Technical Data RDY6

RDY6
Differential pressure switch with intrinsic safety
for variable static pressure
Main Features
„„
Excellent repeatability
„„
Dead band adjustment for regulation
„„
Fix dead band for control and alarm
„„
Intrinsic safety Hazardous area 0, 1, 2
„„
Static pressure max. 20 bar
„„
No influence of the static pressure on the setpoint
Applications
„„Power generation safety equipment
„„Pressurized chambers control
„„Liquid level control
Technical Data
Pressure range
10 ... 200 mbar to 10 ... 2000 mbar
Electrical function
See ordering code details on page 5
Temperature
Process : -15 ... +150°C
Ambient : -25 ... +55°C
Storage : -40 ... +70°C
Adjustment
Repeatability
± 1% F.S. @ constant pressure cycle
2 external adjustment screws on top of the case
for set point and dead band.
The adjustment is not influenced by changes of
the static pressure.
CE conformity
Low Voltage Directive LVD 2006/95/EC
Pressure Equipment Directive PED 97/23/EC
ATEX Directive 94/9/EC
ATEX
Protection rating
IP 66 (EN 60529)
Type examination certificate
LCIE 03 ATEX 6123X
EN 60079-0: 2012 (internal conformity analysis)
EN 60079-11: 2012
Marking
0081
IM1
Ex ia I Ma
II 1 G
Ex ia IIC T6 or T5 Ga
Electrical data
Umax = 28 Vdc
Imax = 120 mA
Pmax = 0.84 W
Sensing element
Flanges :Stainless steel 1.4404 (316L)
Diaphragm : Viton®
Scale
Internal. Accuracy on reading ± 5% FS
Cover
Case
Zamak blue painted
Captive stainless steel screws
Black Zamak
Mounting
Wall mounting braket
Ground connection
Via internal terminal block
Electrical
connection
Terminal block with plastic cable gland for
Ø 7 to 10.5 mm
Ci = Negligible ; Li = Negligible
Design and specifications subject to change without notice
Process connection Stainless steel 1.4404 (316L)
Options
Code SETP
Oxygen application
Code 0765
Mounting on 2" pipe
Code 0407
Electrical connection : stainless steel connector (Souriau)
Code 2298
Mobile plug for stainless steel connector (Souriau)
Code 2249
Stainless steel tag plate and wire
Code 9941
Lead seal of the adjustment screws
Code 8990
2015-04-14
Customer specific set point adjustment
www.baumer.com
Data sheet A32.42
Page 1 / 5
RDY6
Differential pressure switch with intrinsic safety
for variable static pressure
Principle
∆P
A flexible sensing element actuates a microswitch by means of a
piston. The set point is adjusted by means of a compressible spring
installed in opposition.
NC
NC
NC
C
C
C
NO
NO
HP < LP
NO
HP > LP
Set point and reset point must be between 10% and 90% of the selected scale.
Standard factory adjustment
Setpoint at 50% of the scale on falling pressure
NC
C
NC
NC
C
C
NO
Customer speciffic factory adjustment (option SETP)
The following specifications have to be given with the order:
• Setpoint value
• Adjustment on falling or raising pressure.
• Dead band value when using an adjustable dead band switch
NO
NO
Electrical connections
2 SPDT
1 SPDT
NC
Blue
COM
Red
NO
White
NC
Blue
COM
Red
NO
White
NC
Blue
COM
Red
Yellow / green
NO
White
Yellow / green
Certified safety
barrier
NO
C
Non hazardous
area
NO
or NC
NC
+
Rc 1
Supply
–
Screen
For max. ambient temperature refer to technical data on page 1.
The installation must be made in an intrinsically safe circuit whose certified electrical safety parameters do not exceed any of the values Umax,
Imax and Pmax given in the electrical data on page 1.
2015-04-14
All necessary measures must be taken by the user, to avoid the calorific transfer from the fluid to the apparatus head increasing the head's
temperature to such that it reaches the self-ignition temperature of the gas in which it is used.
Design and specifications subject to change without notice
Hazardous area
Zone 0, 1, 2
www.baumer.com
Data sheet A32.42
Page 2 / 5
RDY6
Differential pressure switch with intrinsic safety
for variable static pressure
Micro switches characteristics
Switch code
N (T)
M (K)
C (W)
S
Type
Tropicalized
Gold contact
Hermetic
Ultrasensitive
Gold contact
6 Vdc
0.1 ... 0.12 A
10 ... 50 mA
5 ... 120 mA
10 ... 50 mA
12 Vdc
N/A
10 ... 50 mA
5 ... 66 mA
10 ... 50 mA
24 Vdc
N/A
10 ... 33 mA
5 ... 33 mA
10 ... 33 mA
30 Vdc
N/A
N/A
N/A
N/A
48 Vdc
N/A
N/A
N/A
N/A
110 Vdc
N/A
N/A
N/A
N/A
220 Vdc
N/A
N/A
N/A
N/A
115 Vac
N/A
N/A
N/A
N/A
250 Vac
Dielectric rigidity between contacts and ground
N/A
N/A
N/A
N/A
2000 V
2000 V
1500 V
2000 V
Adjustable ranges
Scale
mbar
10 ... 200
Max
ΔP
Max P
Static
Micro-switch dead band 1)
Adjustable dead band
Code
N (T*)
M (K*)
Fixed dead band
C(W*)
10%
90%
10%
S
90%
10%
90%
mbar
bar
200
20
156
8 - 80
10.5 - 80
35 - 80
45 - 80
5.8
9.5
157
15 - 150
20 - 150
40 - 150
50 - 150
10.5
17
mbar
10 ... 400
400
20
10 ... 1000
1000
20
158
18 - 150
22 - 150
45 - 150
60 - 150
11.5
19.6
10 ... 700
700
20
161**
30 - 250
45 - 250
130 - 450
150 - 450
27.5
34
10 ... 1500
1500
20
162**
30 - 300
45 - 300
130 - 450
150 - 450
27.5
34
10 ... 2000
2000
20
163**
45 - 300
90 - 300
180 - 450
300 - 450
31
50
(*) For version with 2 microswitches lower values of the dead band must be multiplied x 1.5
(**) G1/4 female only
The value of the dead band is depending on the value of the set point.
This table contains the dead band values for set point adjustment at 10% and 90% of the selected scale. For adjustable dead band the lower value corresponds to the
dead band spring totally released and the higher corresponds to the dead band spring fully tensed . For other set points the dead band value can be calculated by
linear interpolation between the values at 10% and 90%.
2015-04-14
Design and specifications subject to change without notice
1)
www.baumer.com
Data sheet A32.42
Page 3 / 5
RDY6
Differential pressure switch with intrinsic safety
for variable static pressure
Dimensions (mm)
125
76.5
=
144
139
=
58
130
5
64
100
45°
Pressure range codes : 156 - 157 - 158
Weight : 6.6 kg
Pressure range codes : 161 - 162 - 163
Weight : 7 kg
130
144
76,5
28,5
G 1/2 (M)
LP
HP
109
LP
Ø100
2015-04-14
Design and specifications subject to change without notice
48
29,5
100
G 1/2 (M)
HP
2 holes G 1/4 (F)
Hex 24
Ø 148
www.baumer.com
Data sheet A32.42
Page 4 / 5
RDY6
Differential pressure switch with intrinsic safety
for variable static pressure
Ordering details RDY6
RD
Model
Differential pressure switch for variable static pressure
Approvals
ATEX intrinsic safety
Sensing element
Diaphragm (Viton ®)
Type of micro switches
1 SPDT hermetically changeover switch
2 SPDT hermetically changeover switch
1 SPDT gold contact changeover switch
2 SPDT gold contact changeover switch
1 SPDT tropicalized changeover switch
2 SPDT tropicalized changeover switch
1 SPDT ultrasensitive gold contact changeover switch
Process connection
G 1/4 female (only pressure ranges 161, 162, 163)
G 1/2 male (standard)
1/2 NPT male
1/4 NPT female
Pressure range (mbar)
Pressure range (kPa)
10
...
200
1
...
20
10
...
400
1
...
40
10
... 1000
1
...
100
10
...
700
1
...
70
10
... 1500
1
...
150
10
... 2000
1
...
200
Options to be added behind the / (see example below)
Y
–
6
.
xxx
/
RD
Y
–
6
Deadband
Adjustable
Adjustable
Adjustable
Adjustable
Adjustable
Adjustable
Fix
C
W
M
K
N
T
S
H
3
6
8
.
156
157
158
161
162
163
Process connection G1/4 female
Process connection G1/4 female
Process connection G1/4 female
/
Ordering example with options
RD
Y
–
6
C
3
.
156
/
0407
_
9941
Differential pressure switch
With ATEX approval intrinsic safety
Sensing element diaphragm
1 SPDT hermetically changeover switch
Process connection G 1/2 male
Pressure range 10 ... 200 mbar
Option : Mounting on 2" pipe
2015-04-14
Design and specifications subject to change without notice
Option : Stainless steel tag plate and wire
www.baumer.com
Data sheet A32.42