SPECIFICATION DATA
APPLICATION
The PC3F in-line, wet rotor circulator with universal flange is
designed for applications in closed-loop hydronic heating and
cooling systems, as well as in solar-powered systems. The
pump is non-submersible and for use in dry, frost-free, wellventilated installations.
SPECIFICATIONS
Rate of flow: up to 34 gpm (128.7 lpm)
Pressure head: up to 31 ft (9 m)
L1
Voltage:
115VAC +/-10% 60hz
Amperage: See “Speed switching” on page 2.
Max. Pressure:
145 psi (at room temperature);
50 psi (at 200°F [93°C])
L3
L2
L4
Temperature Range:
Ambient temperature: 32°F to 104°F (0°C to 40°C)
Media temperature: 14°F to 230°F (-10°F to 110°C) [to 200°F
(93°C) with optional check valve installed]
L5
Storage Temperature: -40°F to 100°F (-40° to 66°C)
Standards:
Insulation Class F
Temperature Class FT 95
M32832A
Fig. 1. Pump dimensions in in. (mm).
L1
L2
6.5 (165.5)
6.1 (155)
L3
L4
6.5 (165.5) 7.75 (197)
L5
3.2 (80.2)
Shipping weight: 9.5 lbs (4.32 Kg)
68-3084-02
PC3F2699IUF00 HYDRONIC CIRCULATING 3 SPEED PUMP
Materials
Component
Media
Clean water or water with up to 20% glycol. Up to 50% glycol
may be used, but flow characteristics will differ from these
specifications.
Material
Pump body
Cast iron
Impeller
Polyamide
Shaft
Ceramic
Ceramic
Bearing plate
Stainless steel
Can
Stainless steel
20
10
Motor protection
The motor includes an internal thermal overload protection.
External motor protection is not required.
1
2
115
3
1
0
0
125
1.52
175
1.78
205
5
10
15
20
US GPM
25
30
35
M32833A
Fig. 2. Flow curve characteristics.
Watts
1.09
2
1
5
Speed switching
Three speed, with manual selector.
Amps
3
H 15
(FEET)
Control: 3-step switch with manual speed selection
Volts
WITHOUT CHECK VALVE
WITH CHECK VALVE
25
Bearing
Speed
PC3F2699IUF00
30
Optional and Replacement Parts
Check valves: PCV125
Flange gasket: PCG100
Flange Connections
Universal flange
Bolt hole spacing 3-5/32 in. (80.2 mm)
Bolt holes 1/2 in. (12.7 mm)
Table 1. Cross Reference for Pump Replacement
Honeywell
Model
Grundfos
Pump Speed
Length
High
PC3F2699IUF00 6.5”
Single
Speed
Taco
3-Speed
Single
Speed
UP26-96F
UPS26-99 High
UP26-96F-FC UPS26-99-FC High
UP26-116F
UP26-116F-FC
Medium UP26-64F
UP26-99FC
UPS26-99 Low
UPS26-99-FC Low
Bell &
Gossett
Armstrong
3-Speed
0011F
0011F-IFC
0013F
0013F-IFC
NRF-36 Med E7
NRF-45 Med Astro 50
Astro 50-3
H-41
0014F
0014F-IFC
Low
Wilo
Single
Speed
Star 30F
Star 32F
3-Speed
S21 High
Star 17 FX S21 Med
NRF-33
Star S21 Low
The information in this table is based on publicly available information as of the date of this publication. Honeywell is not liable if
information is found to be incorrect.
If the cross-referenced model uses a flow check valve, then use a flow check with the Honeywell model as well.
Each Honeywell circulator replaces both regular and rotated flange models.
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com
® U.S. Registered Trademark
© 2012 Honeywell International Inc.
68-3084—02 M.S. Rev. 09-12