Technical Data RDE6

RDE6
Differential pressure switch, explosion proof for
variable static pressure
Main Features
„„
Excellent repeatability
„„
Dead band adjustment for regulation
„„
Fix dead band for control and alarm
„„
Static pressure max. 20 bar
„„
No influence of the static pressure on the setpoint
„„
Explosion proof Hazardous areas 1, 2, 21, 22
Applications
„„Power generation safety equipment
„„Pressurized chambers control
„„Liquid level control
Technical Data
10 ... 200 mbar to 10 ... 2000 mbar
Temperature
Process : -15 ... +150°C
Ambient : -20 ... +55°C
Storage : -40 ... +70°C
Repeatability
± 1% F.S. @ constant pressure cycle
CE conformity
Low Voltage Directive LVD 2006/95/EC
Pressure Equipment Directive PED 97/23/EC
ATEX Directive 94/9/EC
Protection rating
IP 66 (EN 60529)
Process Connection Stainless steel 1.4404 (316L)
Sensing element
Pressure range codes 156 to 163
Flanges :Stainless steel 1.4404 (316L)
Diaphragm :Viton®
Scale
Internal. Accuracy on reading ± 5% FS
Housing
Type RA80, explosion proof, flameproof
Alumunium epoxy painted.
Captive stainless steel screws
Mounting
3 back lugs for wall mounting
Ground connection
Via internal terminal block
Electrical
connection
Terminal block with metallic cable gland for
Ø 7 to 12 mm standard
Electrical function
See ordering code details on page 5
Adjustment
2 external adjustment screws on top of the case
for set point and dead band.
The adjustment is not influenced by changes of
the static pressure.
ATEX
Type examination certificate
LCIE 03 ATEX 6231X (Type RA80)
EN 60079-0: 2012 (internal conformity analysis)
EN 60079-1: 2007
EN 60079-31: 2009
Marking
0081
II 2 G D
Ex d IIC T6 or T5 Gb
Ex t IIIC IIC T80°C or T95°C Db IP6X
T° ambient
-20°C to +60°C (T6 or T80°C) or
-20°C to +70°C (T5 or T95°C)
Design and specifications subject to change without notice
Pressure range
Options
Code SETP
Oxygen application
Code 0765
Lead seal of the adjustment screws
Code 8990
Mounting on 2" pipe
Code 0407
Stainless steel tag plate and wire
Code 9941
2015-05-26
Customer specific set point adjustment
www.baumer.com
Data sheet A32.43
Page 1 / 5
RDE6
Differential pressure switch, explosion proof for
variable static pressure
Principle
∆P
A flexible sensing element actuates a microswitch by means of a
piston. The set point is adjusted by means of a compressible spring
installed in opposition.
NC
NC
C
C
NC
C
NO
NO
NO
HP > LP
HP < LP
Set point and reset point must be between 10% and 90% of the selected scale.
Standard factory adjustment
Setpoint at 50% of the scale on falling pressure
NC
C
NO
NC
NC
C
C
Customer speciffic factory adjustment (option SETP)
The following specifications have to be given with the order:
• Setpoint value
• Adjustment on falling or raising pressure.
• Dead band value when using an adjustable dead band switch
NO
NO
Electrical connections
2 SPDT
1 SPDT
NC
COM
NO
Blue
Red
White
NC
Blue
COM
Red
NO
White
NC
Blue
COM
Red
NO
White
Yellow / green
Hazardous areas : 1, 2, 21, 22
-20°C ≤ Ta ≤ +70°C
Dust IP6x
Gases
T° surface
Class
Ta = 60°C
80°C
T6
Ta = 70°C
95°C
T5
Important : Maximum power dissipation in the case
must not exceed 5 W
2015-05-26
All necessary measures must be taken by the user, to avoid the calorific transfer from the fluid to the apparatus head increasing the head's
temperature to such that it reaches the self-ignition temperature of the gas in which it is used.
Design and specifications subject to change without notice
Yellow / green
www.baumer.com
Data sheet A32.43
Page 2 / 5
RDE6
Differential pressure switch, explosion proof for
variable static pressure
Micro switches characteristics
Switch code
Type
N (T)
A (B)
M (K)
C (W)
E (F)
D (V)
Tropicalized
Standard
Gold contact
Hermetic
Ultra
sensitive
Ultra sensitive
Hermetic
6 Vdc
0.1... 8A
0.4... 10 A
10... 50 mA
5 mA ... 4 A
0.4... 1A
0.4... 4A
12 Vdc
0.1... 8A
0.4... 10 A
10... 50 mA
5 mA ... 4 A
0.4... 1A
0.4... 4A
24 Vdc
0.1... 8A
0.4... 6A
10... 50 mA
5 mA ... 4 A
0.4... 1A
0.4... 4A
30 Vdc
0.1... 8A
0.4... 6A
10... 10 mA
5 mA ... 3 A
0.4... 1A
0.4... 2A
48 Vdc
0.1... 8A
0.4... 110 Vdc
220 Vdc
6A
10... 50 mA
5 mA ... 3 A
N/A
N/A
N/A
0.1... 0.5 A
10... 50 mA
5 mA ... 1 A
N/A
N/A
N/A
N/A
N/A
0.1... 0.25 A
10... 50 mA
5 mA ... 0.5 A
115 Vac
0.1... 10 A
0.4... 10 A
10... 50 mA
50 mA ... 3 A
250 Vac
0.1... 5A
0.2... 10 A
10... 10 mA
2000 V
Dielectric rigidity between contacts and ground
2000 V
2000 V
0.4... 10 A
N/A
50 mA ... 2.5 A
0.2 ... 10 A
N/A
1500 V
2000 V
1000 V
Adjustable ranges
Scale
mbar
Max
ΔP
Max P
Static
Micro-switch dead band 1)
Adjustable dead band
Code
N (T*)
A (B*)
10%
M (K*)
90%
Fixed dead band
C(W*)
10%
E(F*)
90%
D (V*)
10%
90%
10%
90%
mbar
bar
10 ... 200
200
20
156
12 - 120
15.5 - 120
52 - 120
67 - 120
3.75
5.1
15
19.5
10 ... 400
400
20
157
22 - 225
30 - 225
60 - 225
75 - 225
6.75
9
27
36
1000
20
158
27 - 225
33 - 225
67 - 225
90 - 225
7.5
10.5
33
40
10 ... 700
700
20
161**
45 - 375
67 - 375
195 - 675
225 - 675
19.5
22.5
54
81
10 ... 1500
1500
20
162**
45 - 450
67 - 450
195 - 675
225 - 675
19.5
22.5
54
81
10 ... 2000
2000
20
163**
67 - 450
135 - 450
270 - 675
450 - 675
27
37.5
81
162
10 ... 1000
mbar
(*) For version with 2 microswitches lower values of the dead band must be multiplied x 1.5
(**) G 1/4 female only
The value of the dead band is depending on the value of the set point.
This table contains the dead band values for set point adjustment at 10% and 90% of the selected scale. For adjustable dead band the lower value corresponds to the
dead band spring totally released and the higher corresponds to the dead band spring fully tensed . For other set points the dead band value can be calculated by
linear interpolation between the values at 10% and 90%.
2015-05-26
Design and specifications subject to change without notice
1)
www.baumer.com
Data sheet A32.43
Page 3 / 5
RDE6
Differential pressure switch, explosion proof for
variable static pressure
Dimensions (mm)
Set point adjustment
Differential adjustment
56
(3x) Ø 9 on Ø 222
86
20
Ø 194
12
Weight : 4.4 kg
0°
120°
116
RA
139
EE
x d II C T
0°
6
12
Cable gland
not mounted
121
Pressure range codes : 156 - 157 - 158
Weight : 4.4 kg
Pressure range codes : 161 - 162 - 163
Weight : 3.3 kg
G 1/2 (M)
LP
Hex 24
HP
48
HP
109
29,5
LP
Ø100
2015-05-26
Design and specifications subject to change without notice
G 1/2 (M)
2 holes G 1/4 (F)
100
Ø 148
www.baumer.com
Data sheet A32.43
Page 4 / 5
RDE6
Differential pressure switch, explosion proof for
variable static pressure
Ordering details RDE6
RD E
Model
Differential pressure switch for variable static pressure
Approvals
Explosion proof
Sensing element
Diaphragm (Viton®)
Type of micro switches
1 SPDT standard changeover switch
2 SPDT standard changeover switch
1 SPDT hermetically changeover switch
2 SPDT hermetically changeover switch
1 SPDT ultra sensitive changeover switch
2 SPDT ultra sensitive changeover switch
1 SPDT hermetically, ultra sensitive changeover switch
2 SPDT hermetically, ultra sensitive changeover switch
1 SPDT gold contact changeover switch
2 SPDT gold contact changeover switch
1 SPDT tropicalized changeover switch
2 SPDT tropicalized changeover switch
Process connection
G 1/4 female (only pressure ranges 161, 162, 163)
G 1/2 male (standard)
1/2 NPT male
1/4 NPT female
Pressure range (mbar)
Pressure range (kPa)
2
...
10
0.2 ...
1
2
...
20
0.2 ...
2
2
...
50
0.2 ...
5
2
...
100
0.2 ...
10
10
...
200
1
...
20
10
...
400
1
...
40
10
... 1000
1
...
100
10
...
700
1
...
70
10
... 1500
1
...
150
10
... 2000
1
...
200
Options to be added behind the / (see example below)
–
6
.
xxx
/
RD
E
–
6
Deadband
Adjustable
Adjustable
Adjustable
Adjustable
Fix
Fix
Fix
Fix
Adjustable
Adjustable
Adjustable
Adjustable
A
B
C
W
E
F
D
V
M
K
N
T
H
3
6
8
.
111
112
121
131
156
157
158
161
162
163
Process connection G1/4 female
Process connection G1/4 female
Process connection G1/4 female
/
Ordering example with options
RD
E
–
6
C
3
.
111
/
0407
_
9941
Differential pressure switch for variable static pressure
With ATEX approval explosion proof
Sensing element diaphragm
Design and specifications subject to change without notice
1 SPDT hermetically changeover switch
Process connection G 1/2 male
Pressure range 2 ... 10 mbar
Option : Mounting on 2" pipe
2015-05-26
Option : Stainless steel tag plate and wire
www.baumer.com
Data sheet A32.43
Page 5 / 5