PLC4000 SERIES

PLC4000 SERIES
120 WATT DC-DC POWER SUPPLY FOR THE
ALLEN BRADLEY 1771 PLC SYSTEM
FEATURES
•
•
•
•
Active Current Sharing
Full Redundant Operation
Hot Swap Capability
Remote Sense
Input
Input Power: 215 watts max.
Status Alarm: Signals PLC if input voltage drops below specified
range.
Transient Protection: Fuse and back to back zener diodes protect
against catastrophic failure.
Reverse Polarity Protection: Unit will not turn on if re- verse polarity
is detected.
Isolation: 725V for 1 minute, 850V for 1 second. Conditions: input to
output and input to case.
Output
•
•
•
•
Monitor & Alarm Status
Hold Up Time - 20mS
Multiple Input Voltage Ranges
Input & Output Protection
General Description
The lntronics’ PLC4xxx is an external DC-DC power supply designed
to completely and safely power a fully loaded Allen Bradley 1771 PLC.
The PLC4xxx can be operated in "stand alone" or "redundant mode"
for high availability system configurations. The units mount externally
to the 1771 PLC to maximize available I/O slots and provide up to 24
amps @ 5Vdc to power most standard 1771 PLC rack configurations.
The units contain appropriate monitoring and alarm circuitry to
interface with the 1771 PLC rack. In the event of input power failure,
the units have sufficient hold up time to ensure orderly system
shutdown.
General Specifications
Output Voltage: 4.87 - 5.25 Vdc (normal range for the 1771 PLC
Size: 9" x 8" x 3.8" - Refer to figure 1.
system, including noise and ripple.)
Power supply and System Interface:
Current Range (non-redundant): 2 A min., 24 A max.
Current Range (redundant): 4 A min., 24 A max.
Refer to fig. 2 for stand alone configuration.
Refer to fig. 3 for redundant mode configuration.
Remote Sense: Maintains accurate voltage at the PLC with
Fuse: user accessible.
recommended cable (up to 4 ft of 12 AWG wire).
Input Cable: 14 AWG wire.
Overcurrent: Unit will shutdown at 110-130% of rated output
Output Cable: 12 AWG wire, 4 foot max.
current. Reset by cycling power off for 15 seconds.
LED Indicator: Input and output voltages are within specified limits when
Overvoltage: Unit shuts down if output voltage exceeds 5.5 V. For
illuminated.
redundant configuration, range is 5.5 - 6.0 V.
Safety Agency Approval: Pending (UUCSA/CE).
Undervoltage: Provides status alarm.
Turn on Time: 4 sec. max. to specified output range.
Ripple: 35 mV max. p-p, ripple + noise: 50 mV max. p-p measured
at the PLC power input (through 4’ cable).
Load Sharing: Active load sharing is enabled in redundant
configuration.
Hold up Time: 20 mS min. after a 2 mS ride-through under worst
case line and load conditions.
Ordering Information
Model Number
Input Voltage
PLC4024
20 – 32 Vdc (24 V nominal)
PLC4048
40 – 62 Vdc (48 V nominal)
PLC4125
90 – 145 Vdc (125 V nominal)
Transient Load: Maintains specified operation for up to a 25%
load change. Shutdown may result for transients greater than 25%.
Status Output: Closed relay contact when outputs are within
specified range.
PE Output: Power good signal to the PLC 1771 rack.
Rockwell Automation
Encompass Partner
Intronics, Inc. • 1400 Providence Highway, Building #2 • Norwood, MA 02062 • Phone: 781-551-5500 • Fax: 781-551-5555
Toll Free: 800-367-0004 • www.intronicspower.com
Mechanical Specifications and Connection Diagrams
Ordering Information
Mechanical Configuration – Figure 1
.250
Model Number
Input Voltage
PLC4024
20 – 32 Vdc (24 V nominal)
PLC4048
40 – 62 Vdc (48 V nominal)
PLC4125
90 – 145 Vdc (125 V nominal)
Intronics
DC-DC Converters
J4
7.500
8.000
FUSE
J5
.203 (6 plcs)
#10 Screw
Cables
PLC4XXX
J3
J1
LED
CK1 – Stand alone configuration
J2
IPN: 808-19960-10 (figure 2)
.335
4.115
8.230
9.00
Qty
Cable ID
Length
Input Power
1
J1
6’
Status Line
1
J2
5’
Single PLC
1
S1/J5
4’
CK2 – Redundant configuration
IPN: 808-19960-20 (figure 3)
3.80
SIDE VIEW
Single Unit Configuration – Figure 2
Qty
Cable ID
Length
INPUT POWER
2
J1
6’
STATUS LINE
2
J2
5’
Power Output
2
J5
2’
Current Share
1
J3
2’
Redundant PLC
1
R1/TB1
2’
Terminal Block
1
TB1
N/A
Note: Cable kits must be ordered separately.
All connectors are included in cable kits.
J1
J2
PLC4xxx
Power
Supply
S1/J5
Pin Connections & Description
1771 PLC
Redundant Unit Configuration – Figure 3
Tb1
J1
J2
PLC4xxx
Power
Supply
J5
R1/TB1
J3
J1
J2
1771 PLC
J5
PLC4xxx
Power
Supply
Pin
Description
Pin
Description
J1-1
+V in
J5-A1
+5Vdc out
J1-2
-V in
J5-1
N/C
J1-3
Chassis Gnd
J5-2
P/E
J2-1
- Status
J5-3
+Sense
J2-2
+ Status
J5-4
-Sense
J3-1
+V out
J5-A2
+5Vdc Return
J3-2
+V out 2
Case
Chassis Gnd
J3-3
Share out
J3-4
Share in
J3-5
Blank 2
J3-6
Blank
J3-7
Share Return
J3-8
N/C
J3-9
Shield
Case
Chassis Gnd
N/C = No Connect
Note: In hazardous environments, input power must be
turned off when fuses are being changed or units are
being swapped.
Environmental Specifications
Note: Specifications are subject to change without
notice.
Storage Temperature: -40°C to + 85°C
Operating Temperature: + 0°C to + 60°C, baseplate + 75°C
Humidity: 5 – 95% non-condensing
Intronics, Inc. • 1400 Providence Highway, Building #2 • Norwood, MA 02062 • Phone: 781-551-5500 • Fax: 781-551-5555