MEANWELL WDR

WDR-480 series
480W Single Output Industrial DIN RAIL Power Supply
Features :
Single and two phase wide input range 180~550VAC
Built-in active PFC circuit compliance to EN61000-3-2
High efficiency 93% and low power dissipation
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
EN61000-6-2(EN50082-2) industrial immunity level
Built-in DC OK relay contact
100% full load burn-in test
3 years warranty
SPECIFICATION
MODEL
OUTPUT
WDR-480-24
WDR-480-48
DC VOLTAGE
24V
48V
RATED CURRENT
20A
10A
CURRENT RANGE
0 ~ 20A
0 ~ 10A
RATED POWER
480W
480W
RIPPLE & NOISE (max.) Note.2 100mVp-p
150mVp-p
VOLTAGE ADJ. RANGE
48 ~ 55V
1.0%
24 ~ 28V
VOLTAGE TOLERANCE Note.3 1.0%
LINE REGULATION
0.5%
LOAD REGULATION
1.0%
18ms / 400VAC
HOLD UP TIME (Typ.)
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
2000ms, 150ms/230VAC at full load
16ms / 230VAC at full load
Note.6 180 ~ 550VAC
FREQUENCY RANGE
INPUT
1.0%
800ms, 150ms/400VAC
SETUP, RISE TIME
VOLTAGE RANGE
0.5%
254 ~ 780VDC
47 ~ 63Hz
PF 0.84/400VAC
PF 0.84/230VAC
92%
93%
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
1.6A/400VAC
4A/230VAC
COLD STAR 50A
LEAKAGE CURRENT
<3.5mA / 530VAC
105 ~ 130% rated output power
Protection type : Constant current limiting, unit will shut down after 3 sec. ,auto-recovery after 1 minute if the fault condition is removed
OVERLOAD
PROTECTION OVER VOLTAGE
OVER TEMPERATURE
56 ~ 65V
29 ~ 33V
Protection type : Shut down o/p voltage, auto-recovery after 1 minute if the fault condition is removed
95
5
(TSW) detect on heatsink of power switch
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
FUNCTION DC OK REALY CONTACT RATINGS (max.) 60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load
WORKING TEMP.
Note.5 -30 ~ +70 (Refer to "Derating Curve")
20 ~ 95% RH non-condensing
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
SAFETY & WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC
(Note 4)
EMC EMISSION
EMC IMMUNITY
MTBF
OTHERS
DIMENSION
PACKING
NOTE
-40 ~ +85
, 10 ~ 95% RH
0.03%/ (0 ~ 50
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL508 approved, IEC60950-1 CB approved by SIQ, design refer to GL
I/P-O/P:3KVAC
I/P-FG:1.5KVAC
O/P-FG:0.5KVAC
O/P-DC OK:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A approved
112.8Khrs min. MIL-HDBK-217F (25
85.5*125.2*128.5mm (W*H*D)
1.7Kg; 8pcs/14.6Kg/0.9CUFT
)
1. All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power.
In case the adjacent device is a heat source, 15mm clearance is recommended.
6. Derating may be needed under low input voltage. Please check the derating curve for more details.
File Name:WDR-480-SPEC 2011-11-28
WDR-480 series
480W Single Output Industrial DIN RAIL Power Supply
Mechanical Specification
Unit:mm
128.5
Case No.984B
125.2
TB2
+
1
2
DC OK
85.5
DC OK
+V ADJ
TB1
1
2
3
4
5
6
3
Terminal Pin No. Assignment (TB1)
35
Pin No.
1
2
3
Assignment
FG
AC/L2
AC/L1
Terminal Pin No. Assignment (TB2)
Pin No.
1,2
3,4
5,6
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
Assignment
DC OUTPUT +V
DC OUTPUT -V
Relay Contact
Block Diagram
DC OK
I/P
EMI FILTER
&
RECTIFIERS
POWER
SWITCHING
PFC
CIRCUIT
RECTIFIERS
&
FILTER
+V
-V
O.C.P.
U.V.P.
FG
PFC
CONTROL
O.L.P.
PWM & PFC
CONTROL
DETECTION
CIRCUIT
O.V.P.
DC OK Relay Contact
Contact Close
PSU turns on / DC OK.
Contact Open
PSU turns off / DC Fail.
Contact Ratings (max.) 30V/1A resistive load.
File Name:WDR-480-SPEC 2011-11-28
WDR-480 series
480W Single Output Industrial DIN RAIL Power Supply
Derating Curve
Output derating VS input voltage
100
100
90
80
80
70
LOAD (%)
LOAD (%)
60
40
20
-30
60
50
40
0
10
20
30
40
50
AMBIENT TEMPERATURE ( )
60
70 (VERTICAL)
180
190
200
250
290
310 360
400 450
490
500 520 550
INPUT VOLTAGE (VAC) 60Hz
File Name:WDR-480-SPEC 2011-11-28