FAAST XT AAD-9400X

FAAST XT®
AAD-9400X
Intelligent Fire Alarm Aspiration
Sensing Technology
Description
The Gamewell-FCI, Intelligent FAAST XT®, AAD-9400X
aspirating smoke detectors deliver highly accurate Very
Early Warning Fire Detection over a wide coverage area
directly over the Signaling Line Circuit (SLC) to the fire
alarm control panel via the Velociti protocol. This aspirating
smoke detector combines advanced particle separation
with a unique dual source optical smoke detection technology to provide highly sensitive Very Early Warning Fire
Detection while providing enhanced immunity to false
alarms. This technology enables FAAST to accurately
detect incipient fire conditions as early as 60 minutes
before a fire actually starts when set for Early Warning and
Very Early Warning Fire Detection in applications ranging
from mission critical to harsh and extreme environments.
An installed FAAST XT device can protect up to 28,800 sq.
ft. (2,676 sq. m) in the standard coverage type applications.
The Intelligent FAAST XT Detector can be wired to a new
or pre-existing SLC that is used for transmitting communications directly to a fire alarm control panel, via the Velociti
mode, without using extra hardware. In the Velociti mode,
the AAD-9400X, FAAST XT will report back to the fire
alarm control panel as an aspirating detector. By setting
the sensitivity levels in PipeIQ™, the fire alarm control
panel will initiate pre-alarm and alarm conditions based on
the feedback sent from the FAAST XT unit. Using the
Velociti mode, up to 159 units can populate one SLC.
In addition to providing a direct connection on the SLC, the
FAAST XT device can be monitored in several different
ways, including the following:
• Serial or TCP Modbus® • Direct PC connection
• Ethernet over a LAN
• FAAST’s onboard USB
When the AAD-9400X is connected to a LAN, the FAAST’s
email server can email event notification to the appropriate
personnel. FAAST also communicates alarm and fault
conditions via Form C Relays.
PipeIQ® is FAAST’s intuitive design, configuration, and
monitoring software. The all-in-one program can be used
to do the following:
• Create a pipe network tailored to meet site specific
requirements.
• Configure a FAAST device.
• Monitor an installed device including the following:
- live trending
- reading of historic reports
*A complimentary download of PipeIQ is available at
systemsensor.com/faast.
Features
AAD-9400X
• Offers the SLC connectivity via the Velociti protocol.
• Supports 159 FAAST XT devices per loop.
• Provides Very Early Warning Fire Detection, as precise
as 0.00046%/ft obscuration.
• Includes five alarm levels and two sensitivity modes to
provide application flexibility.
• Has 3-fan speed settings that allow for maximum coverage area, and provide savings on current consumption.
• Delivers ultrasonic flow sensing for each pipe inlet and
chamber airflow monitoring for precise system health
information.
• A single device can cover up to 28,800 square feet.
• Combines a dual source optical detection chamber with
enhanced algorithms to provide high sensitivity with
greater immunity to nuisance conditions.
• Delivers a patented particle separator to remove large,
non-fire particulate, ensuring chamber health and
extending the life of the field-replaceable filter.
• Converts TCP and Serial modbus for easy integration
with building management systems.
• Offers easy configuration via USB interface, no external
power needed.
• Supports an onboard Ethernet interface that enables
remote monitoring and email notification.
• Displays an LCD user interface that allows for detailed
device information and interaction such as the following.
- Active faults
- Reset of airflow baseline
- Test/reset/isolate
- Precise airflow monitoring
• Produces configurable air flow fault thresholds.
PipeIQ® is a registered trademark of Honeywell International Inc.
®
FAAST is a registered trademark of System Sensor Inc.
Modbus® is a registered trademark of Modbus Organization
UL® is a registered trademark of Underwriter’s Laboratories, Inc.
SIGNALING
S1913
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9021-60838 Rev. A page 1 of 2
©2014 by Honeywell International Inc. All rights reserved.
Specifications
Specifications (Continued)
Intelligent FAAST XT Specifications
Electrical Specifications
Network Specifications (Continued)
Webserver
Read Configuration, Live View,
Logs
External Supply Voltage 18-30 VDC
Remote Reset Time
External monitor must be pulled
low for a minimum of 100 ms
Power Reset
1 sec.
Avg. Operating Current Fan High - 465mA, 11.2W;
Fan Med - 340mA, 8.2W;
Fan Low - 220mA, 5.3W
Alarm
Fan High - 493mA, 11.85W;
Fan Med - 368mA, 8.85W;
Fan Low - 248mA, 6W
Relay Contact Ratings 3.0 A @ 30 VDC,
0.5 A @ 125 VAC
Configuration Specifications
PipeQ
USB or Ethernet
Modbus
Ethernet or RS-485
Figure 1 illustrates the FAAST XT user interface display.
Environmental Ratings
Operating Temperature 32°F (0°C) to 100°F (38°C);
Factory Tested to 133°F (55°C)
Sampled Air
Temperature
-4°F (-20°C) to 140°F (60°C)
Humidity Range
10 to 95% (non-condensing)
IP Rating
IP30
Coverage Area
28,800 sq.ft. (2,676 sq.m)
Air Movement
0-4,000 ft./min. (0-1,219 m/min.)
Physical Specifications
Height
Width
Depth
Cable Access
Wire Gauge
Maximum Single Pipe
Length
Total Pipe Length
13.3 in (338 mm)
13.1 in (333 mm)
7.5 in (191 mm)
4 1-inch (2.54 cm) cable entry
holes on top, bottom and back of
the unit
12 AWG (2.05 mm) max. to
24 AWG (0.5 mm) min.
400 ft. (123 m)
1050 ft. (320 m)
(*all designs must be verified
within PipeIQ software)
262 ft. per pipe
Figure 1 - Intelligent FAAST XT User Interface Display
The User Interface consists of 5 Alarm levels:
• Alert
• Fire 1 and Fire 2, 10 Particulate levels
• Action 1
and Flow and Fault graph
• Action 2
Ordering Information
Multiple Pipe Network
Network Outside Pipe
Diameter
1.050 inches, IPS (25 mm)
Internal Pipe Diameter 0.591 to 0.827 inches (15-21 mm)
Sensitivity Range
0.00046%Obs/ft to 6.25% Obs/ft
(0.0015% Obs/m to 20.5% Obs/m)
Relays
8 Form C, 3 AMP, programmable latching or non-latching
Diagnostic Specifications
Event Log
18,000 events stored
Trend Data Log
Configurable sampling period
(1 minute to 1 day)
Service Log
300 custom user entries
Network Specifications
Communication
Ethernet monitoring
Network
6 E-mail address alerts,
TCP and Serial Modbus
Network Services
DHCP, SMTP, HTTP, MODBUS/
TCP, AutoIP, NetBIOS-NS,
Serial MODBUS
Ethernet
10/100Mbps, MDI-X
Modbus
TCP or Serial RSEmail
6 recipients, sel. notification
Part Number
AAD-9400X
Description
System Sensor Intelligent FAAST XT Fire
Alarm Aspiration Sensing Technology
Accessories
CMKT00100
FAAST Information Kit–Includes a
Comprehensive Instruction Manual
F-A3384-000 Replacement Air Filter Assembly
Various†
UL®-Approved Pipe and Fittings
† Additional accessory information, including part numbers, can be accessed at systemsensor.com/faast.