PBBT Module Series

BATTERY CHARGER & SYSTEMS
PBBT Module Series
6 0 0 W AT T S T E L E C O M M U N I C AT I O N S
FEATURES
•
•
•
•
•
•
Very high efficiency > 89%
Low Peak-to-Peak Ripple & Noise
Small size 18TE * 220mm * 3RU
Optional Battery High and Low alarms
Free convection operation
Standalone on plug in options
SPECIFICATIONS
INPUT
PROTECTION
Input voltage
200 – 264VAC
Frequency
45 – 65Hz
Power factor
0.64 (full load)
Output short circuit
protection
Output overvoltage
protection
Input surge voltage
280VAC (1 sec)
Output reverse polarity
Inrush current cold start
2.5A max
Over temperature protection Auto reset
Input current full load
3.8A typ 5.0A max
Input Fusing
Output voltage
42 – 60VDC, 54V nominal
Mains On
LED (Green) on front panel
Output current
10A
Rectifier fail
Current limit adjust
2 – 11A
LED (Red) on front panel
N/O voltage free contact
Output power
Ripple and noise
Mains fail
N/O voltage free contact
Output current
10 segment bar graph
Output voltage
1mm protected test sockets
Line regulation
600W max
50mV p-p
(Complies with ETS 300 132-2)
0.5% at full load
Float voltage adjust
Front panel potentiometer
Load regulation
1.5% no load to full load
Current limit adjust
Front panel potentiometer
Output voltage soft start
0.5 to 5 sec
Holdup time
10mS (200VAC, full load)
Transient response
Overshoot
Setting time
50 – 100% load step
2%
1mS
Output voltage trimming
Slope
Control voltage limit
(for temperature compensation)
-1.0V/V
±5V
OUTPUT
322
Output fuse
Reset by cycling input mains
61-65VDC
6.3A 250V (T) HRC
COMMON ALARMS, DISPLAYS AND CONTROLS
OPERATING
ALARMS (PBBT-48X (-S) ONLY)
Remote On/Off
Battery high alarm
Adjustment range
hysteresis
89% min (full load)
Isolation
Input – Output 4242VDC
Input – Chassis 2121VDC
Output – Chassis 2121VDC
Battery low alarm
adjustment range
Parallel operation
Current sharing to within ±15%
(25% to 100% load)
Hysteresis
Built in output diode protection
Discrete input tied to output
positive turns off rectifier
ALARMS (PBBT-48X-1 (-S) ONLY)
Efficiency
Redundancy
Auto reset
LED (Red) on front panel
Front panel potentiometer
N/O Voltage Free Contact
52-60VDC
3VDC
Configurable to shutdown and latch rectifier
by internal link
LED (Red) on front panel
Front panel potentiometer
N/O Voltage Free Contact
40-47VDC
4VDC
ENVIRONMENTAL SPECIFICATIONS
Cooling
Natural Convection
Operating ambient temp.
-5 to 50°C
Humidity
5% to 90% relative non condensing
Doc. No. PBC9 Rev.C 28-4-11
PBBT Module Series
MECHANICAL SPECIFICATIONS
STANDARDS AND APPROVALS
Safety
ACA TS001, AS/NZS 3260, IEC 60950
CLASS I, Installation Category 2,
Pollution Degree 2
C-Tick/RF emissions
AS/NZS CSIPR11: 2004 Class B
Dimensions
Mounting
Termination Option 1
Termination Option 2
TECHNICAL ILLUSTRATIONS
REAR VIEW OPTION 1
REAR VIEW OPTION 2
18TE
Width
236mm Rack mount
Depth
247mm Stand alone
Depth
3RU
Height
PBBT-48X/PBBT-48X-1
19” Rack mounting
PBBT-48X-S/PBBT-48X-1-S
Stand alone
PBBT-48X/PBBT-48X-1
Rack Mount Rectifier
DIN41612 H15 connector
PBBT-48X-S/PBBT-48X-1-S
Stand Alone Rectifier
Input IEC inlet on near panel
Outputs 2-way Anderson 25A powerpole
11-way screw terminal
BATTERY CHARGER & SYSTEMS
6 0 0 W AT T S T E L E C O M M U N I C AT I O N S
SIDE VIEW
Doc. No. PBC9 Rev.C 28-4-11
Powering Progress – www.powerbox.com.au