F9000_PCR273

PCR273
High Power factor State of
the art Current Regulator.
For 2,8—6,6Amp Series
circuits in Airfield
lighting systems
tP
Paten
ending
The PCR 273 Current Regulator is designed for use in airfield lightning systems that use
constant current (2,8-6,6Amps) for power distribution to Information and Direction signs.
The unit contains one complete lamp ballast for 36 up to 58W fluorescent TL tubes.
The PCR 273 presents a very high power factor seen by the Constant Current Regulator
(CCR). This contributes to a good power-factor for the entire system and lower operating
costs as result.
Block diagram PCR273 Current Regulator
EMI Current–
transformer
Installation instructions
Toroid transformer
P/n: 041-00030
Blue
Red
White
Transformer 1:1
6,6A/6,6A 65W
White
PCR273 Current regulator
P/n: 001-00273
Black
Outside Sign
Isolating
Transformer
Power switch
Within Sign
Depending on site
conditions
Lifetime Hours vs Ambient Temp Cº
Lifetime
600000
Hours
400000
300000
Lifetime H:
100000
Technical information
Temperature working
range
- 20 to + 65
Celsius Centigrade
Relative humidity
98% RH
Length 156 Width 56
Mechanical
dimension overall (mm) Height 45
Life time
According to graph
beside
Weight
620 grams
Casing
Metal with plastic
compound
Fluorescent tube
36 to 58W
(Automatic Switch over)
Storage temperature
range
- 20 to + 65
Celsius Centigrade
0
40
50
60
70
Ambient Temp Cº
P.O. ADDRESS
Lamp
36-58W
PFC Controller
200000
30
Lamp
network
2,8-6,6Amps
500000
25
Inverter
Lamp out
Tube 36-58W
White
Rectifier
Phone Switchboard:
Thörnbladsväg 6
S-386 90
Färjestaden
+46 485-56 39 00
SWEDEN
+46 485-358 05
Fax:
PCR273
High Power factor State of
the art Current Regulator.
For 2,8—6,6Amp Series
circuits in Airfield
lighting systems
PowerFactor over Current
Power Factor (PF)
Typical Electrical Data:
The following measurements are made on a
“in-site”system at Changi North Apron,
Singapore International airport.
Measurement made over the CCR output
Used instrument is Fluke 43 Power quality analyzer
System configuration:
CCR at 7,5 kW
20 pcs Fluorescent TL tubes 58W
20 pcs Toroid transformers P/n: 041-00030
20 pcs Current Regulator PCR273 P/n: 001-00273
20 pcs Isolation transformers at 65W
1,00
0,95
0,90
PowerFactor
0,85
0,80
0,75
2,71 3,27 3,96 5,05 6,43
Primary Current (A)
Primary Voltage Drop
80,00
60,00
VA
Consumption
20,00
0,00
2,71 3,27 3,96 5,05 6,43
Voltage (V rms)
Volt Amperé (VA)
VA Consumption over Current
40,00
ing
t Pend
Paten
13,00
12,50
12,00
11,50
11,00
10,50
10,00
9,50
9,00
Primary
Voltage Drop
2,71 3,27 3,96 5,05 6,43
Primary Current
Primary Current (A rms)
Advantages
[High efficiency
[Low temperature rise
[Long life time
[High power factor
[Over voltage and over current
[Simple installation
[Constant tube light output
[Strikes a long life tube at least
[Automatic switch over for 36W to
[Moisture-proof
[Conforms to EMC standards
[Fire resistance class ULV0
P.O. ADDRESS
protected (100 Amps @ 30 sec)
20.000 times
Phone Switchboard:
Thörnbladsväg 6
S-386 90
Färjestaden
+46 485-56 39 00
SWEDEN
+46 485-358 05
Fax:
58W TL lamps