style Z (Class A) circuit. The module shall synchronize multiple zones. Daisychaining two or more synchronization modules together will
synchronize all the zones the modules control. The module
shall not operate on a coded power supply.
Strobe
The strobe shall be a System Sensor SpectrAlert Advance
Model _______ Listed to UL STD 1971 and shall be
approved for fire protective service. The strobe shall be
wired as a primary-signaling notification appliance and
comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over
the strobe’s entire operating voltage range. The strobe light
shall consist of a xenon flash tube and associated lens/
reflector system.
Horn/Strobe Combination
The horn/strobe shall be a System Sensor SpectrAlert
Advance Model _______ Listed to UL Standards 1971 and
464 and shall be approved for fire protective service. The
horn/strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances,
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
CS-2539 Rev. C page 2 of 4
www.gamewell-fci.com
Operating Specifications
Standard operating
temperature:
32° F to 120° F (0° C to 49° C)
K Series operating
temperature:
-40° F and 151° F
(-40° C and 66° C)
Humidity range:
10% to 93% non-condensing
(indoor products).
Strobe flash rate:
1 flash per second.
Nominal voltage:
regulated 12 VDC/FWR or regulated
24 VDC.FWR.
Note: Full Wave Recitified (FWR)
voltage is a non-regulated, timevarying power source that is used
on some power supply and panel
outputs.
Operating voltage
range:
8 V to 17.5 V (12 V nominal); or 16
V to 33 V (24 V nominal).
Note: P, S, PC, and SC products will
operate at 12 V nominal only for 15
cd and 15/75 cd.
Input terminal wire
gauge:
12 to 18 AWG (3.31 to 0.821 mm2).
Ceiling-mount
dimensions
(including lens):
6.8” diameter x 2.5” deep
(17.3 diameter x 6.4 deep cm)
Wall-mount
dimensions
(including lens):
Horn dimensions:
5.6” H x 4.7” W x 2.5” D
(14.2 H x 11.9 W x 6.4 D cm)
5.6” H x 4.7” W x 1.3” D
(14.2 H x 11.9 W x 3.3 D cm)
Standard
Candela
Range
15
15/75
30
75
95
110
115
8 - 17.5 V
DC
FWR
123
128
142
148
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
135
150
177
185
8 - 17.5 V
NA
NA
NA
NA
NA
NA
NA
NA
16 - 33 V
228
207
246
220
281
251
286
258
Horn Current Draw,
UL Maximum (mA RMS)
Sound
Pattern
dB
Temporal
High
Temporal
Medium
Temporal
Low
Non-temporal High
Non-temporal Medium
Non-temporal Low
Coded
High
Coded
Medium
Coded
Low
8 - 17.5 V
DC
FWR
57
55
44
49
38
44
57
56
42
50
41
44
57
55
44
51
40
46
16 - 33 V
DC FWR
69
75
58
69
44
48
69
75
60
69
50
50
69
75
56
69
52
50
Horn and Horn/Strobe
Rotary Switch Setting)
Setting
Repetition Rate
dB Level
1
Temporal Horn
High
2
Temporal horn
Medium
3
Temporal horn
Low
4
Normal horn
Low
5
Normal horn
Medium
6
Normal horn
Low
7*
Externally coded
High
8*
Externally coded
Medium
9*
Externally coded
Low
*NOTE: Settings 7, 8 and 9 are not available on 2-wire
horn/strobe
Horn and Horn/Strobe Output (dBA)
Strobe Current Draw,
UL Maximum (mA RMS)
Candela
High
Candela
Range
16 - 33 V
DC
FWR
66
71
77
81
94
96
158
153
181
176
202
195
210
205
Switch
Sound
8 - 17.5 V
16 - 33 V
Position
Pattern
dB
DC FWR DC FWR
1
Temporal
High
78
78
84
84
2
Temporal Medium 74
74
80
80
3
Temporal
Low
71
73
76
76
4
Non-temporal High
82
82
88
88
5
Non-temporal Medium 78
78
85
85
6
Non-temporal Low
75
75
81
81
7*
Coded
High
82
82
88
88
8*
Coded
Medium 78
78
85
85
9*
Coded
Low
75
75
81
81
*NOTE: Settings 7, 8, and 9 are not available on 2-wire
horn/strobe.
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
www.gamewell-fci.com
CS-2539 Rev. C page 3 of 4
Two-Wire Horn/Strobe, STANDARD Candela Range (15 - 115 cd),
UL Maximum Current Draw (mA RMS)
8 - 17.5 V
Input, Sound Pattern, dB Level
15
15/75
15
15/75
DC Input, Temporal High
DC Input, Temporal, Medium
DC Input, Temporal, Low
DC Input, Non-temporal, High
FWR Input, Non-temporal Medium
DC Input, Non-temporal, Low
FWR Input, Temporal, High
FWR Input, Temporal, Medium
FWR Input, Temporal, Low
FWR Input, Non-temporal, High
FWR Input, Non-temporal, Medium
FWR Input, Non-temporal, Low
30
16 - 33 V
75
95
110
115
107
97
93
116
102
96
112
103
101
126
110
105
176
157
154
176
163
156
168
160
160
181
166
161
194
182
179
201
187
182
190
184
184
203
189
184
212
201
198
221
207
201
210
202
194
221
208
202
218
210
207
229
216
210
218
206
201
229
216
211
Two-Wire Horn/Strobe, HIGH Candela Range (135 - 185 cd),
UL Maximum Current Draw (mA RMS
16 - 33 V
135
150
177
185 FWR Input
DC Input
135
16 - 33 V
150
177
185
DC, Temporal High
DC, Temporal Medium
DC, Temporal Low
DC, Non-temporal, High
DC, Non-temporal, Medium
DC, Non-temporal, Low
215
209
207
233
219
214
231
224
221
248
232
229
265
258
256
281
267
262
245
235
232
255
242
238
137
132
132
141
133
131
136
129
129
142
134
132
259
253
251
270
259
254
290
288
282
303
293
291
147
144
143
152
145
144
155
152
151
161
155
154
297
297
292
309
299
295
79
69
66
91
75
68
88
78
76
103
85
80
90
80
77
100
85
79
97
88
86
112
95
90
FWR, Temporal, High
FWR, Temporal, Medium
FWR, Temporal, Low
FWR, Non-temporal, High
FWR, Non-temporal, Medium
FWR, Non-temporal, Low
258
250
248
275
262
256
Ordering Information:
Model
Description
Model
Description
WALL HORNS/STROBES
CEILING HORN/STROBES
P2R
2-wire horn/strobe, standard cd, red.
PC2R
2-wire horn/strobe, standard cd, red.
P2RH
2-wire horn/strobe, high cd, red.
PC2RH
2-wire horn/strobe, high cd, red.
P2RK
2-wire horn/strobe, standard cd, red, outdoor. PC2RK
2-wire horn/strobe, standard cd, red, outdoor.
P2RHK
2-wire horn/strobe, high cd, red, outdoor.
PC2RHK
2-wire horn/strobe, high cd, red, outdoor.
P2W
2-wire horn/strobe, high cd, white.
PC2W
2-wire horn/strobe, standard cd, white.
P2WH
2-wire horn/strobe, high cd, white.
PC2WH
2-wire horn/strobe, high cd, white.
P4R
4-wire horn/strobe, standard cd, red.
PC4R
4-wire horn/strobe, standard cd, red.
P4RH
4-wire horn/strobe, high cd, red.
PC4RH
4-wire horn/strobe, high cd, red.
P4RK
4-wire horn/strobe, standard
PC4RK
4-wire horn/strobe, standard cd, red, outdoor.
P4RHK
4-wire horn/strobe, high cd, red, outdoor.
PC4RHK
4-wire horn/strobe, high cd, red, outdoor.
P4W
4-wire horn/strobe, standard cd, white.
PC4W
4-wire horn/strobe, standard cd, white.
P4WH
4-wire horn/strobe, high cd, white
PC4WH
4-wire horn/strobe, high cd, white.
WALL STROBES
CEILING STROBES
SR
Strobe, standard cd, red.
SCR
Strobe, standard cd, red.
SRH
Strobe, high cd, red.
SCRH
Strobe, high cd, red.
SRK
Strobe, standard cd, red, outdoor.
SCRK
Strobe, standard cd, red, outdoor.
SRHK
Strobe, high cd, red, outdoor.
SCRHK
Strobe, high cd, red, outdoor.
SW
Strobe, standard cd, white.
SCW
Strobe, standard cd, white.
SWH
Strobe, high cd, white.
SCHW
Strobe, high cd, white.
ACCESSORIES
HORNS
BBS-2
Backbox skirt, wall, red.
HR
Horn, red.
BBSW-2
Backbox skirt, wall, white.
HRK
Horn, red, outdoor.
BBSC-2
Backbox skirt, ceiling, red.
HW
Horn, white
BBSCW-2
Backbox skirt, ceiling, white.
NOTE: “High cd” refers to strobes that include 135, 150, 177, and 185 candela settings. “Standard cd” refers to strobes that include
15, 15/75, 30, 75, 95, 110, and 115 candela settings.
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
CS-2539 Rev. C page 4 of 4