System Sensor M500X Description Style 7 Isolator Module The System Sensor M500X Fault Isolator modules enable part of the communications signaling line circuit to continue operating when a short circuit occurs. The System Sensor M500X Isolator Module is an automatic switch that opens when the line voltage drops below four volts. This module is rigorously designed and tested for electromagnetic compatibility and environmental reliability, in many cases exceeding industry standards. When installing Isolator Modules, the modules should be spaced between groups of sensors or modules in a signaling line circuit to protect the remainder of the signaling line circuit. If a short occurs between any two isolators, then both isolators immediately switch to an open circuit state and isolate the devices between them. The remaining units on the signaling line circuit continue to operate. It is recommended that you do not add more than 20 devices for each group. An LED indicator flashes in the normal condition and lights during a short circuit condition. When the short circuit is removed, the module will automatically restore the entire signaling line circuit. Specifications Standby Current: Operating Temperature Range: Humidity Range: Voltage Range: Communication Line Impedance: Isolation Current: Fault Detection Delay: Fault Detection Threshold: Line Restoration Threshold: Dimensions: .00045 amps. max. 32° F to 120° F (0° C to 49° C) 10% to 93% non-condensing 15 - 32 VDC 40 Ohms 5 mA max. 250 ms min. M500X Features • Up to 20 addressable devices may be grouped between isolator modules. • Offers panel controlled status LED. • Includes low standby current. • Mounts in a standard 4” junction box. • Wiring terminals are easily manageable for troubleshooting purposes. Ordering Information Part Number Description M500X Isolator Module 4 volts 7 volts 4.5” H x 4” W .25” D 11.4 H x 10.2 W x .6 D cm) Mounts to a 4” square by 2.8”D (10. 2 x 7.1 cm) deep box) *Normal operating current. During power failure, current drops to 0.045 amp, since the back light is extinguished. SIGNALING S1949 E3 Series® and NetSOLO® are registered trademarks of Honeywell International Inc. C FM APPROVED UL R US LISTED 7300-1653:0103 GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. www.gamewell-fci.com 9020-0677 Rev. B page 1 of 1 ©2014 Honeywell International Inc. All rights reserved.