PC3F1558IUF00 Hydronic Circulating 3 Speed Pump

PC3F1558IUF00 Hydronic
Circulating 3 Speed Pump
SPECIFICATION DATA
APPLICATION
The PC3F in-line, wet rotor circulator with universal flange is
designed for applications in closed-loop hydronic heating and
cooling systems, as well as in solar-powered systems. The
pump is non-submersible and for use in dry, frost-free, wellventilated installations.
SPECIFICATIONS
Rate of flow: Up to 15 gpm (56.8 lpm)
Pressure head: Up to 19.4 ft (6 m)
L1
Voltage:
115 VAC +/- 10% 60Hz
Amperage:
See “Speed switching” on page 2.
Max. Pressure:
145 psi (at room temperature);
50 psi (at 200°F [93°C])
L3
L2
L4
Temperature Range:
Ambient temperature: 32°F to 104°F (0°C to 40°C)
Media temperature: 14°F to 230°F (-10°C to 110°C) [to 200°F
(93°C) with optional check valve installed]
L5
Storage Temperature: -40°F to 100°F (-40° to 66°C)
Standards:
Insulation Class F
Temperature class: TF 95
M32832A
Fig. 1. Pump dimensions in in. (mm).
L1
L2
L3
L4
L5
6.5 (165.5)
5.5 (140)
4.7 (118)
6.6 (167)
3.2 (80.2)
Shipping Weight: 7.8 lbs (3.54 Kg)
68-3083-02
PC3F1558IUF00 HYDRONIC CIRCULATING 3 SPEED PUMP
Materials
Component
Media
Clean water or water with up to 20% glycol. Up to 50% glycol
may be used, but flow characteristics will differ from these
specifications.
Material
Pump body
Cast iron
Impeller
Polyamide
Shaft
Ceramic
20
Bearing
Ceramic
18
Bearing plate
Stainless steel
Can
Stainless steel
PC3F1558IUF00
22
WITHOUT CHECK VALVE
WITH CHECK VALVE
16
14
H 12
(FEET)
10
Control: 3-step switch with manual speed selection
3
8
Motor Protection
The motor includes an internal thermal overload protection.
External motor protection is not required.
6
2
4
1
2
Speed switching
Three speed, with manual selector.
0
0
2
4
6
8
10
12
14
16
US GPM
Speed
Volts
1
2
115
3
Amps
Watts
0.28
32
0.48
55
0.74
85
18
M32852A
Fig. 2. Flow curve characteristics.
Optional and Replacement Parts
Check valves: PCV100
Flange gasket: PCG100
Flange Connections
Universal flange
Bolt hole spacing: 3-5/32 in. (80.2 mm)
Bolt holes: 1/2 in. (12.7 mm)
Table 1. Cross Reference for Pump Replacement
Honeywell
Model
Grundfos
Pump Speed
Length
PC3F1558IUF00 6.5”
Single
Speed
Taco
3-Speed
Single
Speed
Bell &
Gossett
Armstrong
3-Speed
Wilo
Single
Speed
High
UP-42F
UP-42F-FC
00R High NRF-22
UPS15-58 High
005F
UPS15-58-FC High 007F
00R Med LR-20WR
008F
008F-IFC
Medium
UP15-42FC
UPS15-58 Low
005F-IFC 00R Low
UPS15-58-FC Low 006F
006F-IFC
007F-IFC
Low
UP15-18F
UP15-18F-FC
NRF9F/LW
NRF-25 Med
Astro 30
Astro 30-3
Astro 50-3
Astro 230C1
3-Speed
Star 16 Star S16 High
Star S16 Med
Star 5
S16 Low
The information in this table is based on publicly available information as of the date of this publication. Honeywell is not liable if
information is found to be incorrect.
If the cross referenced model uses a flow check valve, then use a flow check with the Honeywell model as well.
Each Honeywell circulator replaces both regular and rotated flange models.
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com
® U.S. Registered Trademark
© 2012 Honeywell International Inc.
68-3083—02 M.S. Rev. 09-12
Printed in United States