BPU-2A Manual

BPU-2A MANUAL
BEARING PROTECTION UNIT
MARCH 1994
REVISION 2
Copyright © 1994 by Startco Engineering Ltd.
All rights reserved.
Publication: BPU-2A-M
Document: S95-BPU2-00000
Printed in Canada
Downloaded from the Internet, see disclaimer.
Startco Engineering Ltd.
BPU-2A Bearing Protection Unit
Disclaimer
DISCLAIMER
This document has been downloaded from the Internet and might not be complete—
document quality and formatting depend on the user's computer. This Internet manual
is intended as a temporary guide—obtain an original document from Startco or from an
authorized Startco distributor.
Specifications are subject to change without notice. Startco Engineering Ltd. is not
liable for contingent or consequential damages, or for expenses sustained as a result
of a malfunction, incorrect application, or incorrect adjustment.
Pub. BPU-2A, March, 1994
Downloaded from the Internet, see disclaimer.
Startco Engineering Ltd.
BPU-2A Bearing Protection Unit
Page i
Rev. 2
TABLE OF CONTENTS
PAGE
TABLE OF CONTENTS ......................................................................................
LIST OF FIGURES .............................................................................................
i
i
1.
GENERAL................................................................................................
1
2.
2.1
2.2
2.3
2.4
OPERATION ............................................................................................
TRIP-AND-ALARM SET POINTS...............................................................
INDICATION AND RESET.........................................................................
CONFIGURATION ...................................................................................
2.3.1 RELAY OPERATION (S1-1) ............................................................
2.3.2 TRIP DIFFERENTIAL (S1-2, S1-3) ..................................................
2.3.3 ALARM DIFFERENTIAL (S1-4)........................................................
2.3.4 BEARING RTD's (S1-5, S1-6) .........................................................
2.3.5 MPU-16A SENSOR TYPE (S1-7, S1-8) ...........................................
2.3.6 MPU-16A/STAND ALONE (W1).......................................................
2.3.7 LATCHING/NON LATCHING (W2)...................................................
BPU-2A/MPU-16A OPERATION WITHOUT A STATOR RTD .....................
1
2
2
2
2
3
3
3
3
3
3
4
3.
3.1
3.2
3.3
3.4
3.5
INSTALLATION ........................................................................................
PANEL-MOUNT CONFIGURATION ..........................................................
SURFACE-MOUNT CONFIGURATION .....................................................
TERMINAL BLOCKS ................................................................................
RTD CONNECTIONS ...............................................................................
POWER SUPPLY.....................................................................................
4
4
4
4
5
5
4.
TECHNICAL SPECIFICATIONS ................................................................
5
5.
ORDERING INFORMATION .....................................................................
6
LIST OF FIGURES
FIGURE
PAGE
1
BPU-2A TYPICAL APPLICATION ..............................................................
7
2
BPU-2A CONFIGURATION.......................................................................
8
3
PANEL-MOUNT BPU-2A OUTLINE AND MOUNTING DETAILS.................
9
4
SURFACE-MOUNT BPU-2A OUTLINE AND MOUNTING DETAILS............
10
Pub. BPU-2A, March, 1994
Downloaded from the Internet, see disclaimer.
Startco Engineering Ltd.
BPU-2A Bearing Protection Unit
Page 1
Rev. 2
BPU-2A
BEARING PROTECTION UNIT
1.
GENERAL
The BPU-2A is a microprocessor-based bearing protection unit. Trip-and-alarm
set points and LED indication are provided for two bearing RTD's. The BPU-2A
can be user configured for 100-ohm platinum (PT100), 100-ohm nickel (NI100),
or 120-ohm nickel (NI120) RTD's. The BPU-2A can trip-and-alarm on bearing
temperature and on the temperature differential between two bearings.
The BPU-2A was designed to add bearing-temperature protection to the
MPU-16A motor protection unit; however, it can be used as a stand-alone unit to
monitor two bearing RTD's. In the stand-alone configuration, two Form A output
contacts can be user configured for fail-safe or non-fail-safe operation.
2.
OPERATION
When used with the MPU-16A, the BPU-2A accepts inputs from two bearing
RTD's and one stator RTD as shown in Figure 1. The stator temperature signal
is fed to the MPU-16A through the BPU-2A relay contacts and external jumper
W1. If the bearing alarm temperature is exceeded, the stator signal is
interrupted and 4AA0 is displayed on the MPU-16A. If the bearing trip
temperature is exceeded, the BPU-2A introduces a trip resistance and 4FFF is
displayed on the MPU-16A. When a bearing temperature trip or alarm occurs,
MPU-16A hot-motor compensation is automatically disabled, MPU-16A pre-trip
stator temperatures are not available, and bearing temperatures can be
determined with the BPU-2A. A bearing temperature trip can be differentiated
from a stator temperature trip by observing the pre-trip value in Mode C. If a
bearing temperature trip occurs, the pre-trip value will be between 230°C and
240°C. If a stator temperature trip occurs, the pre-trip value will be equal to the
temperature set point (Mode 4).
When used with the MPU-16A, jumper W1 must be installed between terminals
10 and 11 and the trip-and-alarm contacts cannot be used in external circuits.
For stand-alone operation, jumper W1 must be removed so that the trip-andalarm contacts can be used.
---CAUTION--IN STAND-ALONE OPERATION, MAKE NO CONNECTIONS TO TERMINALS 7,
8, 9, 17, 18, and 19.
Pub. BPU-2A, March, 1994
Downloaded from the Internet, see disclaimer.
Startco Engineering Ltd.
BPU-2A Bearing Protection Unit
2.1
Page 2
Rev. 2
TRIP-AND-ALARM SET POINTS
Bearing temperature trip-and-alarm set points are adjustable from 60°C to
120°C. Typical set points are 70°C to 100°C for anti-friction bearings and 60°C
to 75°C for journal bearings. Consult the motor manufacturer for recommended
set points.
For differential temperature trip-and-alarm settings, see sections 2.3.2 and 2.3.3.
2.2
INDICATION AND RESET
Two red LED's indicate over-temperature trips and two yellow LED's indicate
over-temperature alarms. A slowly flashing LED indicates the hottest RTD when
a differential temperature trip-or-alarm occurs. A quickly flashing yellow LED
indicates an open or shorted RTD.
Alarms are non-latching and trips can be selected as latching or non-latching.
Install jumper W2 between terminals 5 and 6 for non-latching operation. With
jumper W2 not installed, trips remain latched until RESET is pressed or until
supply voltage is cycled.
When used with the MPU-16A, non-latching operation is usually selected so that
only the MPU-16A requires a reset after a bearing-temperature trip.
2.3
CONFIGURATION
The rear panel must be removed to access configuration switch S1.
Configuration jumpers W1 and W2 are external jumpers on the lower terminal
block.
2.3.1 RELAY OPERATION (S1-1)
Switch S1-1 configures the BPU-2A for fail-safe or non-fail-safe relay operation.
See Figure 2. In the fail-safe mode, output relays are energized when control
power is on and the BPU-2A is not in a trip-or-alarm condition. The output
relays are de-energized if control power is off or if a trip-or-alarm occurs.
BPU-2A labelling shows the relays de-energized. In the non-fail-safe mode,
output relays are energized only during a trip-or-alarm.
When used with MPU-16A, select the fail-safe mode.
Factory Selection ............................................ Fail Safe
Pub. BPU-2A, March, 1994
Downloaded from the Internet, see disclaimer.
Startco Engineering Ltd.
BPU-2A Bearing Protection Unit
Page 3
Rev. 2
2.3.2 TRIP DIFFERENTIAL (S1-2, S1-3)
Switches S1-2 and S1-3 set the BPU-2A trip differential. Selections available
are: Disabled, 10°, 15°, or 20°. See Figure 2.
Factory Selection ............................................ Disabled
2.3.3 ALARM DIFFERENTIAL (S1-4)
Switch S1-4 sets the alarm differential if the trip differential is enabled.
Selections available are: 50% or 80% of the trip differential. See Figure 2.
Factory Selection ............................................ 50% of Trip Differential
2.3.4 BEARING RTD's (S1-5, S1-6)
Switches S1-5 and S1-6 configure the BPU-2A for the bearing-RTD type.
Selections available are: 100-ohm platinum (PT100), 100-ohm nickel (NI100), or
120-ohm nickel (NI120). See Figure 2.
Factory Selection ............................................ PT100
2.3.5 MPU-16A SENSOR TYPE (S1-7, S1-8)
Switches S1-7 and S1-8 configure the BPU-2A to match the MPU-16A sensor
type. Selections available are: PT100, NI100, or NI120. See Figure 2.
Factory Selection ............................................ PT100
2.3.6 MPU-16A/STAND ALONE (W1)
External jumper W1, between terminals 10 and 11, configures the BPU-2A for
use with the MPU-16A or for stand-alone operation. Jumper W1 is installed for
use with the MPU-16A and must be removed for stand-alone operation. See
Figure 1.
Factory Selection ............................................ Installed (MPU-16A)
2.3.7 LATCHING/NON LATCHING (W2)
External jumper W2, between terminals 5 and 6, configures the BPU-2A for
latching or non-latching trips. Jumper W2 is installed for non-latching trips and
must be removed for latching trips. See Figure 1.
Factory Selection ............................................ Installed (Non Latching)
Pub. BPU-2A, March, 1994
Downloaded from the Internet, see disclaimer.
Startco Engineering Ltd.
BPU-2A Bearing Protection Unit
2.4
Page 4
Rev. 2
BPU-2A/MPU-16A OPERATION WITHOUT A STATOR RTD
If a stator RTD is not used, connect a 120-ohm resistor to the BPU-2A stator
RTD terminals and enter the Mode-4 default values (trip 125°C, alarm 100°C) in
the MPU-16A.
With no BPU-2A trips-or-alarms, the temperature display on the MPU-16A will
indicate a temperature corresponding to the 120-ohm resistance.
3.
INSTALLATION
3.1
PANEL-MOUNT CONFIGURATION
Outline dimensions and mounting details for the panel-mount BPU-2A are
shown in Figure 3. The BPU-2A mounts in a 92-mm square cutout (1/4 DIN)
and is secured to the panel by the panel-mount clamp. To mount the BPU-2A,
insert it through the panel cutout and slip the panel-mount clamp over the
BPU-2A body. Slide the clamp forward until the latch tabs snap into the mating
holes. Lock the unit in place by tightening the four clamp screws against the
mounting panel.
---CAUTION--OVER TIGHTENING THE CLAMP SCREWS WILL DEFORM THE CLAMP AND
CAUSE THE LATCH TABS TO RELEASE.
3.2
SURFACE-MOUNT CONFIGURATION
Outline dimensions and mounting details for the surface-mount BPU-2A are
shown in Figure 4. Mount the BPU-2A using M4 or #8 screws and external-tooth
lockwashers.
3.3
TERMINAL BLOCKS
Connections to the BPU-2A are made through two plug-in, wire-clamping
terminal blocks. Each terminal will accept one #14 AWG conductor.
Terminal blocks are keyed so that supply voltage cannot be applied to the RTD
inputs. The line-voltage terminal block has a keying pin blocking terminal 4.
Pub. BPU-2A, March, 1994
Downloaded from the Internet, see disclaimer.
Startco Engineering Ltd.
BPU-2A Bearing Protection Unit
3.4
Page 5
Rev. 2
RTD CONNECTIONS
The BPU-2A uses three-wire lead compensation which requires the three leads
to a RTD to have equal resistance. This requirement can be met with shielded,
three-conductor #18 AWG to #22 AWG cable. The RTD cable shields must be
grounded at the BPU-2A only. The output cable to the MPU-16A must be
grounded at the MPU-16A only.
3.5
POWER SUPPLY
The BPU-2A can be ordered for either 120- or 240-Vac operation. Connect
supply voltage to terminals 2 and 3 (L1 & L2) as shown in Figure 1. In 120-Vac
systems, L2 is usually designated as the neutral conductor. Ground terminal 1.
4.
TECHNICAL SPECIFICATIONS
Supply:
120/240 Vac (+10%, -30%), 50/60 Hz, 5 VA
Environment:
Operating Temperature......................... -40°C to 60°C
Storage Temperature ............................ -55°C to 80°C
Output Relays:
Contact Rating ...................................... 1 mA to 8 A Resistive,
250 Vac or 30 Vdc.
0.125 hp @ 120/240 Vac
Contact Configuration ........................... Form A
Operating Mode .................................... Fail Safe or Non Fail Safe
Bearing-RTD Inputs:
RTD Type ............................................. 100-: Platinum (DIN43760),
100-: Nickel, or
120-: Nickel.
Lead Compensation .............................. 25 : max.
Temperature Range .............................. 60°C to 120°C
Differential Range ................................. 10° to 20°
Accuracy .............................................. ±3°C
Stator-RTD Input:
RTD Type ............................................. 100-: Platinum (DIN43760),
100-: Nickel, or
120-: Nickel.
Pub. BPU-2A, March, 1994
Downloaded from the Internet, see disclaimer.
Startco Engineering Ltd.
BPU-2A Bearing Protection Unit
5.
Page 6
Rev. 2
ORDERING INFORMATION
Example:
Pub. BPU-2A, March, 1994
BPU-2A-P12-00 specifies a panel-mount
Protection Unit with a 120-Vac supply.
BPU-2A
Bearing
Downloaded from the Internet, see disclaimer.
Startco Engineering Ltd.
BPU-2A Bearing Protection Unit
Page 7
Rev. 2
BPU-2A TYPICAL APPLICATION
FIGURE 1
Pub. BPU-2A, March, 1994
Downloaded from the Internet, see disclaimer.
Startco Engineering Ltd.
BPU-2A Bearing Protection Unit
Page 8
Rev. 2
BPU-2A CONFIGURATION
FIGURE 2
Pub. BPU-2A, March, 1994
Downloaded from the Internet, see disclaimer.
Startco Engineering Ltd.
BPU-2A Bearing Protection Unit
Page 9
Rev. 2
PANEL-MOUNT BPU-2A OUTLINE AND MOUNTING DETAILS
FIGURE 3
Pub. BPU-2A, March, 1994
Downloaded from the Internet, see disclaimer.
Startco Engineering Ltd.
BPU-2A Bearing Protection Unit
Page 10
Rev. 2
SURFACE-MOUNT BPU-2A OUTLINE AND MOUNTING DETAILS
FIGURE 4
Pub. BPU-2A, March, 1994
Downloaded from the Internet, see disclaimer.