9020-0628 - Gamewell

Velociti® Series
AOM-TELF
Description
Addressable Audio Evacuation Module
•
The Gamewell-FCI Velociti® Series, Telephone Monitor
Module (AOM-TELF) controls the communications
between the command center and the telephone jacks/
warden stations. Wiring to individual telephone jacks and
handsets is supervised and may be configured as two-wire
(Class B), or fault tolerant, (Class A). Status is reported to
the panel as the following:
• NORMAL
• TROUBLE
• TELEPHONE
AOM-TELF
The module contains a panel-controlled LED indicator.
The AOM-TELF is installed in the signaling line circuit of
the Gamewell-FCI Emergency Voice Evacuation Systems.
The AOM-TELF is designed to fit into a 4" (10.16 cm) square
junction box 2 1/8" (5.5 cm) deep.
Features
• Listed under UL® Standard UL 864 and UL2572 for
Mass Notification.
•
The Velociti® Series use a communication protocol that
substantially increases the speed of communication
between the SLC devices and certain Gamewell-FCI analog addressable fire alarm controls. These devices operate
in a grouped fashion. If one of the devices in the group has
a status change, the panel’s microprocessor stops the
group poll and concentrates on the single device. The net
result is a superior response speed up to five times greater
than earlier designs.
• Designed as a compact size to allow easy installation.
Ordering Information
Supervisory Current:
Alarm Current:
Operating
Temperature:
Relative Humidity:
Part Number
Description
AOM-TELF
Telephone monitor module
•
• Provides Class A, fault tolerant, or Class B wiring.
•
• Includes a bicolor LED that flashes green whenever the
module is addressed, and lights steady red upon
activation.*
•
*Note: Only the red LED is operative in panels that do not operate
in Velociti® mode.
Specifications
AOM-TELF .0024 A
AOM-TELF .0075 A
32° to 120° F (0° to 49° C)
10 to 93% relative humidity
(non-condensing)
Dimensions:
4 1/2” H x 4” W x 1 1/4” D
(11.4 H x 10.16 W x 3.2 D cm)
End-of-Line Resistance: AOM-TELF—3.9K
SIGNALING
FM
Velociti® and E3 Series® are registered trademarks of Honeywell International Inc.
®
UL is a registered trademark for Underwriter’s Laboratories Inc.
APPROVED
S1949
MEA
Approved
3023594 227-03 E Vol. IV 7300-1703:0107
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9020-0628 Rev. G page 1 of 1