Data Sheet - System Sensor

FAAST XS
Fire Alarm Aspiration
Sensing Technology®
FAAST XS aspirating smoke detectors deliver highly
accurate Very Early Warning Fire Detection for the smaller
applications and offer extensive communication capabilities.
Features
• Provides Very Early Warning Fire Detection, as precise as
0.00029%/ft obscuration
• Three alarm levels and three sensitivity modes provide
application flexibility
• User configurable 3-speed fan, allowing for maximum coverage
area or minimizing on current consumption
• Ultrasonic flow sensing and chamber airflow monitoring
for precise system health information
The FAAST XS aspirating smoke detector combines advanced
particle separation with unique dual source optical smoke detection
technology to provide highly sensitive Very Early Warning Fire
Detection while providing enhanced immunity to false alarms.
This technology enables FAAST XS to accurately detect incipient
fire conditions as early as 60 minutes before a fire actually starts
when set for Early Warning and Very Early Warning Fire Detection
in applications ranging from mission critical to harsh and extreme
environments.
• A single device covers up to 5,000 square feet (464 sq. m)
• Dual source optical detection chamber with enhanced
algorithms provide high sensitivity with greater immunity to
nuisance conditions
• Patented particle separator removes large, non-fire particulate,
ensuring chamber health and extending the life of the fieldreplaceable filter
• TCP and Serial modbus for easy integration with building
management systems
• Easy configuration via USB interface, no external power needed
• Onboard Ethernet interface enables remote monitoring,
configuration, web server and e-mail notifications
• Multilingual LCD user interface allows for detailed device
information and interaction such as: Active faults, precise airflow
monitoring, reset of airflow baseline, test/reset/isolate, and more
• Configurable air flow fault thresholds and verification period
• Convenient wiring compartment
• Status-at-a-glance provides immediate alarm, fault and
airflow status
Agency Listings
S911
An installed FAAST XS device can protect up to 5,000 sq. ft.
(464 sq. m) in standard coverage type applications and can be
monitored in several different ways, including: Serial or TCP Modbus,
Ethernet over a LAN or a direct connection, or via FAAST XS’s
onboard USB. When connected to a LAN, FAAST XS’s email server
can provide email event notification to appropriate personnel. FAAST
XS also communicates alarm and notifications via form C relays.
PipeIQ® is FAAST XS’s intuitive design, configuration, and monitoring
software. The all-in-one program can be used to create a pipe
network tailored to meet site specific requirements, configure a
FAAST XS device, and monitor an installed device -- including live
trending and reading of historic reports.
*A complimentary download of PipeIQ is available at
systemsensor.com/faast.
FAAST XS Specifications
Electrical Specifications
External Supply Voltage
Remote Reset Time
Power Reset
Operating Current
Alarm Current
Relay Contact Ratings
18-30 VDC
External monitor must be pulled low for a minimum of 100 ms
1 sec.
Fan High - 200mA, 4.8W; Fan Med - 151mA, 3.7W; Fan Low - 120mA, 2.1W
Fan High - 230mA, 5.6W; Fan Med - 172mA, 4.2W; Fan Low - 142mA, 3.5W
3.0 A @ 30 VDC, 0.5 A @ 125 VAC 5 form C, 3 AMP, programmable latching or non-latching
Operating Specifications
Operating Temperature
Sampled Air Temperature
Humidity Range
Sensitivity Range
IP Rating
Coverage Area
Air Movement
32°F (0°C) to 100°F (38°C); Factory Tested to 131°F (55°C)
-4°F (-20°C) to 140°F (60°C)
10 to 95% (non-condensing)
0.00029% Obs/ft to 6.25% Obs/ft (0.00095% Obs/m to 20.5% Obs/m)
IP30
5,000 sq.ft. (464 sq.m)
0-4,000 ft./min. (0-1,219 m/min.)
Physical Specifications
Height
Width
Depth
Cable Access
Wire Gauge
Maximum Single Pipe Length
Total Aggregate Pipe Length
Outside Pipe Diameter
Internal Pipe Diameter
Relays
Diagnostic Specifications
Event Log
Trend Data Log
Service Log
Networking Specifications
Communication Network
Network Services
Ethernet
Modbus
Email
Webserver
Configuration Specifications
PipeIQ
Modbus
Ordering Information
11.0 in (279mm)
9.0 in (229mm)
6.25 in (159mm)
3 1-inch (2.54 cm) cable entry holes on top, and back of the unit
12 AWG (2.05 mm) max. to 24 AWG (0.5 mm) min.
180 ft. (54.9 m) *all designs must be verified within PipeIQ software
300 ft. (91.5m) *all designs must be verified within PipeIQ software
1.050 inches, IPS (25 mm)
0.591 to 0.827 inches (15-21 mm)
5 form C, 3 AMP, programmable latching or non-latching
18,000 events stored
Configurable sampling period 1
minute to 1 day.
300 custom user entries
Ethernet monitoring, 6 email
address alerts, TCP and
Serial Modbus
DHCP, SMTP, HTTP, MODBUS/
TCP, AutoIP, NetBIOS-NS, Serial
MODBUS
10/100Mbps, MDI-X
TCP or Serial RS-485
6 recipients, selectable
notifications
Read Configuration,
Live View, Logs
USB or Ethernet
Ethernet or RS-485
FAAST XS User Interface Display
The User Interface consists of 3 Alarm levels – Alert, Fire 1, and Fire 2,
10 Particulate levels, 10 Airflow indicators, 4 Fault indicators, LCD.
Part No.
Description
7100X
System Sensor Conventional FAAST Fire Alarm Aspiration Sensing Technology
Accessories
UL-Approved Pipe and Fittings
Various†
†
Additional accessory information, including part numbers, can be accessed at systemsensor.com/faast
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
www.systemsensor.com
©2015 System Sensor.
Product specifications subject to change without notice. Visit systemsensor.com
for current product information, including the latest version of this data sheet.
ASDS78701 • 9/15