SE-3SCR-LM Manual

SE-3SCR-LM MANUAL
MOTOR LOAD MANAGER
OCTOBER 24, 2006
REVISION 3
Copyright © 2006 by Startco Engineering Ltd.
All rights reserved.
Publication: SE-3SCR-LM-M
Document: S95-S3LM-00000
Printed in Canada.
Startco Engineering Ltd.
SE-3SCR-LM Motor Load Manager
Page i
Rev. 1
TABLE OF CONTENTS
PAGE
Table of Contents .................................................................... i
List of Figures.......................................................................... i
1.
General ......................................................................... 1
2.
2.1
2.2
2.3
2.4
Current-Feedback Operation.................................... 1
Minimum Acceleration Time........................................ 1
Current-Limit-Hold Level............................................. 1
Current-Limit-Hold Trip Time ..................................... 1
Initial Voltage................................................................ 3
3.
Tachometer-Feedback Operation............................. 3
4.
4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8
Trip Indications ........................................................... 3
Phase Loss ..................................................................... 3
Phase Reverse................................................................ 3
Current Limit ................................................................. 3
Overcurrent.................................................................... 3
Setup.............................................................................. 3
Anti Jog.......................................................................... 3
Current Feedback .......................................................... 3
Emergency-Trip Circuit ................................................ 5
5.
5.1
5.2
5.3
5.4
5.5
5.6
Other Indication .......................................................... 5
Run ................................................................................ 5
Shed Enabled................................................................. 5
Current-Limit Hold ....................................................... 5
Tach Signal Loss ........................................................... 5
Jog Temperature............................................................ 5
Motor Voltage ............................................................... 5
Pub. SE-3SCR-LC-M, October 24,2006.
6.
6.1
6.2
6.3
6.4
Initial Setup and Commissioning.............................. 5
Motors In Use................................................................ 5
Initial Voltage................................................................ 5
Current-Feedback Start................................................. 5
Tachometer-Feedback Start.......................................... 5
6.4.1 Analog Tachometer......................................... 5
6.4.2 Digital Tachometer.......................................... 6
6.5 Configuration ................................................................ 6
6.6 Shed............................................................................... 6
6.7 Reduced-Voltage Run................................................... 6
7.
Motor-Shed Control ................................................... 6
8.
Reduced-Voltage Run ................................................ 6
9.
Troubleshooting .......................................................... 6
10. Technical Specifications ............................................. 7
LIST OF FIGURES
PAGE
FIGURE
1
2
3
SE-3SCR-LM Rear View............................................. 2
SE-3SCR-LM Outline and Mounting Detail ............... 4
Troubleshooting Guide ................................................. 8
DISCLAIMER
Specifications are subject to change without notice. Startco
Engineering Ltd. is not liable for contingent or consequential
damages, or for expenses sustained as a result of incorrect
application, incorrect adjustment, or a malfunction.
Startco Engineering Ltd.
SE-3SCR-LM Motor Load Manager
Page 1
Rev. 1
1. GENERAL
2. CURRENT-FEEDBACK OPERATION
Each Startco solid-state starter uses one Load Manager to
control the power applied to three-phase, squirrel-cage
induction motors in one-, two-, three-, or four-motor
configurations. The SE-3SCR-LM Motor Load Manager
control module replaces the SE-2SCR-LC, SE-2SCR, and
SE-1SCR control modules. The Load Manager is standard
in new equipment and it can be retrofitted to existing Startco
starters to provide the following additional features:
— On-board, active and passive digital-tachometer
inputs.
— Adjustable current-limit-hold trip time.
— Isolated run-signal and remote-reset inputs.
— Run, trip, and full-conduction relay outputs.
— On-board, emergency-trip circuit with an output
contact for shunt or undervoltage breaker control.
— Individual control of each motor for smooth shed and
share transitions.
— Choice of current-shed or forced-shed operation.
— Reduced-voltage-run adjustment for each motor in a
multiple-motor drive to allow load sharing.
A silicon-controlled rectifier (SCR) is an electrically
operated switch that can be gated into conduction by
applying a trigger pulse to its gate terminal. Once an SCR is
gated on, it will remain on until current drops below a low
value called the holding current. In ac applications, this
happens each cycle on the negative zero crossing;
consequently, SCR's can be used to control ac voltage by
triggering the SCR's into conduction once each cycle. The
portion of the cycle in which current flows is called the
conduction angle.
In Startco Solid-State Starters,
conduction-angle signals from the Load Manager initiate
SCR trigger pulses generated by firing circuits in the power
modules.
A Startco power module has an SCR and a diode in a
parallel, back-to-back configuration. Three power modules
are used to control the voltage applied to a three-phase
motor. The Load Manager uses either current or tachometer
feedback to adjust SCR conduction angles during a start to
bring a load smoothly up to speed. A reduced-voltage
indicator flashes whenever a conduction angle is changing.
Once full speed has been achieved and full voltage is
indicated, the SCR's are gated full-on so that currents are the
same as they would be if the power modules were replaced
by contacts.
Load Manager adjustments are functionally grouped as
shown in Fig. 1.
For current-feedback starts, the top switch in the
TACHOMETER FEEDBACK START group must be in
the NO position. When this switch is in the NO position, all
other controls in the TACHOMETER FEEDBACK START
group are disabled.
Pub. SE-3SCR-LC-M, October 24,2006.
2.1 MINIMUM ACCELERATION TIME
The MINIMUM ACCELERATION TIME control is a
16-position selector switch that sets the time for motor
voltage to increase from initial voltage to full voltage
without a current-limit hold. Each clockwise step above 3
seconds increases the minimum time to reach full voltage by
1.5 seconds. The REDUCED VOLTAGE indicator flash
rate is proportional to the rate at which motor voltage is
changing.
2.2 CURRENT-LIMIT-HOLD LEVEL
The CURRENT LIMIT HOLD LEVEL control is a 16position selector switch that sets the current limit during a
current-feedback start. The selection range is 200% to
500% of motor full-load current (FLA). Each clockwise
step increases the current-limit-hold level by 20% FLA.
During a current-feedback start, voltage will increase at a
rate set by the MINIMUM ACCELERATION TIME
control; however, if the load is sufficient to cause any motor
current to reach the current-limit-hold level, the CURRENT
LIMIT HOLD indicator will come on, the REDUCED
VOLTAGE indicators will stop flashing, and the conduction
angle will not advance until all motor currents fall below the
current-limit-hold level. As the load accelerates, current
decreases and voltage will continue to increase until full
conduction is reached.
2.3 CURRENT-LIMIT-HOLD TRIP TIME
The CURRENT LIMIT HOLD TRIP TIME control is a
16-position selector switch that sets the cumulative trip time
for current-limit hold. The selection range is 2 seconds to 32
seconds in 2-second increments. When configured for
DOUBLE TRIP TIME in the CONFIGURATION group,
the selection range is 4 seconds to 64 seconds in 4-second
increments. In most applications, the CURRENT LIMIT
HOLD indicator should come on momentarily during a
heavily loaded start. If unnecessary current-limit trips occur,
increase MINIMUM ACCELERATION TIME, increase
CURRENT LIMIT HOLD LEVEL, or increase CURRENT
LIMIT HOLD TRIP TIME.
Startco Engineering Ltd.
SE-3SCR-LM Motor Load Manager
FIGURE 1. SE-3SCR-LM Rear View.
Pub. SE-3SCR-LC-M, October 24,2006.
Page 2
Rev. 1
Startco Engineering Ltd.
SE-3SCR-LM Motor Load Manager
2.4 INITIAL VOLTAGE
The INITIAL VOLTAGE control is a 16-position
selector switch that sets the voltage applied to the motors at
the beginning of the start. The selection range is 35% to
50% of full voltage in 1% increments. A setting of 38% to
42% will be sufficient for most applications. The INITIAL
VOLTAGE control should be set so that torque is applied
smoothly and shaft rotation begins without delay. If the
initial-voltage setting is too high, the Load Manager will trip
on overcurrent at the beginning of the start.
3. TACHOMETER-FEEDBACK OPERATION
Load Manager adjustments are functionally grouped as
shown in Fig. 1.
For tachometer-feedback starts, the top switch in the
TACHOMETER FEEDBACK START group must be in
the YES position. When this switch is in the YES position,
all controls in the TACHOMETER FEEDBACK START
group are enabled, and all controls in the CURRENT
FEEDBACK START group must be set to their maximum
settings.
The tachometer-feedback circuit accepts an analog
tachometer, an active digital tachometer, or a passive digital
tachometer. Separate inputs are provided for analog and
digital tachometers. The SE-3SCR-LM must be configured
for the type of tachometer used. See Section 6.4. Set one of
the SYNC SPEED switches to program the tachometer
circuit for 900, 1200, or 1800 rpm.
In tachometer-feedback start, motor voltage is adjusted
automatically to cause the motors to accelerate at a constant
rate.
The TACHOMETER FEEDBACK START
ACCELERATION TIME potentiometer adjusts acceleration
time from 10 seconds to 20 seconds. When DOUBLE
ACCEL TIME is selected, acceleration time is doubled.
REDUCED VOLTAGE indicators flash slowly while the
tachometer-feedback circuit has control of motor voltage.
When 97% of synchronous speed is reached, motor voltage
is increased to full voltage in 1.5 seconds.
In tachometer-feedback start, the function of the INITIAL
VOLTAGE selector is changed—it limits maximum motor
voltage during starting. If the INITIAL VOLTAGE selector
is set too high, an OVERCURRENT trip can occur during a
heavily loaded start. For most applications, an initialvoltage setting of 44% will be adequate; however, the
setting should be increased if load acceleration droops
during a start. If the INITIAL VOLTAGE selector is set
correctly, motors will be permitted to draw up to 450% fullload current during a heavily loaded start.
Pub. SE-3SCR-LC-M, October 24,2006.
Page 3
Rev. 2
4. TRIP INDICATIONS
All Load Manager trips are annunciated by the frontpanel indicators shown in Fig. 2. Trips remain latched until
the trip condition is removed and RESET is pressed or the
supply voltage is cycled.
4.1 PHASE LOSS
A phase-loss trip will occur if any of the zero-crossing
signals are not detected, or if the zero-crossing signals are
not displaced 120° with respect to each other.
4.2 PHASE REVERSE
A phase-reverse trip will occur if all zero-crossing signals
are detected and their phase sequence is not A-B-C.
4.3 CURRENT LIMIT
A current-limit trip will occur if motor current exceeds the
current-limit-hold level for the current-limit-hold trip time.
4.4 OVERCURRENT
An overcurrent trip will occur if current to any motor
exceeds the overcurrent-trip level. The overcurrent-trip
level can be selected at 550% or 600% FLA by a switch in
the CONFIGURATION group.
4.5 SETUP
A setup trip will occur if the SHED switches and
REDUCED VOLTAGE RUN potentiometer settings do not
allow at least one of the motors in use to run at full voltage.
A valid setup requires at least one of the motors in use to
have its SHED switch set to NO and its REDUCED
VOLTAGE RUN potentiometer set to FULL. To assist in
setup, the rear-panel INVALID SETUP indicator mimics the
front-panel SETUP trip indicator.
4.6 ANTI JOG
An anti-jog trip will occur if JOG TEMPERATURE
reaches a count of 14. An anti-jog trip will remain latched
until JOG TEMPERATURE counts down to 4. The top two
switches in the CONFIGURATION group can be used to
enable or disable anti-jog trips and to double the time to trip.
See Section 5.5.
4.7 CURRENT FEEDBACK
A current-feedback trip will occur during starting or
running if less than 12% FLA is detected for any motor in
use.
Startco Engineering Ltd.
SE-3SCR-LM Motor Load Manager
FIGURE 2. SE-3SCR-LM Outline and Mounting Detail.
Pub. SE-3SCR-LC-M, October 24,2006.
Page 4
Rev. 1
Startco Engineering Ltd.
SE-3SCR-LM Motor Load Manager
4.8 EMERGENCY-TRIP CIRCUIT
An emergency-trip-circuit trip will occur if motor current
(above 12% FLA) continues for more than 3.5 seconds after
the run signal is removed. Emergency-trip-circuit protection
is similar to "welded-contact" protection. Circuit operation
is SHUNT or UV selectable with a switch located in the
CONFIGURATION group. Output contacts can be used in
a breaker or interposed contactor control circuit.
5. OTHER INDICATION
5.1 RUN
The green LED labelled RUN indicates a 12- to 24-Vdc
run signal on terminal 201 when the Load Manager is not
tripped.
5.2 SHED ENABLED
The yellow LED labelled SHED ENABLED indicates
that at least one of the motors in use has its SHED switch set
to YES.
5.3 CURRENT-LIMIT HOLD
The red LED labelled CURRENT LIMIT HOLD
indicates that motor current has reached the current-limithold level.
5.4 TACH SIGNAL LOSS
The yellow LED labelled TACH SIGNAL LOSS
indicates that the tachometer-feedback signal lags the
reference speed signal by more than 6% of synchronous
speed. Tach-signal loss does not cause a trip.
5.5 JOG TEMPERATURE
An MPU Motor Protection Unit or an MPS Motor
Protection System is recommended for each motor;
however, the jog-temperature circuit can provide protection
in the event of repeated starts. Four yellow LED's labelled
JOG TEMPERATURE indicate the recent starting history of
the starter. The LED's have a binary weighting of 8, 4, 2,
and 1 from left to right and the number in the jog
temperature display is obtained by adding the binary value
of the LED's that are on. Values assigned to this display are:
0 is cold, 4 is normal run, and 14 is trip. Two, successive,
maximum-acceleration-time starts are allowed if the motors
are stopped on normal run; however, if a third start is
attempted, the anti-jog circuit will trip at 14 and not allow a
reset until the display decrements to 4. This will take
approximately 11 minutes.
Time to trip can be doubled with a switch in the
CONFIGURATION group.
The top switch in the
CONFIGURATION group can be used to disable anti-jog
trips.
Pub. SE-3SCR-LC-M, October 24,2006.
Page 5
Rev. 3
5.6 MOTOR VOLTAGE
The status of the voltage applied to each motor in use is
indicated by three LED’s. The bottom LED indicates if the
motor is SHED, the middle LED indicates if the motor is
operating at REDUCED VOLTAGE and it flashes when
motor voltage is changing, and the top LED indicates FULL
VOLTAGE.
6. INITIAL SETUP AND COMMISSIONING
6.1 MOTORS IN USE
Set the MOTORS IN USE switches to the YES position
for each motor used. If a motor is selected but not used,
feedback current will not be detected and a current-feedback
trip will occur within 3 seconds. If a motor is connected but
not selected, it will not receive power. All unused feedback
inputs (261, 262, 263, 261A, 261B, 261C, and 261D) should
be connected to terminal 260.
NOTE: To prevent a feedback trip during troubleshooting
when no motor is connected, set the MINIMUM
ACCELERATION to 2 seconds.
6.2 INITIAL VOLTAGE
Set the INITIAL VOLTAGE selector to 40% for currentfeedback starts or 44% for tachometer-feedback starts. See
Sections 2.4 and 3.
6.3 CURRENT-FEEDBACK START
If current feedback is used, set the top switch in the
TACHOMETER FEEDBACK START group to NO, set
the MINIMUM ACCELERATION TIME selector to 15
seconds, set the CURRENT LIMIT HOLD LEVEL selector
to 460% FLA, and set the CURRENT LIMIT HOLD TRIP
TIME to 6 seconds.
6.4 TACHOMETER-FEEDBACK START
If tachometer feedback is used, set the top switch in the
TACHOMETER FEEDBACK START group to YES and
set all controls in the CURRENT FEEDBACK START
group to their maximum settings.
6.4.1 ANALOG TACHOMETER
1. Set switch to ANALOG TACH.
2. Connect the positive output of a 100-Vdc/1000-rpm
tachometer to the terminal labelled ANALOG TACH
INPUT and connect the negative output to terminal
260.
3. Set one SYNC SPEED switch for 900, 1200, or 1800
rpm.
4. Set the acceleration-time switch to ACCEL TIME x1.
5. Set the ACCELERATION TIME potentiometer to 15
seconds.
Startco Engineering Ltd.
SE-3SCR-LM Motor Load Manager
6.4.2 DIGITAL TACHOMETER
The Load Manager accepts speed signals from a passive
digital tachometer or a 12-Volt active digital tachometer.
1. Set switch to DIGITAL TACH.
2. Set switch to ACTIVE PICKUP or PASSIVE PICKUP
to correspond with the pickup used.
3. Connect the pickup signal lead to terminal TK7 and the
ground lead to terminal TK8. Ground the shield only at
terminal TK8. If a passive pickup is used, leave
terminal TK9 unconnected. If an active pickup is used,
connect the 12-Vdc lead to TK9.
4. Set one SYNC SPEED switch for 900, 1200, or 1800
rpm.
5. Set the acceleration-time switch to ACCEL TIME x1.
6. Set the ACCELERATION TIME potentiometer to 15
seconds.
6.5 CONFIGURATION
Commission the system with the CONFIGURATION
group set as follows:
— ANTI JOG ON.
— JOG TIME x1.
— EMERGENCY TRIP to match breaker operating
mode.
— 550% OVERCURRENT TRIP.
— CURRENT LIMIT HOLD TRIP TIME x1.
6.6 SHED
Commission the system with the SHED switches set to
the NO and CURRENT positions. After the system is
operational, the benefits of motor shedding for the
application can be determined as outlined in Section 7.
6.7 REDUCED-VOLTAGE RUN
Commission the system with the REDUCED VOLTAGE
RUN potentiometers fully clockwise and the REDUCED
VOLTAGE RUN switch to NO. After the system is
operational, the benefits of motor sharing for the application
can be determined as outlined in Section 8.
Page 6
Rev. 1
The current-shed circuit monitors motor currents from the
phase-A feedback CT’s of each motor. DROPOUT
CURRENT and PICKUP CURRENT selectors adjust the
thresholds at which motors drop-out and pick-up. The
drop-out current range is 50 to 74% of motor FLA and the
pick-up current range is 76 to 100% of motor FLA. If all
phase-A currents remain below the drop-out current, the
current-shed-enabled motors will be sequentially turned off
starting with motor 4. The drop-out rate is one motor per 3
minutes. If any phase-A current is more than the pick-up
current, motors will be sequentially turned on starting with
Motor 1. The pick-up rate is one motor per 10 seconds.
At least one MOTOR IN USE must have its SHED
switch in the NO position and its REDUCED
VOLTAGE RUN potentiometer set to FULL. Setting
the REDUCED VOLTAGE RUN switch to NO is
equivalent to setting all REDUCED VOLTAGE RUN
potentiometers to FULL.
8. REDUCED-VOLTAGE RUN
The Load Manager can reduce the steady-state voltage for
all motors except one in a multiple-motor drive. A
REDUCED VOLTAGE RUN potentiometer for each motor
can reduce applied voltage to 45%. The purpose of voltage
reduction is to balance motor currents in a multiple-motor
drive; however, if motors are lightly loaded, power factor
will be low and load sharing will not be effective. If all
motors in a multiple-motor drive run below 80% FLA at
100% voltage, there is little benefit in using the REDUCED
VOLTAGE RUN controls.
For effective load-share operation, the motor chosen to
remain at full voltage should be the motor with the lowest
running current. Load will shift to this motor as other
motors in the drive have their voltages reduced.
After a successful start, full voltage will be applied to
all selected motors. After 5 seconds, motor voltages will
ramp down (at the MINIMUM ACCELERATION
TIME rate) to the voltages set by their respective
REDUCED VOLTAGE RUN potentiometers.
7. MOTOR-SHED CONTROL
Two shed-control switches are used for each motor. If
the upper switch is in the NO position, shed control is
disabled for that motor. If the upper switch is in the YES
position, the lower switch is active and its position
determines if the motor will be forced off 15 seconds after
full conduction or if the motor will drop-out and pick-up as
the load changes. The DROPOUT CURRENT and
PICKUP CURRENT selector switches apply only to motors
with their shed switches in the YES and CURRENT
positions.
Pub. SE-3SCR-LC-M, October 24,2006.
9. TROUBLESHOOTING
Reference: Fig. 3a, Fig. 3b.
CAUTION: Power modules, heat sinks, and motor cables
can be energized even if a motor is not running. If a motor
is stopped, diodes in the power modules provide half-wave
rectification with respect to ground. If a motor is
disconnected, current through snubber networks in the
power modules is sufficient to be lethal. Use the same
precautions and safety procedures for both line-side and
load-side measurements and service.
Startco Engineering Ltd.
SE-3SCR-LM Motor Load Manager
The following troubleshooting procedure requires a dc
voltmeter. All voltage measurements on the SE-3SCR-LM
are with respect to terminal 260.
1. Turn all motor circuit breakers off.
2. To prevent a CURRENT FEEDBACK and
EMERGENCY TRIP CIRCUIT TRIP during testing,
set the MINIMUM ACCELERATION to 2 seconds. It
is recommended to disconnect the motor and to use a 3wire light bulb load for these tests. However when
motors are connected, the gate leads at terminals G and
C on the firing card should be removed to prevent SCR
gate triggering during the test.
3. Set the top switch in the TACHOMETER FEEDBACK
START group to NO, the REDUCED VOLTAGE
RUN switch to NO, all MOTORS IN USE switches to
YES, all SHED switches to NO, and the MINIMUM
ACCELERATION TIME switch to 2 seconds.
4. Turn on circuit breaker to motor 1 to restore zerocrossing signals to the Load Manager. If the light bulb
load lights are ON or if motor current is detected go to
step 6. Press RESET on the Load Manager. Apply a
run signal to terminal 201. The reduced-voltage
indication should flash until full voltage is reached.
Measure the voltages on terminals 210 to 236. Starting
at terminal 211 and working clockwise toward terminal
230, the voltage pattern 12, 2, 0 Vdc should be
measured. The voltage at odd-numbered terminals is
12 Vdc, and the voltage at even-numbered terminals is
2 Vdc except for terminals ending with a 0. The
voltage at terminals ending with a 0 is 0 Vdc. If this
voltage pattern is not observed, remove the output
connections and repeat the measurements. If the
voltage pattern is correct with outputs disconnected, the
Load Manager is not defective and there is a problem
with the firing boards or the interconnecting cables.
The voltages on even-numbered terminals should be 0
Vdc when the run signal is removed.
5. With the Load Manager in full conduction, input
signals to the firing boards should also be 12, 2, and 0
Vdc. When using a light bulb load, intensity should be
balanced. If intensity is unbalanced, test or replace the
three firing boards. To check a firing board, connect a
1-kΩ resistor between terminals G and C and measure
the voltage across the resistor. The voltage should be 6
Vdc when the Load Manager indicates full voltage and
0 Vdc when the Load Manager is off.
6. To check the SCR and the diode, remove the
connecting bar on the split heat sink. The diode can be
checked by an ohmmeter with a diode-test function and
the SCR can be checked with the test circuit shown in
Fig. 3.
Pub. SE-3SCR-LC-M, October 24,2006.
Page 7
Rev. 2
10. TECHNICAL SPECIFICATIONS
Supply:
24 Vac (±30%), centre-tapped, 60 Hz, 10 VA
Environment:
Operating Temperature .......... -40°C to 60°C
Storage Temperature .............. -55°C to 80°C
Output Relays:
Trip, Run:
Contact Rating .................. 600 mA Resistive,
120 Vac or 120 Vdc.
2 A Resistive @ 30 Vdc.
Contact Configuration ...... Form A
Operating Mode................ Fail-Safe
Emergency Trip Circuit:
Contact Rating .................. 8 A Resistive,
250 Vac or 30 Vdc
Contact Configuration ...... Form A
Operating Mode................ Fail-Safe or
Non-Fail-Safe
Full Conduction:
Contact Rating .................. 8 A Resistive,
250 Vac or 30 Vdc
Contact Configuration ...... Form A
Reset Input Voltage (241)............ 12 to 24 Vdc with
Respect to 241G
Run Input Voltage (201).............. 12 to 24 Vdc with
Respect to 241G
Circuit Accuracies:
Shed Inputs (261A-261D)...... ±4% FLA
Current-Feedback
Inputs (261-263)................... ±4% of Full Scale
Tachometer Requirements:
Digital:
Pulses Per Revolution....... 60
Active Pickup Supply
Voltage ........................... 12 Vdc
Active Input Threshold..... 2.5 Vdc
Passive Input Threshold ... 50 mV
Analog:
Volts Per 1000 rpm........... 100 Vdc
Startco Engineering Ltd.
SE-3SCR-LM Motor Load Manager
FIGURE 3a. Troubleshooting Guide.
Pub. SE-3SCR-LC-M, October 24,2006.
Page 8
Rev. 1
Startco Engineering Ltd.
SE-3SCR-LM Motor Load Manager
FIGURE 3b. Troubleshooting Guide.
Pub. SE-3SCR-LC-M, October 24,2006.
Page 9
Rev. 1