Features • • • • • • • 2 x 2 Industry Standard Package 18−264 Volts AC or DC Operation 0.2 to 8 Minutes (12 to 480 Seconds) Timing Range 0.5% Repeat Accuracy Transient Protected .250” Quick Connect Terminals Encapsulated Construction RLY220 Knob Adjustable, AC or DC, Delay on Operate, Solid State, Universal Cube Timer. D67 .250 (6.35) Dia 2.000 (50.8) .2 8 MINUTES 1 J1 INPUT LOAD 3 JUMPER: SEE NOTE 2.000 (50.8) OPERATION .250 (6.35) DELAY ON OPERATE− The delay period begins when input voltage is applied. At the end of the delay period, the relay will operate and will not release until input voltage is removed. Reset occurs when input voltage is reapplied. .750 (19.05) 1.200 (30.48) ON LINE OFF NOTE: 18−40 V AC or DC Cut J1 for 40−264 V AC, DC ON LOAD DELAY OFF Ratings and Specifications Line Timer 1.0 Amp Max. * 1 3 LOAD * For higher current applications connect a switching relay in series with timer in place of load. NTE Electronics, Inc. Voice (973) 748−5089 Operating Voltage Range (Line): Jumper J1 Not Cut: 18−40 V DC or AC (50/60Hz) Jumper J1 Cut: 40−264 V DC or AC (50/60Hz) Switch Configuration: Solid State, SPST Switching Current (Load): 40mA Amp min., 1 Amp max. Timing Adjustment Range: 0.2 to 8 minutes (12 to 480 seconds) Repeat Accuracy: ±0.5% Reset Time: 100ms Max. Expected Life (Electrical): 100,000,000 operations @ rated load Operating Temperature: −20° to +80°C Storage Temperature: −40° to +85°C Dielectric Breakdown Voltage Between All Elements: 1500Vrms Transient Protection: 1500 V for 150µs Mounting: One #8 or #10 Screw FAX (973) 748−6224 http://www.nteinc.com 89