FAAST XM AAD-8100 Intelligent Aspiration Detector

AAD-8100
Intelligent FAAST Fire Alarm
Aspiration Sensing Technology
Description
The Gamewell-FCI, Intelligent FAAST®, AAD-8100 Aspirating Smoke Detector combines dual source (blue LED
and infrared laser), optical smoke detection with the fire
alarm control panel connectivity, via the Velociti mode to
provide high sensitivity to fire with intelligent reporting
capabilities. In addition, the FAAST can provide enhanced
immunity to a nuisance particulate. As a result, FAAST can
deliver highly accurate Very Early Warning Fire Detection,
directly over the Signaling Line Circuit (SLC) to a fire alarm
control panel, via the Velociti protocol. This process
enables maximum control over mission critical and challenging environments. Moreover, the FAAST can seamlessly integrate with an existing fire signaling circuit.
The Intelligent FAAST Detector can be wired to a new or
pre-existing SLC that is used for transmitting communications directly to a fire alarm control panel, via the Velociti
mode, without using extra hardware. In the Velociti mode,
the AAD-8100, FAAST will report back to the fire alarm
control panel as an Aspirating detector. By setting the sensitivity levels in PipeIQ™, the fire alarm control panel will
initiate pre-alarm and alarm conditions based on the feedback sent from the FAAST unit. Using the Velociti mode,
up to 159 units can populate one SLC.
For the initial system creation, FAAST’s design, configuration and monitoring software, PipeIQ, guide users through
pipe layout. An installed device can be monitored through
its integral display by any of the following ways:
• from a computer connected to the device
• remotely through a web browser
When FAAST is connected to the Internet, it can also email status updates to the appropriate personnel.
*A complimentary download of the PipeIQ software program is available at systemsensor.com/faast.
AAD-8100
Features
•
•
•
•
•
•
•
•
•
•
•
•
•
Provides the SLC connectivity via the Velociti Protocol.
Supports up to 159 FAAST devices per loop.
Detection as precise as 0.00046%/ft obscuration.
Includes five (5) alarm levels and two sensitivity modes
provide application flexibility.
Offers dual flow detection including both ultrasonic and
electronic sensing for pipe and chamber air flow measurement.
A single device protects up to 8,000 square feet.
Applies advanced detection algorithms to reject common nuisance conditions.
Uses a Patented particle separator and a field-replaceable filter to remove contaminants from the system.
Employs PipeIQ™ software that provides an intuitive
system layout, configuration, and monitoring all in one
package.
Has an on-board Ethernet interface that enables
remote monitoring and e-mail status updates.
Fault indicators exhibit a broad spectrum of events.
Unique air flow pendulum graph verifies pipe network
functionality.
Particulate graph displays subtle environmental
changes for early problem indications.
SIGNALING
PipeIQ™ and Acclimate™ are registered trademarks of Honeywell International Inc.
®
FAAST is a registered trademark of System Sensor Inc.
® is a registered trademark of Underwriter’s Laboratories, Inc.
UL
S1913 7259-1703:0177
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9021-60770 Rev. B page 1 of 2
©2013 by Honeywell International Inc. All rights reserved.
Specifications
Intelligent FAAST Specifications
Electrical Specifications
External Supply Voltage 18-30 VDC
Remote Reset Time
External monitor must be pulled
low for a minimum of 100 ms
Power Reset
1 sec.
Avg. Operating Current 500 mA @ 24 VDC
Alarm
650 mA – All relays active, all
alarm levels displayed.
Voltage @ 24 VDC
Average SLC Current 700uA
SLC Voltage Range
15 to 32 VDC
Relay Contact Ratings 3.0 A @ 30 VDC
0.5 A @ 125 VAC
Environmental Ratings
Operating Temperature
Sampled Air
Temperature
Humidity Range
IP Rating
Coverage Area
Air Movement
32°F (0°C) to 100°F (38°C)
Figure 1 - Intelligent FAAST User Interface Display
-4°F (-20°C) to 140°F (60°C)
10 to 95% (non-condensing)
IP30
8,000 sq. ft. (800 sq. m)
0-4,000 ft./min. (0-1,219 m/min.)
The User Interface consists of 5 Alarm levels:
• Alert
• Fire 1, 10 Particulate levels
• Action 1
• Fire 2, 10 Bi-color Flow and Fault graph
• Action 2
Physical Specifications
Height
Width
Depth
Cable Access
Wire Gauge
Maximum Single Pipe
Length
Maximum Branched (2)
Pipe Length
Maximum Air Inlet
Holes
Network Outside Pipe
Diameter
Internal Pipe Diameter
Sensitivity Range
Relays
Event Log
Communication
Network
Shipping Weight
13.25 inches (33.7 cm)
13.0 inches (33 cm)
5.0 inches (12.7 cm)
4 1-inch (2.54 cm) cable entry
holes on top and bottom of unit
12 AWG (2.05 mm) max. to
24 AWG (0.5 mm) min.
262 ft. (80 m)
165 ft. (50 m) each branch
40 holes
Ordering Information
Part Number
AAD-8100
Description
System Sensor Intelligent FAAST Fire
Alarm Aspiration Sensing Technology
Accessories
CMKT00100
FAAST Information Kit–Includes a
Comprehensive Instruction Manual
F-A3384-000 Replacement Air Filter Assembly
Various†
Language Card
Various†
UL®-Approved Pipe and Fittings
† Additional accessory information, including part numbers, can be accessed at systemsensor.com/faast.
1.050 inches, IPS (25 mm)
0.591 to 0.827 inches
(15-21 mm)
0.00046%Obs/ft to 6.25% Obs/ft
(0.0015%Obs/m to 20.5%Obs/m)
6 form C, 3 AMP, programmable
latching or non-latching
18,000 events stored
Ethernet monitoring,
6 E-mail address alerts
11.6 lbs. (5.3 kg),
includes packing material
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9021-60770 Rev. B page 2 of 2
www.gamewell-fci.com