MEANWELL DR-45

45W Single Output Industrial DIN Rail Power Supply
DR-45
series
Features :
Universal AC input/Full range
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
LED indicator for power on
100% full load burn-in test
Fix switching frequency at 100KHz
3 years warranty
SPECIFICATION
MODEL
DR-4505
DR-4512
DR-4515
DR-4524
DC VOLTAGE
5V
12V
15V
24V
RATED CURRENT
5A
3.5A
2.8A
2A
CURRENT RANGE
0 ~ 5A
0 ~3. 5A
0 ~ 2.8A
0 ~ 2A
RATED POWER
25W
42W
42W
48W
200mVp-p
240mVp-p
480mVp-p
10.8 ~ 13.2V
13.5 ~ 16.5V
21.6 ~ 26.4V
RIPPLE & NOISE (max.) Note.2 100mVp-p
OUTPUT
INPUT
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE Note.3
2.0%
1.0%
1.0%
1.0%
LINE REGULATION
1.0%
1.0%
1.0%
1.0%
LOAD REGULATION
1.0%
1.0%
1.0%
1.0%
SETUP, RISE TIME
800ms, 60ms/230VAC at full load
HOLD UP TIME (Typ.)
100ms/230VAC at full load
VOLTAGE RANGE
85 ~ 264VAC
FREQUENCY RANGE
47 ~ 63Hz
72%
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
1.5A/115VAC
0.75A/230VAC
COLD START 28A/115VAC
56A/230VAC
OVERLOAD
Protection type : Shut off o/p voltage, clamping by zener diode
Tj 135
typically (U1) detect on heat sink of power transistor
Protection type : Shut down o/p voltage, re-power on to recover
-10 ~ +50 (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-20 ~ +85
, 10 ~ 95% RH
0.03%/ (0 ~ 50
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL508, TUV EN60950-1 approved
I/P-O/P:3KVAC
I/P-FG:1.5KVAC
O/P-FG:0.5KVAC
ISOLATION RESISTANCE
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC
EMI CONDUCTION & RADIATION Compliance to EN55011,EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
HARMONIC CURRENT
EMS IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
MTBF
364.6K hrs min. MIL-HDBK-217F (25
93*78*67mm (L*W*H)
0.31Kg; 48pcs/16.1Kg/1.3CUFT
DIMENSION
PACKING
NOTE
80%
<1mA / 240VAC
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
OTHERS
77%
105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
5.75 ~ 6.75V
13.8 ~ 16.2V
17.25 ~ 20.25V
27.6 ~ 32.4V
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
(Note 4)
77%
LEAKAGE CURRENT
OVER TEMPERATURE
EMC
120 ~ 370VDC
EFFICIENCY (Typ.)
PROTECTION OVER VOLTAGE
SAFETY &
4.75 ~ 5.5V
)
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
File Name:DR-45-SPEC 2008-04-07
DR-45
45W Single Output Industrial DIN Rail Power Supply
Mechanical Specification
Unit:mm
29
67
Case No. 918A
series
7.5 8.5
46.5
46.5
9
8
7
6
35
78
5
4
3
2
Install DIN rail TS35/7.5 or TS35/15
1
Terminal Pin No. Assignment
Pin No.
1
2
3
4,5
Assignment
AC/L
AC/N
FG
DC OUTPUT -V
77
Pin No.
6,7
8
9
93
Assignment
DC OUTPUT+V
LED
+V ADJ.
Block Diagram
fosc : 100KHz
RECTIFIERS
&
FILTER
EMI
FILTER
I/P
POWER
SWITCHING
RECTIFIERS
&
FILTER
PWM
CONTROL
DETECTION
CIRCUIT
FG
Derating Curve
+V
-V
Static Characteristics (24V)
OUTPUT VOLTAGE (V)
100
80
LOAD (%)
60
40
20
-10
0
10
20
30
40
50
AMBIENT TEMPERATURE ( )
60 (VERTICAL)
350
28
300
24
250
20
200
16
150
12
100
8
50
70
80
100
120
140
160
180
200
220
240
OUTPUT RIPPLE (mVp-p)
Ta=25
32
260
INPUT VOLTAGE (V) 60Hz
File Name:DR-45-SPEC 2008-04-07