faast xt - Gamewell

FAAST® 9400X
Conventional FAAST Fire Alarm
Aspiration Sensing Technology
Description
The Gamewell-FCI, FAAST XT®, 9400X aspirating smoke
detectors deliver highly accurate Very Early Warning Fire
Detection over a wide coverage area and offer extensive
communication applications. This aspirating smoke detector combines advanced particle separation with a unique
dual source optical smoke detection technology to provide
highly sensitive Very Early Warning Fire Detection while
providing enhanced immunity to false alarms. This technology enables FAAST XT to accurately detect incipient fire
conditions as early as 60 minutes before a fire actually
starts when set for Early Warning and Very Early Warning
Fire Detection in applications ranging from mission critical
to harsh and extreme environments.
An installed FAAST XT device can protect up to 28,800 sq.
ft. (2,676 sq. m) in the standard coverage type applications
and can be monitored in several different ways, including
the following:
• Serial or TCP Modbus
• Direct PC connection
• Ethernet over a LAN
• FAAST XT’s onboard USB
When the 9400X is connected to a LAN, FAAST XT’s email
server can email event notification to the appropriate personnel. FAAST XT also communicates alarm and fault
conditions via Form C Relays.
PipeIQ® is FAAST XT’s intuitive design, configuration, and
monitoring software. The all-in-one program can be used
to do the following:
• Create a pipe network tailored to meet site specific
requirements.
• Configure a FAAST XT device.
• Monitor an installed device including the following:
- live trending
- reading of historic reports
*A complimentary download of PipeIQ is available at
systemsensor.com/faast.
9400X
Features
• Provides Very Early Warning Fire Detection, as precise
as 0.00046%/ft obscuration.
• Includes five alarm levels and two sensitivity modes to
provide application flexibility.
• Has user-configurable 3-speed fan, allowing for maximum coverage area or minimizing current consumption.
• Delivers ultrasonic flow sensing for each pipe inlet and
chamber airflow monitoring for precise system health
information.
• A single device can cover up to 28,800 square feet.
• Combines a dual source optical detection chamber with
enhanced algorithms to provide high sensitivity with
greater immunity to nuisance conditions.
• Delivers a patented particle separator to remove large,
non-fire particulate, ensuring chamber health and
extending the life of the field-replaceable filter.
• Converts TCP and Serial modbus for easy integration
with building management systems.
• Offers easy configuration via USB interface, no power
needed.
• Supports an on-board Ethernet interface that enables
remote monitoring and email notification.
• Displays an LCD user interface that allows for detailed
device information and interaction such as the following.
- Active faults
- Reset of airflow baseline
- Test/reset/isolate
- Precise airflow monitoring
• Produces configurable air flow fault thresholds and
verification period.
• Designed with convenient wiring compartment.
• Shows the status-at-a-glance that provides immediate
alarm, fault and airflow status.
SIGNALING
PipeIQ™ is a trademarks of Honeywell International Inc.
®
FAAST XT is a registered trademark of System Sensor Inc.
®
UL is a registered trademark of Underwriter’s Laboratories, Inc.
S1913 7259-1653:0236
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9021-60840 Rev. A page 1 of 2
©2014 by Honeywell International Inc. All rights reserved.
Specifications
Specifications (Continued)
Conventional FAAST XT Specifications
Electrical Specifications
Networking Specifications (Continued)
External Supply Voltage 18-30 VDC
Remote Reset Time
External monitor must be pulled
low for a minimum of 100 ms
Power Reset
1 second
Avg. Operating Current Fan High - 465mA, 11.2W
Fan Med - 340mA, 8.2W
Fan Low - 220mA, 5.3W
Alarm Current
Fan High - 493mA, 11.85W
Fan Med - 368mA, 8.85W
Fan Low - 248mA, 6W
Relay Contact Ratings 3.0 A @ 30 VDC
0.5 A @ 125 VAC 8 form C
3 AMP, programmable latching
or non-latching
Ethernet
Modbus
Email
Webserver
10/100Mbps, MDI-X
TCP or Serial RS6 recipients, sel. notifications
Read Configuration, Live View,
Logs
Configuration Specifications
PipeQ
Modbus
USB or Ethernet
Ethernet or RS-485
Figure 1 illustrates the FAAST XT user interface display.
Environmental Ratings
Operating Temperature 32°F (0°C) to 100°F (38°C);
Factory Tested to 133°F (55°C)
Sampled Air
Temperature
-4°F (-20°C) to 140°F (60°C)
Humidity Range
10 to 95% (non-condensing)
Sensitivity Range
0.00046% Obs/ft to 6.25% Obs/ft
(0.0015% Obs/m to 20.5% Obs/m)
IP Rating
IP30
Coverage Area
28,800 sq.ft. (2,676 sq.m)
Air Movement
0-4,000 ft./min. (0-1,219 m/min.)
Physical Specifications
Height
Width
Depth
Cable Access
Wire Gauge
Maximum Single Pipe
Length
Total Pipe Length
13.3 in (338 mm)
13.1 in (333 mm)
7.5 in (191 mm)
4 1-inch (2.54 cm) cable entry
holes located on top, bottom and
back of the unit
12 AWG (2.05 mm) max. to
24 AWG (0.5 mm) min.
400 ft. (123 m)
(*other there pipes disabled)
1050 ft. (320 m)
(*all designs must be verified
within PipeIQ software)
262 ft. per pipe
Multiple Pipe Network
Network Outside Pipe
Diameter
1.050 inches, IPS (25 mm)
Internal Pipe Diameter 0.591 to 0.827 inches (15-21 mm)
Sensitivity Range
0.00046%Obs/ft to 6.25% Obs/ft
(0.0015%Obs/m to 20.5%Obs/m)
Relays
8 Form C, 3 AMP, programmable
latching or non-latching
Figure 1 - FAAST XT User Interface Display
The User Interface consists of 5 Alarm levels:
• Alert
• Fire 1 and Fire 2, 10 Particulate levels
• Action 1
and Flow and Fault graph
• Action 2
Ordering Information
Part Number
9400X
Description
System Sensor Conventional FAAST Fire
Alarm Aspiration Sensing Technology
Accessories
Various†
UL®-Approved Pipe and Fittings
† Additional accessory information, including part numbers, can be accessed at systemsensor.com/faast.
Diagnostic Specifications
Event Log
Trend Data Log
Service Log
18,000 events stored
Configurable sampling period
(1 minute to 1 day)
300 custom user entries
Networking Specifications
Communication
Network
Network Services
Ethernet monitoring,
6 E-mail address alerts,
TCP and Serial Modbus
DHCP, SMTP, HTTP, MODBUS/
TCP, AutoIP, NetBIOS-NS,
Serial MODBUS
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9021-60840 Rev. A page 2 of 2
www.gamewell-fci.com