Technical Data RDE5

RDE5
Differential pressure switch, explosion proof for
high static pressure
Main Features
„„
Excellent repeatability
„„
Dead band adjustment for regulation
„„
Fix dead band for control and alarm
„„
High static pressure
„„
Explosion proof Hazardous areas 1, 2, 21, 22
Applications
„„Power generation safety equipment
„„Pressurized chambers control
„„Liquid level control
Technical Data
Pressure range
2 ... 10 mbar to 10 ... 2000 mbar
Ground connection
Via internal terminal block
Temperature
Process : -15 ... +150°C
Ambient : -20 ... +55°C
Storage : -40 ... +70°C
Electrical
connection
Terminal block with metallic cable gland for
Ø 7 to 12 mm standard
Repeatability
± 1% F.S. @ constant pressure cycle
Electrical function
See ordering code details on page 5
CE conformity
Low Voltage Directive LVD 2006/95/EC
Pressure Equipment Directive PED 97/23/EC
ATEX Directive 94/9/EC
Adjustment
Protection rating
IP 66 (EN 60529)
2 external adjustment screws for set point and
deadband.
When set point adjustment is required it is necessary to know the static pressure, as it has an
influence on the set point.
ATEX
Type examination certificate
LCIE 03 ATEX 6231X (Type RA80)
EN 60079-0:2012 (internal conformity analysis)
EN 60079-1:2007
EN 60079-31: 2009
Marking
0081
II 2 G D
Ex d IIC T6 or T5 Gb
Ex t IIIC IIC T80°C or T95°C Db IP6X
Sensing element
Pressure range codes 111 to 131
Flanges :Stainless steel 1.4404 (316L)
Diaphragm : Nitrile Butyl rubber
Pressure range codes 156 to 163
Flanges :Stainless steel 1.4404 (316L)
Diaphragm :Viton®
Scale
Internal. Accuracy on reading ± 5% FS
Housing
Type RA80, explosion proof, flameproof
Alumunium epoxy painted.
Captive stainless steel screws
Mounting
3 back lugs for wall mounting
T° ambient
-20°C to +60°C (T6 or T80°C) or
-20°C to +70°C (T5 or T95°C)
Design and specifications subject to change without notice
Process Connection Stainless steel 1.4404 (316L)
Options
Code SETP
Oxygen application
Code 0765
Lead seal of the adjustment screws
Code 8990
Mounting on 2" pipe
Code 0407
Stainless steel tag plate and wire
Code 9941
2015-05-26
Customer specific set point adjustment
www.baumer.com
Data sheet A32.23
Page 1 / 5
RDE5
Differential pressure switch, explosion proof for
high static pressure
Principle
∆P
A flexible sensing element actuates a microswitch by means of a
piston. The set point is adjusted by means of a compressible spring
installed in opposition.
NC
NC
C
C
NC
C
NO
NO
NO
HP > LP
HP < LP
Set point and reset point must be between 10% and 90% of the selected scale.
Standard factory adjustment
Setpoint at 50% of the scale on falling pressure
NC
C
NO
NC
NC
C
C
NO
NO
Customer speciffic factory adjustment (option SETP)
The following specifications have to be given with the order:
• Setpoint value
• Adjustment on falling or raising pressure.
• Static pressure
• Dead band value when using an adjustable dead band switch
Electrical connections
2 SPDT
1 SPDT
NC
COM
NO
Blue
Red
White
NC
Blue
COM
Red
NO
White
NC
Blue
COM
Red
NO
White
Yellow / green
Hazardous areas : 1, 2, 21, 22
-20°C ≤ Ta ≤ +70°C
Dust IP6x
Gases
T° surface
Class
Ta = 60°C
80°C
T6
Ta = 70°C
95°C
T5
Important : Maximum power dissipation in the case
must not exceed 5 W
2015-05-26
All necessary measures must be taken by the user, to avoid the calorific transfer from the fluid to the apparatus head increasing the head's
temperature to such that it reaches the self-ignition temperature of the gas in which it is used.
Design and specifications subject to change without notice
Yellow / green
www.baumer.com
Data sheet A32.23
Page 2 / 5
RDE5
Differential pressure switch, explosion proof for
high static pressure
Micro switches characteristics
Switch code
Type
N (T)
A (B)
M (K)
C (W)
E (F)
D (V)
Tropicalized
Standard
Gold contact
Hermetic
Ultra
sensitive
Ultra sensitive
Hermetic
6 Vdc
0.1... 8A
0.4... 10 A
10... 50 mA
5 mA ... 4 A
0.4... 1A
0.4... 4A
12 Vdc
0.1... 8A
0.4... 10 A
10... 50 mA
5 mA ... 4 A
0.4... 1A
0.4... 4A
24 Vdc
0.1... 8A
0.4... 6A
10... 50 mA
5 mA ... 4 A
0.4... 1A
0.4... 4A
30 Vdc
0.1... 8A
0.4... 6A
10... 10 mA
5 mA ... 3 A
0.4... 1A
0.4... 2A
48 Vdc
0.1... 8A
0.4... 110 Vdc
220 Vdc
6A
10... 50 mA
5 mA ... 3 A
N/A
N/A
N/A
0.1... 0.5 A
10... 50 mA
5 mA ... 1 A
N/A
N/A
N/A
N/A
N/A
0.1... 0.25 A
10... 50 mA
5 mA ... 0.5 A
115 Vac
0.1... 10 A
0.4... 10 A
10... 50 mA
50 mA ... 3 A
250 Vac
0.1... 5A
0.2... 10 A
10... 10 mA
2000 V
Dielectric rigidity between contacts and ground
2000 V
2000 V
0.4... 10 A
N/A
50 mA ... 2.5 A
0.2 ... 10 A
N/A
1500 V
2000 V
1000 V
Adjustable ranges
Scale
Max
ΔP
Max P
Static
mbar
mbar
bar
2 ... 10
10
0 ... 5
2 ... 20
50
2 ... 50
50
Micro-switch dead band 1)
Adjustable dead band
Code
N (T*)
A (B*)
10%
M (K*)
90%
Fixed dead band
C(W*)
10%
E(F*)
90%
D (V*)
10%
90%
10%
90%
mbar
111
1.8 - 15
2.4 - 15
6.7 - 15
6.7 - 15
0.45
0.6
2.25
3
0 ... 5
112
2.6 - 30
3.3 - 30
7.5 - 30
8 - 30
0.6
0.75
3
4.5
0 ... 5
121
2.6 - 40
3.3 - 40
7.5 - 40
8 - 40
0.6
0.75
3
4.5
2 ... 100
100
0 ... 5
131
2.6 - 60
3.7 - 60
8.2 - 60
15 - 60
0.75
1.05
3
4.5
10 ... 200
200
5.5 ... 50
156
12 - 120
15.5 - 120
52 - 120
67 - 120
3.75
5.1
15
19.5
10 ... 400
400
5.5 ... 50
157
22 - 225
30 - 225
60 - 225
75 - 225
6.75
9
27
36
10 ... 1000
1000
5.5 ... 50
158
27 -225
33 - 225
67 - 225
90 - 225
7.5
10.5
33
40
10 ... 700
700
5.5 ... 80
161**
30 - 300
45 - 300
90 - 525
135 - 525
9
12
36
54
30 - 450
45 - 450
90 - 525
150 - 525
9
12
36
54
40 - 450
90 - 450
135 - 525
300 - 525
13
18
54
108
10 ... 1500
1500
5.5 ... 80
162**
10 ... 2000
2000
5.5 ... 80
163**
(*) For version with 2 microswitches lower values of the dead band must be multiplied x 1.5
(**) G 1/4 female only
The value of the dead band is depending on the value of the set point.
This table contains the dead band values for set point adjustment at 10% and 90% of the selected scale. For adjustable dead band the lower value corresponds to the
dead band spring totally released and the higher corresponds to the dead band spring fully tensed . For other set points the dead band value can be calculated by
linear interpolation between the values at 10% and 90%.
2015-05-26
Design and specifications subject to change without notice
1)
www.baumer.com
Data sheet A32.23
Page 3 / 5
RDE5
Differential pressure switch, explosion proof for
high static pressure
Dimensions (mm)
Set point adjustment
Differential adjustment
56
(3x) Ø 9 on Ø 222
86
20
Ø 194
Weight : 4.4 kg
12
0°
120°
116
RA
x d II C T
0°
6
12
Cable gland
not mounted
121
Pressure range codes : 111 - 112 - 121 - 131
Weight : 8.8 kg
Pressure range codes : 156 - 157 - 158
Weight : 4.7 kg
1/2 NPT(M)
48
G 1/2(M)
LP
LP
Hex 24
94
Ø 260
56
83
Hex 24
Ø 148
Hex 24
HP
HP
1/2 NPT(M)
88
139
EE
Hex 24
76.5
G 1/2(M)
95
Pressure range codes : 161-162-163
Weight : 5.4 kg
Design and specifications subject to change without notice
28.5
97
LP
36
HP
Ø120
2015-05-26
2 holes G 1/4 (F)
Hex 24
www.baumer.com
Data sheet A32.23
Page 4 / 5
RDE5
Differential pressure switch, explosion proof for
high static pressure
Ordering details RDE5
RD E
Model
Differential pressure switch
Approvals
Explosion proof
Sensing element
Diaphragm (Nitrile Butyl rubber, ranges 111 to 131, Viton®, ranges 156 to 163)
Type of micro switches
1 SPDT standard changeover switch
2 SPDT standard changeover switch
1 SPDT hermetically changeover switch
2 SPDT hermetically changeover switch
1 SPDT ultra sensitive changeover switch
2 SPDT ultra sensitive changeover switch
1 SPDT hermetically, ultra sensitive changeover switch
2 SPDT hermetically, ultra sensitive changeover switch
1 SPDT gold contact changeover switch
2 SPDT gold contact changeover switch
1 SPDT tropicalized changeover switch
2 SPDT tropicalized changeover switch
Process connection
G 1/4 female (only pressure ranges 161, 162, 163)
G 1/2 male (standard)
1/2 NPT male
1/4 NPT female
Pressure range (mbar)
Pressure range (kPa)
2
...
10
0.2 ...
1
2
...
20
0.2 ...
2
2
...
50
0.2 ...
5
2
...
100
0.2 ...
10
10
...
200
1
...
20
10
...
400
1
...
40
10
... 1000
1
...
100
10
...
700
1
...
70
10
... 1500
1
...
150
10
... 2000
1
...
200
Options to be added behind the / (see example below)
–
5
.
xxx
/
RD
E
–
5
Deadband
Adjustable
Adjustable
Adjustable
Adjustable
Fix
Fix
Fix
Fix
Adjustable
Adjustable
Adjustable
Adjustable
A
B
C
W
E
F
D
V
M
K
N
T
H
3
6
8
.
111
112
121
131
156
157
158
161
162
163
Process connection G1/4 female
Process connection G1/4 female
Process connection G1/4 female
/
Ordering example with options
RD
E
–
5
C
3
.
111
/
0407
_
9941
Differential pressure switch
With ATEX approval explosion proof
Sensing element diaphragm
Design and specifications subject to change without notice
1 SPDT hermetically changeover switch
Process connection G 1/2 male
Pressure range 2 ... 10 mbar
Option : Mounting on 2" pipe
2015-05-26
Option : Stainless steel tag plate and wire
www.baumer.com
Data sheet A32.23
Page 5 / 5