PC3F1558IUF00 Hydronic Circulating 3 Speed Pump SPECIFICATION DATA APPLICATION The PC3F in-line, wet rotor circulator with universal flange is designed for applications in closed-loop hydronic heating and cooling systems, as well as in solar-powered systems. The pump is non-submersible and for use in dry, frost-free, wellventilated installations. SPECIFICATIONS Rate of flow: Up to 15 gpm (56.8 lpm) Pressure head: Up to 19.4 ft (6 m) L1 Voltage: 115 VAC +/- 10% 60Hz Amperage: See “Speed switching” on page 2. Max. Pressure: 145 psi (at room temperature); 50 psi (at 200°F [93°C]) L3 L2 L4 Temperature Range: Ambient temperature: 32°F to 104°F (0°C to 40°C) Media temperature: 14°F to 230°F (-10°C to 110°C) [to 200°F (93°C) with optional check valve installed] L5 Storage Temperature: -40°F to 100°F (-40° to 66°C) Standards: Insulation Class F Temperature class: TF 95 M32832A Fig. 1. Pump dimensions in in. (mm). L1 L2 L3 L4 L5 6.5 (165.5) 5.5 (140) 4.7 (118) 6.6 (167) 3.2 (80.2) Shipping Weight: 7.8 lbs (3.54 Kg) 68-3083-02 PC3F1558IUF00 HYDRONIC CIRCULATING 3 SPEED PUMP Materials Component Media Clean water or water with up to 20% glycol. Up to 50% glycol may be used, but flow characteristics will differ from these specifications. Material Pump body Cast iron Impeller Polyamide Shaft Ceramic 20 Bearing Ceramic 18 Bearing plate Stainless steel Can Stainless steel PC3F1558IUF00 22 WITHOUT CHECK VALVE WITH CHECK VALVE 16 14 H 12 (FEET) 10 Control: 3-step switch with manual speed selection 3 8 Motor Protection The motor includes an internal thermal overload protection. External motor protection is not required. 6 2 4 1 2 Speed switching Three speed, with manual selector. 0 0 2 4 6 8 10 12 14 16 US GPM Speed Volts 1 2 115 3 Amps Watts 0.28 32 0.48 55 0.74 85 18 M32852A Fig. 2. Flow curve characteristics. Optional and Replacement Parts Check valves: PCV100 Flange gasket: PCG100 Flange Connections Universal flange Bolt hole spacing: 3-5/32 in. (80.2 mm) Bolt holes: 1/2 in. (12.7 mm) Table 1. Cross Reference for Pump Replacement Honeywell Model Grundfos Pump Speed Length PC3F1558IUF00 6.5” Single Speed Taco 3-Speed Single Speed Bell & Gossett Armstrong 3-Speed Wilo Single Speed High UP-42F UP-42F-FC 00R High NRF-22 UPS15-58 High 005F UPS15-58-FC High 007F 00R Med LR-20WR 008F 008F-IFC Medium UP15-42FC UPS15-58 Low 005F-IFC 00R Low UPS15-58-FC Low 006F 006F-IFC 007F-IFC Low UP15-18F UP15-18F-FC NRF9F/LW NRF-25 Med Astro 30 Astro 30-3 Astro 50-3 Astro 230C1 3-Speed Star 16 Star S16 High Star S16 Med Star 5 S16 Low The information in this table is based on publicly available information as of the date of this publication. Honeywell is not liable if information is found to be incorrect. If the cross referenced model uses a flow check valve, then use a flow check with the Honeywell model as well. Each Honeywell circulator replaces both regular and rotated flange models. Automation and Control Solutions Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 customer.honeywell.com ® U.S. Registered Trademark © 2012 Honeywell International Inc. 68-3083—02 M.S. Rev. 09-12 Printed in United States