Velociti® Series AOM-TELF Description Addressable Audio Evacuation Module • The Gamewell-FCI Velociti® Series, Telephone Monitor Module (AOM-TELF) controls the communications between the command center and the telephone jacks/ warden stations. Wiring to individual telephone jacks and handsets is supervised and may be configured as two-wire (Class B), or fault tolerant, (Class A). Status is reported to the panel as the following: • NORMAL • TROUBLE • TELEPHONE AOM-TELF The module contains a panel-controlled LED indicator. The AOM-TELF is installed in the signaling line circuit of the Gamewell-FCI Emergency Voice Evacuation Systems. The AOM-TELF is designed to fit into a 4" (10.16 cm) square junction box 2 1/8" (5.5 cm) deep. Features • Listed under UL® Standard UL 864 and UL2572 for Mass Notification. • The Velociti® Series use a communication protocol that substantially increases the speed of communication between the SLC devices and certain Gamewell-FCI analog addressable fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel’s microprocessor stops the group poll and concentrates on the single device. The net result is a superior response speed up to five times greater than earlier designs. • Designed as a compact size to allow easy installation. Ordering Information Supervisory Current: Alarm Current: Operating Temperature: Relative Humidity: Part Number Description AOM-TELF Telephone monitor module • • Provides Class A, fault tolerant, or Class B wiring. • • Includes a bicolor LED that flashes green whenever the module is addressed, and lights steady red upon activation.* • *Note: Only the red LED is operative in panels that do not operate in Velociti® mode. Specifications AOM-TELF .0024 A AOM-TELF .0075 A 32° to 120° F (0° to 49° C) 10 to 93% relative humidity (non-condensing) Dimensions: 4 1/2” H x 4” W x 1 1/4” D (11.4 H x 10.16 W x 3.2 D cm) End-of-Line Resistance: AOM-TELF—3.9K SIGNALING FM Velociti® and E3 Series® are registered trademarks of Honeywell International Inc. ® UL is a registered trademark for Underwriter’s Laboratories Inc. APPROVED S1949 MEA Approved 3023594 227-03 E Vol. IV 7300-1703:0107 GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. www.gamewell-fci.com 9020-0628 Rev. G page 1 of 1 ©2014 Honeywell International Inc. All rights reserved.