BATTERY CHARGER & SYSTEMS PBBT Module Series 6 0 0 W AT T S T E L E C O M M U N I C AT I O N S FEATURES • • • • • • Very high efficiency > 89% Low Peak-to-Peak Ripple & Noise Small size 18TE * 220mm * 3RU Optional Battery High and Low alarms Free convection operation Standalone on plug in options SPECIFICATIONS INPUT PROTECTION Input voltage 200 – 264VAC Frequency 45 – 65Hz Power factor 0.64 (full load) Output short circuit protection Output overvoltage protection Input surge voltage 280VAC (1 sec) Output reverse polarity Inrush current cold start 2.5A max Over temperature protection Auto reset Input current full load 3.8A typ 5.0A max Input Fusing Output voltage 42 – 60VDC, 54V nominal Mains On LED (Green) on front panel Output current 10A Rectifier fail Current limit adjust 2 – 11A LED (Red) on front panel N/O voltage free contact Output power Ripple and noise Mains fail N/O voltage free contact Output current 10 segment bar graph Output voltage 1mm protected test sockets Line regulation 600W max 50mV p-p (Complies with ETS 300 132-2) 0.5% at full load Float voltage adjust Front panel potentiometer Load regulation 1.5% no load to full load Current limit adjust Front panel potentiometer Output voltage soft start 0.5 to 5 sec Holdup time 10mS (200VAC, full load) Transient response Overshoot Setting time 50 – 100% load step 2% 1mS Output voltage trimming Slope Control voltage limit (for temperature compensation) -1.0V/V ±5V OUTPUT 322 Output fuse Reset by cycling input mains 61-65VDC 6.3A 250V (T) HRC COMMON ALARMS, DISPLAYS AND CONTROLS OPERATING ALARMS (PBBT-48X (-S) ONLY) Remote On/Off Battery high alarm Adjustment range hysteresis 89% min (full load) Isolation Input – Output 4242VDC Input – Chassis 2121VDC Output – Chassis 2121VDC Battery low alarm adjustment range Parallel operation Current sharing to within ±15% (25% to 100% load) Hysteresis Built in output diode protection Discrete input tied to output positive turns off rectifier ALARMS (PBBT-48X-1 (-S) ONLY) Efficiency Redundancy Auto reset LED (Red) on front panel Front panel potentiometer N/O Voltage Free Contact 52-60VDC 3VDC Configurable to shutdown and latch rectifier by internal link LED (Red) on front panel Front panel potentiometer N/O Voltage Free Contact 40-47VDC 4VDC ENVIRONMENTAL SPECIFICATIONS Cooling Natural Convection Operating ambient temp. -5 to 50°C Humidity 5% to 90% relative non condensing Doc. No. PBC9 Rev.C 28-4-11 PBBT Module Series MECHANICAL SPECIFICATIONS STANDARDS AND APPROVALS Safety ACA TS001, AS/NZS 3260, IEC 60950 CLASS I, Installation Category 2, Pollution Degree 2 C-Tick/RF emissions AS/NZS CSIPR11: 2004 Class B Dimensions Mounting Termination Option 1 Termination Option 2 TECHNICAL ILLUSTRATIONS REAR VIEW OPTION 1 REAR VIEW OPTION 2 18TE Width 236mm Rack mount Depth 247mm Stand alone Depth 3RU Height PBBT-48X/PBBT-48X-1 19” Rack mounting PBBT-48X-S/PBBT-48X-1-S Stand alone PBBT-48X/PBBT-48X-1 Rack Mount Rectifier DIN41612 H15 connector PBBT-48X-S/PBBT-48X-1-S Stand Alone Rectifier Input IEC inlet on near panel Outputs 2-way Anderson 25A powerpole 11-way screw terminal BATTERY CHARGER & SYSTEMS 6 0 0 W AT T S T E L E C O M M U N I C AT I O N S SIDE VIEW Doc. No. PBC9 Rev.C 28-4-11 Powering Progress – www.powerbox.com.au 323