UNIVERSAL IN-LINE TRANSDUCER AMPLIFIER MODEL UBP-10

MODEL UBP-10
UNIVERSAL IN-LINE
TRANSDUCER AMPLIFIER
BI-POLAR SUPPLY, 0-10 VOLT OUTPUT
2080 Arlingate Lane, Columbus, Ohio 43228 • (614) 850-5000
Sensotec, Inc.
2080 Arlingate Lane
Columbus, Ohio 43228
Copyright 1995 by Sensotec, Inc. all rights reserved
Telephone: (614) 850-5000
FAX: (614) 850-1111
Toll Free: 1-800-848-6564
E-mail: [email protected]
WWW: http://www.sensotec.com
Model UBP-10, Universal In-line Transducer Amplifier
(Bi-polar supply, 0-10 volt output)
Sensotec Part Number: 008 - 0319 - 00
Rev. C: February, 1999
IMPORTANT! IT IS RECOMMENDED THAT YOU READ
THIS DOCUMENT THOROUGHLY BEFORE APPLYING
POWER TO THIS UNIT. THIS DOCUMENT CONTAINS
INFORMATION ON WIRING, CALIBRATION, AND USE
OF FEATURES.
Table Of Contents
Chapter 1
INTRODUCTION
1.1 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1.2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
1.3 Layout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Chapter 2
INSTALLATION / SETUP
2.1 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
2.2 Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
2.3 Panel Mounting Template. . . . . . . . . . . . . . . . . 2-5
Chapter 3
CALIBRATION
3.1 Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.2 Using Shunt Calibration . . . . . . . . . . . . . . . . . . 3-1
Chapter 4
WARRANTY / REPAIR POLICY
4.1 Limited Warranty on Products . . . . . . . . . . . . .
4.2 Service Under Warranty . . . . . . . . . . . . . . . . . .
4.3 Non-Warranty Service . . . . . . . . . . . . . . . . . . .
4.4 Repair Warranty . . . . . . . . . . . . . . . . . . . . . . . .
4-1
4-1
4-2
4-2
Chapter 1
INTRODUCTION
1.1 Overview
Sensotec’s Universal In-Line Amplifiers are housed in a
small plastic package, which is connected between the
transducer and a readout instrument. The Model UBP-10
amplifier supplies a highly regulated bridge excitation voltage for the transducer and converts the millivolt signal of
the transducer to a 0-10 volt DC signal. The Universal InLine features include three selectable excitation voltages,
programmable gain settings, a wide adjustment range on
the zero and a buffered solid-state shunt cal relay for
quick calibration.
008-0319-00 page 1-1
1.2 Specifications
Power Requirements:
24 - 32 volts DC (with (-)Output voltage
= 1/3 of supply)
Bridge Excitation:
10, 5, or 3 volts DC @ 70 mA (user
selectable)
Output Voltage Range:
0 - 10 volts @ 2 mA
Frequency Response:
DC - 5000 Hz
Zero Balance Range:
+/- 50% coarse, +/- 15% fine adjustment
range
Gain Adjustment Range:
Switch selectable (1 to 10 mV/V), +/25% fine adjust
Short Circuit Protection:
(+)Output to (-)Output
Environment Protection:
IP-66 or NEMA4
Shunt Calibration:
Solid-state relay
Long Term Zero Drift:
.1% of Full Scale per 6 months
page 1-2
Model UBP-10 Universal In-Line Amplifier
1.3 Layout
Figure 1-1: Layout of Model UBP-10 In-Line Amplifier
008-0319-00 page 1-3
page 1-4
Model UBP-10 Universal In-Line Amplifier
Chapter 2
INSTALLATION / SETUP
2.1 Wiring
The Model UBP-10 Universal In-Line Amplifier (Sensotec
p/n 060-6827-06) can be powered from a 24 to 32 volt single voltage supply. The following diagram shows the wiring transducer, power supply and readout.
Cables should be stripped back 3 inches with the wires
stripped and tinned 1/2 inch. Connections to the terminal
block are made by pressing the orange levers and inserting the wires into the holes next to the levers. The terminal block will accept wire up to AWG 20.
Install a shunt cal resistor with the value specified on the
transducer data sheet.
Figure 2-1: Transducer to In-Line Wiring
008-0319-00 page 2-1
Figure 2-2: 24 to 32 Single Voltage Supply to In-Line Wiring
NOTE: For the single voltage supply, (-)OUTPUT is
biased approximately 1/3 of the supply voltage. The output will swing 0-10 VDC around the (-)OUTPUT reference
voltage.
page 2-2
Model UBP-10 Universal In-Line Amplifier
2.2 Setup
Use the following procedure for setting up the excitation
and the coarse gain:
1. Determine the EXCITATION VOLTAGE required by
the transducer being used.
2. Set the EXCITATION SELECT JUMPER as shown
below: (See Fig.1-1 for location of jumpers)
3. Determine the sensitivity of the transducer in mV/V
from the transducer calibration sheet.
4. Set the COARSE GAIN SWITCH (See Fig.1-1 for location of switch) to the nearest mV/V setting in the corresponding excitation column in Table 1.
008-0319-00 page 2-3
Table 1: Coarse Gain Setup
SWITCH
POSITION
ON
10
5
3
1
1 mV/V
2 mV/V
3.2 mV/V
2&3&5
1.2 mV/V
2.4 mV/V
4 mV/V
2&4
1.5 mV/V
3.0 mV/V
5 mV/V
2
2 mV/V
4 mV/V
6.6 mV/V
3&6
2.5 mV/V
5 mV/V
8.32 mV/V
3
3.0 mV/V
6 mV/V
10 mV/V
4&7
3.5 mV/V
7 mV/V
11.6 mV/V
4
4 mV/V
8 mV/V
13.2 mV/V
5&8
4.5 mV/V
9 mV/V
15 mV/V
5
5 mV/V
10 mV/V
16.6 mV/V
6
6 mV/V
12 mV/V
20 mV/V
7
7 mV/V
14 mV/V
23.2 mV/V
8
8 mV/V
16 mV/V
26.6 mV/V
page 2-4
EXCITATION (VDC)
Model UBP-10 Universal In-Line Amplifier
2.3 Panel Mounting Template
The Universal In-Line Amplifier can be easily mounted to
a panel by using the template below for marking the holes
in the panel. The cover must be removed to get access to
the mounting holes. Use # 6 or # 8 screws for mounting
box to panel.
Figure 2-3: Panel Mounting Template
008-0319-00 page 2-5
page 2-6
Model UBP-10 Universal In-Line Amplifier
Chapter 3
CALIBRATION
3.1 Calibration
Step 1. Apply power and allow unit to stabilize for 10 minutes.
Step 2. With zero load or pressure on the transducer,
adjust the ZERO potentiometers to indicate zero on
the readout instrument or voltmeter connected to the
output.
Step 3. Apply full scale pressure or load to the transducer
and adjust the SPAN potentiometer to indicate full
scale on the readout instrument or voltmeter.
Step 4. Re-check zero and full scale (repeat steps 2 &
3).
3.2 Using Shunt Calibration
Sensotec transducers feature a calibration technique
called shunt calibration. This method applies a known
resistance across one leg of the transducer, which simulates an output as if a load or pressure was applied to the
transducer. When performing shunt calibration, the transducer should be at ZERO pressure or load. The full scale
output and shunt cal output is found on the TRANSDUCER CALIBRATION SHEET. This information can be
used to calibrate the amplifier’s output voltage and the
readout’s display with the following equations.
008-0319-00 page 3-1
TRANSDUCER CALIBRATION DATA
Full Scale Output =
____________
mV/V.
Shunt Resistor Value of
____________
Ohms
Shunt Cal Output =
____________
mV/V.
The following equations are used to calculate output voltage and display units:
FORMULA TO CALCULATE OUTPUT VOLTAGE
SHUNT CAL OUTPUT
FULL SCALE OUTPUT
X
10V
= OUTPUT VOLTAGE
__________________
X
10V
= ________________
FORMULA TO CALCULATE DISPLAY UNITS
SHUNT CAL OUTPUT
FULL SCALE OUTPUT
X FULL SCALE UNITS
= DISPLAY UNITS
__________________
X ________________
= _____________
Step 1. Apply power and allow the amplifier to warm up.
Step 2. With zero load or pressure on the transducer,
adjust the ZERO potentiometer to indicate zero on
the readout instrument or voltmeter.
page 3-2
Model UBP-10 Universal In-Line Amplifier
Step 3. Connect a jumper across PINS 5 & 6 of the power
terminals (See Fig. 1-1) or wire in a switch as shown
in wiring section. Adjust the SPAN potentiometer to
the calculated voltage or calculated units on the
readout instrument or voltmeter.
Step 4. Disconnect the shunt cal jumper or release the
shunt cal switch and repeat steps 2 & 3 if needed.
008-0319-00 page 3-3
page 3-4
Model UBP-10 Universal In-Line Amplifier
Chapter 4
WARRANTY / REPAIR POLICY
4.1 Limited Warranty on Products
Any of our products which, under normal operating conditions, proves
defective in material in workmanship within one year from the date of
shipment by SENSOTEC, will be repaired or replaced free of charge
provided that you obtain a return material authorization from SENSOTEC and send the defective product, transportation charges prepaid
with notice of the defect, and establish that the product has been
properly installed, maintained, and operated within the limits of rated
and normal usage. Replacement product will be shipped F.O.B. our
plant. The terms of this warranty do not extend to any product or part
thereof which, under normal usage, has an inherently shorter useful
life than one year. The replacement warranty detailed here is the
buyer's exclusive remedy, and will satisfy all obligations of SENSOTEC whether based on contract, negligence, or otherwise. SENSOTEC is not responsible for any incidental or consequential loss or
damage which might result from a failure of any SENSOTEC product.
This express warranty is made in lieu of any and all other warranties,
express or implied, including implied warranty of merchantability or fitness for particular purpose. Any unauthorized disassembly or
attempt to repair voids this warranty.
4.2 Service Under Warranty
Advanced authorization is required prior to the return to SENSOTEC.
Before returning the items, either write to the Customer Service
Department c/o SENSOTEC, Inc., 2080 Arlingate Lane, Columbus,
Ohio 43228, or call (800) 848-6564 with: 1) a part number; 2) a serial
number for the defective product; 3) a technical description* of the
defect; 4) a no-charge purchase order number (so products can be
returned to you correctly); and 5) ship and bill addresses. Shipment
to SENSOTEC shall be at Buyer's expense and repaired or replacement items will be shipped F.O.B. our plant in Columbus, Ohio. Nonverified problems or defects may be subject to an evaluation charge.
Please return the original calibration data with the unit.
008-0319-00 page 4-1
4.3 Non-Warranty Service
Advance authorization is required prior to the return to SENSOTEC.
Before returning the item, either write to the Customer Service
Department c/o SENSOTEC, Inc., 2080 Arlingate Lane, Columbus,
Ohio 43228, or call (800) 848-6564 with: 1) a model number; 2) a
serial number for the defective product; 3) a technical description* of
the malfunction; 4) a purchase order number to cover SENSOTEC's
repair cost; and 5) ship and bill addresses. After the product is evaluated by SENSOTEC, we will contact you to provide the estimated
repair costs before proceeding. Shipment to SENSOTEC shall be at
Buyer's expense and repaired items will be shipped to you F.O.B.,
our plant in Columbus, Ohio. Please return the original calibration
data with the unit.
4.4 Repair Warranty
All repairs of SENSOTEC products are warranted for a period of 90
days from date of shipment. This warranty applies only to those
items which were found defective and repaired, it does not apply to
products in which no defect was found and returned as is or merely
recalibrated. Out of warranty products may not be capable of being
returned to the exact original specifications or dimensions.
* Technical description of the defect: In order to properly repair a
product, it is necessary for SENSOTEC to receive information specifying the reason the product is being returned. Specific test data,
written observations on the failure and the specific corrective action
you require is needed.
page 4-2
Model UBP-10 Universal Inline Amplifier