120W Single Output Industrial DIN RAIL Power Supply WDR-120 series Features : Single and two phase wide input range 180 ~ 550VAC Protections: Short circuit / Overload / Over voltage / Over temperature Cooling by free air convection Built-in constant current limiting circuit Can be installed on DIN rail TS-35/7.5 or 15 UL508(industrial control equipment)approved EN61000-6-2(EN50082-2) industrial immunity level 100% full load burn-in test Built-in DC OK relay contact 3 years warranty SPECIFICATION MODEL OUTPUT WDR-120-12 WDR-120-24 WDR-120-48 DC VOLTAGE 12V 24V 48V RATED CURRENT 10A 5A 2.5A CURRENT RANGE 0 ~ 10A 0 ~ 5A 0 ~2.5A RATED POWER 120W 120W 120W RIPPLE & NOISE (max.) Note.2 120mVp-p 120mVp-p 150mVp-p VOLTAGE ADJ. RANGE 24 ~ 29V 1.0% 48 ~ 58V 1.0% 12 ~ 15V VOLTAGE TOLERANCE Note.3 1.5% LINE REGULATION 0.5% 0.5% 0.5% LOAD REGULATION 0.5% 0.5% 0.5% SETUP, RISE, HOLD UP TIME 2000ms, 70ms, 50ms/400VAC INPUT VOLTAGE RANGE 180 ~ 550VAC FREQUENCY RANGE 47 ~ 63Hz EFFICIENCY (Typ.) 89.5% / 400V AC CURRENT INRUSH CURRENT (max.) 0.55A/400VAC 1.2A/230VAC COLD START 50A LEAKAGE CURRENT OVERLOAD PROTECTION OVER VOLTAGE FUNCTION DC OK SIGNAL WORKING TEMP. WORKING HUMIDITY ENVIRONMENT STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION SAFETY STANDARDS SAFETY & WITHSTAND VOLTAGE ISOLATION RESISTANCE EMC (Note 4) 92% / 400V <3.5mA / 530VAC 5 (12V),110 5 (24V) (TSW1) detect on heatsink of power transistor ; 100 5 (48V) (TSW1) detect on heatsink of power diode Protection type : Shut down o/p voltage, recovers automatically after temperature goes down Relay contact rating(max.) : 30V / 1A resistive -25 ~ +70 (Refer to output load derating curve) 20 ~ 90% RH non-condensing -40 ~ +85 , 10 ~ 95% RH 0.03%/ (0 ~ 50 Component: 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting clip: Compliance to IEC60068-2-6 UL508 approved, IEC60950-1 CB approved by SIQ, design refer to GL I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN61204-3, EN61000-6-2 (EN50082-2), heavy industry level, criteria A MTBF 268Khrs min. DIMENSION 40*125.2*113.5mm (W*H*D) 0.65Kg; 20pcs/14Kg/1.16CUFT PACKING NOTE 91% / 400V I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH EMI CONDUCTION & RADIATION Compliance to EN55011 (CISPR11), EN55022 (CISPR22), EN61204-3 Class B EMS IMMUNITY OTHERS 254 ~ 780VDC 105 ~ 130% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed 16 ~ 18V 31 ~ 37V 60 ~ 67V Protection type : Shut down o/p voltage, re-power on to recover 105 OVER TEMPERATURE 2000ms, 70ms, 10ms/230VAC at full load MIL-HDBK-217F (25 ) 1. All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25 of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. 5. Length of set up time is measured at cold first start. Turning ON/OFF the power supply very quick may lead to increase of the set up time. File Name:WDR-120-SPEC 2010-12-07 120W Single Output Industrial DIN RAIL Power Supply WDR-120 Mechanical Specification Unit:mm 113.5 Case No.992B series 125.2 40 DC OK + TB1 DC OK +V ADJ. 1 2 3 1 2 3 4 TB2 Terminal Pin No. Assignment (TB1) 35 Pin No. 1 2 3 Assignment FG AC/L2 AC/L1 Terminal Pin No. Assignment (TB2) Pin No. 1,2 3 4 ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15 Assignment Relay Contact DC OUTPUT -V DC OUTPUT+V Block Diagram DC OK I/P EMI FILTER RECTIFIERS & FILTER POWER SWITCHING RECTIFIERS & FILTER +V -V DETECTION CIRCUIT FG CURRENT LIMIT O.L.P. PWM CONTROL O.T.P. O.V.P. DC OK Relay Contact Contact Close PSU turns on / DC OK. Contact Open PSU turns off / DC Fail. Contact Ratings (max.) 30V/1A resistive load. File Name:WDR-120-SPEC 2010-12-07 120W Single Output Industrial DIN RAIL Power Supply Derating Curve WDR-120 series Static Characteristics 100 Others 100 90 80 80 12V 70 LOAD (%) LOAD (%) 60 40 20 -25 60 50 40 0 10 20 30 40 50 AMBIENT TEMPERATURE ( ) 60 70 (VERTICAL) 180 190 200 250 290 310 360 400 450 490 500 520 550 INPUT VOLTAGE (VAC) 60Hz File Name:WDR-120-SPEC 2010-12-07