GAMEWELL-FCI MS95-SS

MS95-S Series
Features
Addressable Manual Pull Station
with SmartScan™
• Maintenance personnel can open station
without causing an alarm condition.
• Built- in LED, which is visible through the
handle of the station, flashes in normal
operation and latches steady read when
in alarm.
g2282ph1.jpg
Description
The Gamewell MS95-S Series is
a state-of-the-art, single- or dualaction pull station that includes
an addressable interface for any
Gamewell 600 Series Fire Alarm
Control Panel (FACP) with
SmartScan™. Because the
MS95-S Series is addressable,
the FACP can display the exact
location of the activated manual
station. This leads fire personnel
quickly to the location of the
alarm.
Operation
• Handle latches in down position and the
word “Activated” appears to clearly
indicate the station has been operated.
• Captive screw terminals wire-ready for
easy connection to SLC loop (accepts up
to 12 AWG/3.1 mm² wire).
• Semi-flush, mounts to a standard single
gang (2.125" [5.3975 cm] minimum
depth), double-gang, or 4" (10.16 cm)
square electrical box.
• Smooth dual-action design.
• Within ADA 5 lb. pull force.
• Highly visible.
• Attractive shape and textured finish.
• Key reset.
Pushing in, then pulling down on
the handle causes it to latch in
the down/activated position. Once
latched, the word “ACTIVATED” (in bright yellow) appears at the top of the
handle, while a portion of the handle protrudes from the bottom of the
station. To reset the station, simply unlock the station with the key and
pull the door open. This action resets the handle; closing the door automatically resets the switch. Each manual station, on command from the control
panel, sends data to the panel representing the state of the manual switch.
Two rotary decimal switches allow address settings.
• Includes Braille text on station handle.
• Optional trim ring (BG-TR).
• Meets UL 38, standard for manually
actuated signalling boxes.
• Up to 99 MS95-S Series stations per loop
on SmartScan™ protocol systems
• Dua-color LED blinks red to indicate
normal on SmartScan™ systems.
Construction
Shell,door, and handle are molded of durable LEXAN® (or polycarbonate
equivalent) with a textured finish.
Installation
The MS95-SS or MS95-SD will mount semi-flush into a single-gang, doublegang, or standard 4" (10.16 cm) square electrical outlet box, or will surface
mount to the Model SB-IO surface backbox. If the MS95-SS or MS95-SD is
being semi-flush mounted, then the optional trim ring (BG-TR) may be
used. The BG-TR is usually needed for semi-flush mounting with 4" (10.16
cm) or double-gang boxes (not with single-gang boxes).
MS95-L Series
CS-2488
09/01/06
Page 1 of 2
Listings
Listings and approvals below apply to the
basic MS95-S Series pull station. In some
cases, certain modules may not be listed
by certain approval agencies, or listing
may be in process. Consult factory for
latest listing status.
• UL Listed: file S281.
Engineer’s Specifications
Specifications
Manual Fire Alarm Stations shall be non-coded, with a key- operated reset
lock in order that they may be tested, and so designed that after actual
Emergency Operation, they cannot be restored to normal except by use of a
key. An operated station shall automatically condition itself so as to be
visually detected as activated. Manual stations shall be constructed of redcolored LEXAN® (or polycarbonate equivalent) with clearly visible operating
instructions provided on the cover. The word FIRE shall appear on the front
of the stations in white letters, 1.00 inches (25.4 mm) or larger. Stations
shall be suitable for surface mounting on matching backbox SB-I/O; or semiflush mounting on a standard single-gang, double-gang, or 4" (10.16 cm)
square electrical box, and shall be installed within the limits defined by the
Americans with Disabilities Act (ADA) or per national/local requirements.
Manual Stations shall be Underwriters Laboratories listed.
Nominal Operating Voltage
Manual stations shall connect with two wires to one of the control panel
SLC loops. The manual station shall, on command from the control panel,
send data to the panel representing the state of the manual switch. Manual
stations shall provide address setting by use of rotary decimal switches.
Humidity
The loop poll LED shall be clearly visible through the front of the station.
The LED shall flash while in the normal condition, and stay steadily illuminated when in alarm.
15 – 32 VDC.
Average Operating Current
375 µA maximum.
EOL Resistance
47K ohms.
Maximum IDC Wiring Resistance
1,500 ohms.
Temperature Range
32°F to 120°F (0°C to 49°C).
10 to 93% noncondensing.
Wiring Diagram
Ordering Information
MS95-SS
SmartScan™ pull station, single-action with key.
MS95-SD
SmartScan™ pull station, dual-action with key.
SB- I/O
Surface box.
BG-TR
Optional trim ring
Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
Phone: 203-484-7161
Fax: 203-484-7118
www.gamewell-fci.com
A Honeywell Company
© 2006 Gamewell-FCI
Specifications and wiring information are provided for information only and are
believed to be accurate. Gamewell-FCI assumes no responsibility for their use.
Data and design are subject to change without notice. Installation and wiring
instructions shipped with the product shall always be used for actual installation.
For more information, contact Gamewell-FCI.