NDR-120 series - f.building

120W Single Output Industrial DIN RAIL
NDR-120
series
Bauar t gepruft
Sicherheit
egel ma ge
od
o s
be wac
g
www.tuv.com
ID 2000000000
■ Features
Universal AC input / Full range
Protections: Short circuit / Overload / Over voltage
/ Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508 (industrial control equipment) approved
EN61000-6-2(EN50082-2) industrial immunity level
100% full load burn-in test
3 years warranty
■ Applications
Industrial control system
Semiconductor fabrication equipment
Factory automation
Electro-mechanical apparatus
■ Description
NDR-120 is one economical slim 120W DIN rail power supply series, adapt to be installed on TS-35/7.5
or TS-35/15 mounting rails. The body is designed 40mm in width, which allows space saving inside the
c a b i n e t s . T h e e n t i r e s e r i e s a d o p t s th e f u l l r a n g e AC i n p u t f r o m 9 0 V A C t o 2 6 4 V A C a n d c o n f o r m s t o
EN61000-3-2, the norm the European Union regulates for harmonic current.
NDR-120 is designed with metal housing that enhances the unit's power dissipation. With working efficiency
up to 89%, the entire series can operate at the ambient temperature between -20℃ and 70℃ under air
convection. It is equipped with constant current mode for over-load protection, fitting various inductive
or capacitive applications. The complete protection functions and relevant certificates for industrial control
apparatus (UL508, TUV EN60950-1, and etc.) make NDR-120 a very competitive power supply solution for
industrial applications.
■ Model Encoding
NDR - 120 - 12
Output voltage
Output wattage
Series name
File Name:NDR-120-SPEC 2014-09-16
NDR-120
120W Single Output Industrial DIN RAIL
series
SPECIFICATION
MODEL
OUTPUT
NDR-120-12
NDR-120-24
NDR-120-48
DC VOLTAGE
12V
24V
48V
RATED CURRENT
10A
5A
2.5A
CURRENT RANGE
0 ~ 10A
0 ~ 5A
0 ~ 2.5A
RATED POWER
120W
120W
120W
RIPPLE & NOISE (max.) Note.2 100mVp-p
120mVp-p
150mVp-p
VOLTAGE ADJ. RANGE
12 ~ 14V
VOLTAGE TOLERANCE Note.3 ±2.0%
24 ~ 28V
±1.0%
48 ~ 55V
±1.0%
LINE REGULATION
±0.5%
±0.5%
±0.5%
LOAD REGULATION
±1.0%
±1.0%
±1.0%
SETUP, RISE TIME
1200ms, 60ms/230VAC
HOLD UP TIME (Typ.)
16ms/230VAC
VOLTAGE RANGE
INPUT
Note.6 90 ~ 264VAC
FREQUENCY RANGE
47 ~ 63Hz
EFFICIENCY (Typ.)
85.5%
2.25A/115VAC
20A/115VAC
LEAKAGE CURRENT
<1mA / 240VAC
105 ~ 130% rated output power
(Note 4)
OTHERS
89%
Protection type : Constant current limiting, recovers automatically after fault condition is removed
OVER VOLTAGE
OVER TEMPERATURE
Shut down o/p voltage, re-power on to recover
WORKING TEMP.
-20 ~ +70℃ (Refer to "Derating Curve")
56 ~ 65V
20 ~ 95% RH non-condensing
-40 ~ +85℃, 10 ~ 95% RH
±0.03%/℃ (0 ~ 50℃)
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL508, TUV EN60950-1 approved
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE
EMC EMISSION
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH
Compliance to EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3
EMC IMMUNITY
MTBF
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A
456.3K hrs min. MIL-HDBK-217F (25℃)
40*125.2*113.5mm (W*H*D)
0.6Kg; 20pcs/13Kg/1.16CUFT
DIMENSION
PACKING
NOTE
88%
1.3A/230VAC
35A/230VAC
14 ~ 17V
29 ~ 33V
Protection type : Shut down o/p voltage, re-power on to recover
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND
VOLTAGE
SAFETY &
EMC
127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)]
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
OVERLOAD
PROTECTION
2500ms, 60ms/115VAC at full load
10ms/115VAC at full load
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power.
In case the adjacent device is a heat source, 15mm clearance is recommended.
6. Derating may be needed under low input voltage. Please check the derating curve for more details.
File Name:NDR-120-SPEC 2014-09-16
NDR-120
120W Single Output Industrial DIN RAIL
series
Block Diagram
fosc : 70KHz
EMI FILTER
&
RECTIFIERS
I/P
RECTIFIERS
&
FILTER
POWER
SWITCHING
+V
-V
O.C.P.
O.L.P.
FG
DETECTION
CIRCUIT
PWM
CONTROL
O.T.P.
O.V.P.
Derating Curve
Static Characteristics
230VAC
100
12V,24V,48V
100
90
80
80
115VAC
50
LOAD (%)
LOAD (%)
70
12V
(115VAC only)
60
40
20
-20 -10 0
10
20
30
40 45 50
AMBIENT TEMPERATURE (℃)
60
70 (VERTICAL)
60
50
40
90
100
125
135
145
155 165
175
180
200
230
264
INPUT VOLTAGE (V) 60Hz
File Name:NDR-120-SPEC 2014-09-16
NDR-120
120W Single Output Industrial DIN RAIL
series
Mechanical Specification
Case No.992D
Unit:mm
Top View
113.5
40
12 3 4
39
TB2
+
125.2
+V ADJ.
DC OK
TB1
1 2 3
Side View
Front View
Side View
Terminal Pin No. Assignment (TB1)
Pin No.
1
2
3
Assignment
FG
AC/N or DC AC/L or DC +
Terminal Pin No. Assignment (TB2)
Pin No.
1,2
3,4
Assignment
DC OUTPUT -V
DC OUTPUT+V
Bottom View
Installation Instruction
35
This series fits DIN-RAIL TS35/7.5 or TS35/15.
For installation details, please refer to the USER MANUAL on
http://www.meanwell.com/search/NDR-120/NDR_manual.pdf
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
(For reference only. Not included with unit.)
Back View
File Name:NDR-120-SPEC 2014-09-16