RPPN RPPN

RPPN
Industrial pressure switch
Main Features
„„
Excellent repeatability
„„
Dead band adjustment for regulation
„„
Fix dead band for control and alarm
Applications
„„Energy safety equipment
„„Power generation safety equipment
„„Pressurized chambers control
„„Liquid level control
Technical Data
Pressure range
-200 mbar ... 0 to 60 ... 600 bar
Scale
Internal. Accuracy on reading ± 5% FS
Temperatures
Pressure range codes 101 to 153
Medium : -15 ... +150°C
Ambient : -25 ... + 70°C
Storage : -40 ... + 70°C
Cover
Case
Zamak blue painted
Captive stainless steel screws
Black Zamak
Mounting
Wall mounting braket
Ground connection
Via internal terminal block
Electrical
connection
Terminal block with plastic cable gland for
Ø 7 to 10.5 mm
Electrical function
See ordering code details on page 5
Adjustment
2 external adjustment screws on top of the case
for set point and dead band
Pressure range codes 200 to 602
Medium : -50 ... +200°C
Ambient : -25 ... + 55°C
Storage : -40 ... + 70°C
Repeatability
± 1% F.S. @ constant pressure cycle
CE conformity
Low Voltage Directive LVD 2006/95/EC
Pressure Equipment Directive PED 97/23/EC
IP 66 (EN 60529)
Protection rating
Process Connection Stainless steel 1.4404 (316L)
Sensing element
Pressure range codes 101 to 153
Flanges :Stainless steel 1.4404 (316L)
Diaphragm :Viton®
Pressure range codes 200 to 209
Bellow :Stainless steel 1.4404 or
1.4432 (316L)
Design and specifications subject to change without notice
Pressure range codes 600 to 602
Piston :Nickel plated steel
Options
Code SETP
Oxygen application
Code 0765
Mounting on 2" pipe
Code 0407
Electrical connection : stainless steel connector (Souriau)
Code 2298
Mobile plug for stainless steel connector (Souriau)
Code 2249
Stainless steel tag plate and wire
Code 9941
Lead seal of the adjustment screws
Code 8990
2015-04-21
Customer specific set point adjustment
www.baumer.com
Data sheet A32.03
Page 1 / 5
RPPN
Industrial pressure switch
Principle
A flexible sensing element actuates a microswitch by means of a
lever. The set point is adjusted by means of a compressible spring
installed in opposition.
NC
NC
NC
C
C
C
NO
NO
NO
Set point and reset point must be between 10% and 90% of the
selected scale.
Standard factory adjustment
Setpoint at 50% of the scale on falling pressure
Customer specific factory adjustment (option SETP)
The following specifications have to be given with the order:
• Setpoint value
• Adjustment on falling or raising pressure
• Dead band value when using an adjustable dead band switch
NC
C
NC
NC
C
C
NO
NO
NO
Electrical connections
2 SPDT
1 SPDT
NC
Blue
COM
Red
NO
White
NC
Blue
COM
Red
NO
Yellow / green
NC
COM
NO
White
Blue
Red
White
2015-04-21
Design and specifications subject to change without notice
Yellow / green
www.baumer.com
Data sheet A32.03
Page 2 / 5
RPPN
Industrial pressure switch
Micro switches characteristics
Switch code
N (T)
A (B)
M (K)
C (W)
E (F)
H
D (V)
J
Type
Tropicalized
Standard
Gold contact
Hermetic
Ultra sensitive
Manual reset
Ultra sensitive
Hermetic
Manual reset
6 Vdc
0.1 ... 8 A
0.4 ... 10 A
10 ... 50 mA
5 mA ... 4 A
0.4 ... 1 A
N/A
0.4 ... 4 A
N/A
12 Vdc
0.1 ... 8 A
0.4 ... 10 A
10 ... 50 mA
5 mA ... 4 A
0.4 ... 1 A
N/A
0.4 ... 4 A
N/A
24 Vdc
0.1 ... 8 A
0.4 ... 6 A
10 ... 50 mA
5 mA ... 4 A
0.4 ... 1 A
0.1 ... 8 A
0.4 ... 4 A
N/A
30 Vdc
0.1 ... 8 A
0.4 ... 6 A
10 ... 50 mA
5 mA ... 3 A
0.4 ... 1 A
0.1 ... 8 A
0.4 ... 2 A
0.1 ... 10 A
48 Vdc
0.1 ... 8 A
0.4 ... 6 A
10 ... 50 mA
5 mA ... 3 A
N/A
0.1 ... 8 A
N/A
0.1 ... 10 A
110 Vdc
N/A
0.1 ... 0.5 A
10 ... 50 mA
5 mA ... 1 A
N/A
N/A
N/A
N/A
220 Vdc
N/A
0.1 ... 0.25 A
10 ... 50 mA
5 mA ... 0.5 A
N/A
N/A
N/A
N/A
115 Vac
0.1 ... 10 A
0.4 ... 10 A
10 ... 50 mA
50 mA ... 3 A
0.4 ... 10 A
0.1 ... 10 A
N/A
0.1 ... 10 A
250 Vac
0.1 ... 5 A
0.2 ... 10 A
10 ... 50 mA
50 mA ... 2.5 A
0.2 ... 10 A
0.1 ... 5 A
N/A
0.1 ... 5 A
2000 V
2000 V
2000 V
1500 V
2000 V
2000 V
1000 V
2000 V
Dielectric rigidity
between contacts
and ground
Adjustable ranges
mbar
-50 ... Adjustable dead band
Code
bar
0
N (T*)
A (B*)
M (K*)
Fixed dead band
C (W*)
E (F*)
10%
90%
10%
90%
H
10%
90%
10%
D (V*)
J
90%
mbar
0.15
101
2 - 25
2.5 - 25
6.5 - 25
7.5 - 25
0.5
0.5
2.5
3
102
1-5
1.2 - 5
4.5 - 5
4.5 - 5
0.3
0.3
1.5
1.5
-2
... 10
0.15
-5
... 50
0.15
103
1.2 - 15
2 - 15
5 - 15
7 - 15
0.4
0.4
1.5
2.5
-8
... 100
0.15
104
1.5 - 25
2 - 25
5 - 25
10 - 25
0.5
0.5
2
2.5
0
1
151
6 - 80
8 - 80
15 - 80
15 - 80
2
3
7.5
10
0
... 200
1
152
6 - 80
8 - 80
15 - 80
15 - 80
2
3
7.5
10
0
... 400
1
153
15 - 150
20 - 150
30 - 150
35 - 150
4
6
18
25
bar
Code
1.5
200
25 - 250
35 - 250
80 - 250
95 - 250
5
6
30
42
80 - 1200
100 - 1200
150 - 1200
200 - 1200
22
25
96
120
-200... bar
-1
... 0
mbar
-1
... 2.5
7
201
0
... 0.2
1.5
202
15 - 100
20 - 100
60 - 100
65 - 100
4
5
18
24
1
1.5
203
20 - 400
25 - 400
80 - 400
95 - 400
4
5
24
30
0.5 ... 10
30
204
200 - 3000
250 - 3000
650 - 3000
850 - 3000
45
50
240
300
3.5 ... 25
30
205
600 - 5000
1200 - 5000
750 - 5000
1300 - 5000
60
100
720
1440
bar
bar
Code
0.05... bar
5
... 50
65
206
1 - 10
2 - 10
2.5 - 10
3 - 10
0.15
0.2
1.5
2.5
5
... 100
220
207
2.5 - 15
3 - 15
5.5 - 15
6.5 - 15
0.7
0.9
3
3.5
20 ... 150
220
208
2.5 - 15
3.5 - 15
5.5 - 15
6.5 - 15
0.7
1
3
4.5
0.25
... 3.5
30
209
0.15 - 1.5
0.2 - 1.5
0.65 - 1.5
0.85 - 1.5
0.045
0.050
0.2
25 ... 175
800
600
20 - 80
30 - 80
30 - 80
35 - 80
14
14
24
36
30 ... 350
800
601
20 - 100
30 - 100
30 - 100
35 - 100
16
16
24
36
60 ... 600
800
602
20 - 120
30 - 120
30 - 120
35 - 120
16
16
24
36
-1
(*) For version with 2 microswitches lower values of the dead band must be multiplied x 1.5
The value of the dead band is depending on the value of the set point.
This table contains the dead band values for set point adjustment at 10% and 90% of the selected scale. For adjustable dead band the lower value corresponds to
the dead band spring totally released and the higher corresponds to the dead band spring fully tensed. For other set points the dead band value can be calculated
by linear interpolation between the values at 10% and 90%.
1)
www.baumer.com
Data sheet A32.03
Page 3 / 5
Design and specifications subject to change without notice
Scale
Micro-switch dead band 1)
2015-04-21
P. Max
accidental
RPPN
Industrial pressure switch
Dimensions (mm)
125
76.5
=
144
139
=
58
130
5
64
100
45°
Pressure range codes : 151 - 152 - 153
Weight : 2.8 kg
130
Pressure range codes : 200 - 202 - 203
Weight : 2.5 kg
130
68
52
52
144
144
144
130
24
24
Ø 218
24
Ø 146
Ø 90
Pressure range codes : 204 - 205 - 206 - 207
208 - 209 - 600 - 601 - 602
Weight : 2 kg
Pressure range codes : 201
Weight : 2.4 kg
130
130
17
144
144
Design and specifications subject to change without notice
Pressure range codes : 101 - 102 - 103 - 104
Weight : 3 kg
68
24
2015-04-21
24
Ø 65
www.baumer.com
Data sheet A32.03
Page 4 / 5
RPPN
Industrial pressure switch
Ordering details RPPN
RP
Model
Industrial pressure switch
Approvals
Standard version without ATEX approval
A
–
.
xxx
/
RP
PN
–
Deadband
Adjustable
Adjustable
Adjustable
Adjustable
Fix
Fix
Fix
Fix
Adjustable
Adjustable
Adjustable
Adjustable
Fix
Fix
A
B
C
W
E
F
D
V
M
K
N
T
H
J
Z
Y
A
3
6
8
Pressure range (mbar)
Pressure range (kPa)
-50 ...
0
-5
...
0
-2 ... 10
-0.2 ...
1
-5 ... 50
-0.5 ...
5
-8 ... 100
-0.8 ... 10
-200...
0
-20 ...
0
0 ... 200
0
... 20
0 ... 400
0 ... 40
Pressure range (bar)
Pressure range (kPa)
-1 ...
0
-100 ...
0
-1 ... 2.5
-100 ... 250
0 ... 0.2
0
...
20
0.05 ...
1
5
... 100
0.5 ... 10
50
... 1000
3.5 ... 25
350 ... 2500
5 ... 50
500 ... 5000
5 ... 100
500 ... 10000
20 ... 150
2000 ... 15000
-1 ... 3.5
-100 ... 350
25 ... 175
2500 ... 17500
30 ... 350
3000 ... 35000
60 ... 600
6000 ... 60000
Options to be added behind the / (see example below)
.
101
102
103
104
151
152
153
200
201
202
203
204
205
206
207
208
209
600
601
602
/
Ordering example with options
RP
PN
–
A
A
3
.
101
/
0407
_
9941
Industrial pressure switch
Without ATEX approval
1 SPDT standard changeover switch
Standard type
Process connection G 1/2 male
Pressure range -50 ... 0 mbar
2015-04-21
Option : Mounting on 2" pipe
Option : Stainless steel tag plate and wire
www.baumer.com
Design and specifications subject to change without notice
Type of micro switches
1 SPDT standard changeover switch
2 SPDT standard changeover switch
1 SPDT hermetically changeover switch
2 SPDT hermetically changeover switch
1 SPDT ultra sensitive changeover switch
2 SPDT ultra sensitive changeover switch
1 SPDT hermetically, ultra sensitive changeover switch
2 SPDT hermetically, ultra sensitive changeover switch
1 SPDT gold contact changeover switch
2 SPDT gold contact changeover switch
1 SPDT tropicalized changeover switch
2 SPDT tropicalized changeover switch
1 SPDT changeover switch, manual reset, opening on raising pressure
1 SPDT changeover switch, manual reset, opening on falling pressure
Pneumatic changeover contact, NO
Pneumatic changeover contact, NC
Type
Standard
Process connection
G 1/2 male (standard)
1/2 NPT male
1/4 NPT female
PN
Data sheet A32.03