RTNA4 - RTAA4 RTNA4

RTNA4 - RTAA4
Industrial temperature switch with capillary
Main Features
„„
Excellent repeatability
„„
Dead band adjustment for regulation
„„
Fix dead band for control and alarm
„„
Capillary 1 to 20 meters
Applications
„„Power generation safety equipment
Technical Data
Temperature range
-46 ... 0°C to 200 ... 270°C
Case
Black Zamak
Temperature
Process : Ambient : Storage : Mounting
Wall mounting braket
Ground connection
Via internal terminal block
Electrical
connection
Terminal block with plastic cable gland for
Ø 7 to 10.5 mm
Electrical function
See ordering code details on page 5
Adjustment
2 external adjustment screws on top of the case
for set point and dead band
-46 ... +270°C
-30 ... +55°C
-40 ... +55°C
Repeatability
± 1% F.S. @ constant temperature cycle
CE conformity
Low Voltage Directive LVD 2006/95/EC
Protection rating
IP 66 (EN 60529)
Process connection
RTA : Copper alloy
RTN : Stainless steel 1.4404 (316L)
RTA : Copper alloy
RTN : Stainless steel 1.4404 (316L)
RTA : Copper alloy
RTN : Stainless steel 1.4404 (316L)
For types of protection see ordering details on
page 5
Bulb
Capillary
Scale
Internal. Accuracy on reading ± 5% FS
Cover
Zamak blue painted
Captive stainless steel screws
Code SETP
Mounting on 2" pipe
Code 0407
Stainless steel tag plate and wire
Code 9941
Lead seal of the adjustment screws
Code 8990
Nuclear cleanliness (RTN only)
Code 0838
Electrical connection : stainless steel connector (Souriau)
Code 2298
Mobile plug for stainless steel connector (Souriau)
Code 2249
2015-04-21
Customer specific set point adjustment
Design and specifications subject to change without notice
Options
www.baumer.com
Data sheet B31.13
Page 1 / 6
RTNA4 - RTAA4
Industrial temperature switch with capillary
Principle
A vapour filled flexible sensing element actuates a microswitch by
means of a lever. The set point is adjusted by means of a compressible spring installed in opposition.
NC
NC
NC
C
C
C
NO
NO
NO
Set point and reset point must be between 10% and 90% of the
selected scale.
Standard factory adjustment
Setpoint at 50% of the scale on falling temperature
NC
C
NC
NC
C
C
NO
Customer specific factory adjustment (option SETP)
The following specifications have to be given with the order:
• Setpoint value
• Adjustment on falling or raising temperature
• Dead band value when using an adjustable dead band switch
NO
NO
Electrical connections
2 SPDT
NC
Blue
COM
Red
NO
White
NC
Blue
COM
Red
NO
Yellow / green
NC
COM
NO
White
Blue
Red
White
Design and specifications subject to change without notice
1 SPDT
2015-04-21
Yellow / green
www.baumer.com
Data sheet B31.13
Page 2 / 6
RTNA4 - RTAA4
Industrial temperature switch with capillary
Micro switches characteristics
Switch code
N (T)
A (B)
M (K)
C (W)
E (F)
H
D (V)
J
Type
Tropicalized
Standard
Gold contact
Hermetic
Ultra sensitive
Manual reset
Ultra sensitive
Hermetic
Manual reset
6 Vdc
0.1 ... 8 A
0.4 ... 10 A
10 ... 50 mA
5 mA ... 4 A
0.4 ... 1 A
N/A
0.4 ... 4 A
N/A
12 Vdc
0.1 ... 8 A
0.4 ... 10 A
10 ... 50 mA
5 mA ... 4 A
0.4 ... 1 A
N/A
0.4 ... 4 A
N/A
24 Vdc
0.1 ... 8 A
0.4 ... 6 A
10 ... 50 mA
5 mA ... 4 A
0.4 ... 1 A
0.1 ... 8 A
0.4 ... 4 A
0.1 ... 8 A
30 Vdc
0.1 ... 8 A
0.4 ... 6 A
10 ... 50 mA
5 mA ... 3 A
0.4 ... 1 A
0.1 ... 8 A
0.4 ... 2 A
0.1 ... 8 A
48 Vdc
0.1 ... 8 A
0.4 ... 6 A
10 ... 50 mA
5 mA ... 3 A
N/A
0.1 ... 8 A
N/A
0.1 ... 8 A
110 Vdc
N/A
0.1 ... 0.5 A
10 ... 50 mA
5 mA ... 1 A
N/A
N/A
N/A
N/A
220 Vdc
N/A
0.1 ... 0.25 A
10 ... 50 mA
5 mA ... 0.5 A
N/A
N/A
N/A
N/A
115 Vac
0.1 ... 10 A
0.4 ... 10 A
10 ... 50 mA
50 mA ... 3 A
0.4 ... 10 A
0.1 ... 10 A
N/A
0.1 ... 10 A
250 Vac
0.1 ... 5 A
0.2 ... 10 A
10 ... 10 mA
50 mA ... 2.5 A
0.2 ... 10 A
0.1 ... 5 A
N/A
0.1 ... 5 A
2000 V
2000 V
2000 V
1500 V
2000 V
2000 V
1000 V
2000 V
Dielectric rigidity
between contacts
and ground
Adjustable ranges
Micro-switch dead band 1)
TMax
Scale
accidential
Adjustable dead band
Code
N (T*)
10%
°C
A (B*)
M (K*)
90%
Fixed dead band
C (W*)
10%
E (F*)
90%
10%
H
90%
D (V*)
J
10%
90%
2.5
°C
0
40
400
4-9
2-9
8 - 12
4 - 12
1.5
0.8
5
-20 ... 20
60
401
3-8
1.5 - 6
6 - 10
4 - 10
1
0.5
4
2
0
60
402
4-9
2-9
7 - 12
4 - 12
1.5
0.7
5
2.5
-46 ... ... 45
40 ... 120
145
403
5 - 16
3 - 16
10 - 20
6 - 20
2
1.2
6
4
100 ... 160
180
414
5 - 12
3 - 12
9 - 15
5 - 15
2
1
6
3
20 ... 80
100
415
5 - 12
3 - 12
9 - 15
5 - 15
2
1
6
3
160 ... 250
290
406
6 - 18
4 - 18
11 - 22
7 - 22
2.5
1.2
8
4.5
70 ... 150
175
408
5 - 16
4 - 16
10 - 20
6 - 20
2
1
6
4
130 ... 190
210
412
5 - 12
3 - 12
9 - 15
5 - 15
2
1
6
3
200 ... 270
290
413
5 - 12
3 - 12
9 - 15
5 - 15
2
1
6
3
(*) For version with 2 microswitches lower values of the dead band must be multiplied x 1.5
The value of the dead band is depending on the value of the set point.
This table contains the dead band values for set point adjustment at 10% and 90% of the selected scale. For adjustable dead band the lower value corresponds to
the dead band spring totally released and the higher corresponds to the dead band spring fully tensed. For other set points the dead band value can be calculated
by linear interpolation between the values at 10% and 90%.
2015-04-21
Design and specifications subject to change without notice
1)
www.baumer.com
Data sheet B31.13
Page 3 / 6
RTNA4 - RTAA4
Industrial temperature switch with capillary
Dimensions (mm)
76.5
130
=
125
=
Minimum additional stem length (Amin/mm)
58
Connection
144
139
5
TD2
TD3
Without
0
0
0
G1/2
0
18
18
1/2 NPT
0
21
21
64
100
28.5
TD1
45°
K ±2%
K ±2%
S
Ø8
Ø 2,6
Ø8
P±3
S
S
Ø 9,5
= Bulb length (temperature sensitive part, see tables below)
A =
A
P
Additional stem length
Minimum additional length Amin depends on type of capillary and process connection (see table above)
For version TD1 there is no additional stem length (A=0).
The sliding connection is mounted on the capillary.
= Immersion length (P = S + A)
Pmin = Minimum immersion length (Pmin = S + Amin)
TD1
TD2
TD3
K = Capillary length
Bulb Ø 14 mm
K = 0 ... 2 m
Code
400
401
402
403
408
412
413
414
415
S / mm
80
80
80
80
80
80
80
80
80
K = 3 ... 7 m
S / mm
100
100
100
100
100
100
100
100
100
K = 8 ... 16 m
S / mm
150
150
150
150
150
150
150
150
K = 17 ... 20 m
S / mm
180
180
180
180
180
180
150
_
180
180
Code
400
401
402
403
408
412
413
414
415
K = 0 ... 2 m
Bulb Ø 9.5 mm
S / mm
155
155
155
155
155
155
155
155
155
K = 3 ... 7 m
S / mm
200
200
200
200
200
200
200
200
200
300
_
300
300
370
370
K = 8 ... 16 m
S / mm
300
300
300
300
300
300
K = 17 ... 20 m
S / mm
370
370
370
370
370
370
Stainless steel sliding male connection (TD1)
Thread and sizes
A
Clamping nut
B
Tightness
fittings
L
Process
connection
H
Thread and sizes
A
F
G 1/2
1/2 NPT
H
18
21
L
43
46
A
27/flat
27/flat
B
27/flat
27/flat
Waterproof after tightening mounted
on the capillary.
Clamping nut
Process
connection
Clamping
ring
F
B
L
H
F
G 1/2
1/2 NPT
H
18
21
L
36
40
A
17/flat
17/flat
B
23/flat
23/flat
After tightening of the clamping
nut, the stem is fixed in the process
connection. Tight up to 40 bar.
2015-04-21
F
Stainless steel sliding male connection (TD2/3)
Design and specifications subject to change without notice
Bulb length (S) according to the capillary length (K) and the temperature range (code)
www.baumer.com
Data sheet B31.13
Page 4 / 6
RTNA4 - RTAA4
Industrial temperature switch with capillary
Ordering details RTNA4 - RTAA4
Temperature range (°C)
-46... 0
-20 ... 20
0 ... 45
40 ... 120
100 ... 160
20 ... 80
160 ... 250
70 ... 150
130 ... 190
200 ... 270
RT
A
–
.
4xx
.
–
A
N
Deadband
Adjustable
Adjustable
Adjustable
Adjustable
Fix
Fix
Fix
Fix
Adjustable
Adjustable
Adjustable
Adjustable
Fix
Fix
A
A
B
C
W
E
F
D
V
M
K
N
T
H
J
.
400
401
402
403
414
415
406
408
412
413
.
Type of capillary
TD1
Stainless steel capillary without protection
1
TD2
Stainless steel capillary with stainless steel protection
2
TD3
Stainless steel capillary with stainless steel protection and PVC coating
3
Capillary length (K)
1 meter
1
2 meters
2
3 meters
3
4 meters
4
5 meters
5
6 meters
6
7 meters
7
8 meters
8
9 meters
9
10 meters
A
11 meters
B
12 meters
C
13 meters
D
14 meters
E
15 meters
F
16 meters
G
17 meters
H
18 meters
J
19 meters
K
20 meters
L
Immersion length (P) = Bulb length (S) + additional stem length (A)
Immersion length (P)
(Amin depends on type of capillary and process connection, for S and Amin see tables on page 4)
P = S + Amin
P = 150 mm
(not for TD1)
P = 160 mm
(not for TD1)
P = 250 mm
(not for TD1)
P = 400 mm
(not for TD1)
P = 600 mm
(not for TD1)
P = 1000 mm
(not for TD1)
Bulb diameter
Ø 14 mm (standard)
Ø 9.5 mm
Process connection
Without
G1/2
1/2 NPT
Options to be added behind the / (see example below)
www.baumer.com
/
Data sheet B31.13
Design and specifications subject to change without notice
Type of the bulb
Copper alloy bulb and capillary
Stainless steel bulb and capillary
Approval
Standard version without ATEX approval
Type of micro switches
1 SPDT standard changeover switch
2 SPDT standard changeover switch
1 SPDT hermetically changeover switch
2 SPDT hermetically changeover switch
1 SPDT ultra sensitive changeover switch
2 SPDT ultra sensitive changeover switch
1 SPDT hermetically, ultra sensitive changeover switch
2 SPDT hermetically, ultra sensitive changeover switch
1 SPDT gold contact changeover switch
2 SPDT gold contact changeover switch
1 SPDT tropicalized changeover switch
2 SPDT tropicalized changeover switch
1 SPDT changeover switch, manual reset, opening on raising pressure
1 SPDT changeover switch, manual reset, opening on falling pressure
RT
0
3
2
4
5
6
D
E
C
0
3
6
/
Page 5 / 6
2015-04-21
Model
Industrial temperature switch
RTNA4 - RTAA4
Industrial temperature switch with capillary
Ordering example with options
RT
–
A
A
A
.
400
.
1
1
2
E
3
/
0407
_
9941
Industrial temperature switch
Copper alloy bulb and capillary
Without ATEX approval
1 SPDT standard changeover switch
Temperature range -46 ... 0 °C
TD1 stainless steel capillary without protection
1 meter capillary
Immersion length P = 160 mm
Bulb diameter Ø 14mm
Process connection G1/2
Option : Mounting on 2" pipe
2015-04-21
Design and specifications subject to change without notice
Option : Stainless steel tag plate and wire
www.baumer.com
Data sheet B31.13
Page 6 / 6