IdentiFlex 100

IdentiFlex 100
Single Loop Addressable
Fire Alarm Control Panel
Description
The IdentiFlex 100 is a 25 point, single loop, addressable
fire alarm control panel that supports Gamewell-FCI, Velociti Series detectors and modules. The IdentiFlex 100 also
features a powerful built-in, dual line fire communicator that
offers communication for reporting of all system activity to a
remote monitoring location.
The IdentiFlex 100 provides you with the revolutionary
value and performance of the addressable sensing technology combined with an exclusive, built-in digital communication that includes an easy-to-use interface. With the code
wheel addressable detectors/modules and the JumpStart™
feature, the IdentiFlex 100 can be Life Safety operational
without a single programming tool. Powerful features such
as drift compensation and maintenance alert are delivered
in this robust FACP from Gamewell-FCI.
Installation
The IdentiFlex 100 is a surface mount FACP.
Compatibility
The IdentiFlex 100 SLC supports the Velociti Series intelligent detectors and modules.
Approvals
The following list the NFPA Standard Approvals for the
devices listed below:
NFPA 13, NFPA 15, NFPA 16, NFPA 70, & NFPA 72:
• Central Station
• Auxiliary Protected Premises
Unit
• Remote Signalling • Local Protective Signaling
Systems
The above devices are suitable for automatic, manual,
waterflow, sprinkler supervisory (DACT non-coded), signalling services.
IdentiFlex
Features
• Built-in support for a combination of up to 25 detectors
and modules.
• Built-in digital communicator.
• Detectors and modules are code wheel addressed for a
faster installation time.
• Offers drift compensation.
• Maintenance alert region.
• Point status eliminates calibrated smoke test
requirements for NFPA 72.
• Auto learn “JumpStart™” feature for easy programming.
• Custom programming can be performed through an
FACP built-in browser. No programming software required.
• Uses standard wire–no shielded or twisted-pair
required.Central Station reporting up to five zones
• Built-in synchronization for AMSECO, Gentex®,
Cooper-Wheelock®, or System Sensor® notification
appliances.
• Two Style Y (Class B) notification appliance circuits (NAC).
• Two built-in Form C programmable relays.
• Built-in Form C trouble relay.
• Provides SBUS for a connection to an optional
GFANN-80 remote LCD annunciator.
ISO 9001-2000 Company
JumpStart™ is a trademark of Honeywell International Inc.
System Sensor is a registered trademark of Honeywell International Inc.
®
Gentex is a registered trademark of Gentex.
®
Cooper-Wheelock is a registered trademark of Cooper-Wheelock Inc.
®
UL is a registered trademark of Underwriters Laboratories Inc.
SIGNALING
S1869 7165-1703:0172
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9021-60579 Rev. C page 1 of 2
©2013 by Honeywell International Inc. All rights reserved.
GFANN-80
Remote Annunciator
Signaling Line Circuit
DNR duct detector
AOM-2RF
ASD-PL2F
MS-7AF
AMM-2F
ATD-L2F
Horn/
Strobe
Strobe
BELL
M500X
Notification Appliance Circuit
Figure 1 IdentiFlex 100 Addressable FACP Overview
Ordering Information
Specifications
Electrical
GIF100 Primary AC:
GIF100G Primary AC:
Total Accessory Load:
Notification Power:
Standby Current:
Alarm Current:
Aux Power Circuits:
Battery Charging
Capacity:
Battery Size:
120 VRMS @ 60 Hz,1.5A
230 VRMS @ 50/60, .75A Hz
2.0A @ 24 VDC
2.0A @ 24 VDC, power-limited
135 mA
220 mA
1.0A @ 24 VDC per circuit,
power-limited
7.0 – 33 AH or 18 AH for ULC®
installations
7 AH max. allowed in FACP cabinet. Larger capacity batteries
can be housed in an accessory
cabinet.
Physical
Dimensions:
Weight:
Color:
Telephone
Requirements:
Type of Jack:
12.75" W x 15.2" H x 3.4" D
(32.39 W x 38.42 H x 8.57 D cm)
11.5 lbs. (5.2 kg)
Red
FCC Part 15 and Part 68
approved
RJ31X (two required)
Part Number
GIF100
GIF100G
Description
IdentiFlex 100, 120 VAC FACP
IdentiFlex 100, 230 VAC FACP
Gamewell-FCI Fire Systems Devices
ASD-PL2F
Photoelectric smoke detector
ASD-PTL2F
Photoelectric smoke detector with
thermal
DNR
Photoelectric duct smoke detector
Photoelectric smoke detector, remote
test capable, for use with the
ASD-PL2FR duct smoke detectors
ATD-L2F
Fixed temperature thermal detector
AMM-2F
Mini monitor Module
AOM-2RF
Addressable relay module
MS-7ASF
Addressable single action pull station
MS-7AF
Addressable dual action pull station
IdentiFlex fire alarm control panel
GFANN-80
Remote Annunciator
005220
City box connection module
HFS-P
Photoelectric smoke detector
HFS-PT
Photoelectric smoke detector with thermal
HFS-D
Photoelectric duct smoke detector
HFS-DPR
Photoelectric smoke detector, remote
test capable, for use with the HFS-D
duct smoke detectors
HFS-T
Fixed temperature thermal detector
HFS-MM
Mini monitor module
HFS-MR
Addressable relay module
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9021-60579 Rev. C page 2 of 2