C-Series AS-i Master Module User manual AS-i 3.0 specification Name: en_system_manual_3023.pdf | Revision: 1.6 | Revision date: 2015-04-16 Subject to modifications without notice. Generally, this manual refers to products without mentioning existing patents, utility models, or trademarks. The absence of any such references does not indicate that a product is patent-free. © Bihl+Wiedemann GmbH Flosswoerthstr. 41 D-68199 Mannheim C-Series AS-i Master Module Table of contents Table of contents C-Series AS-i Master Module 1 1.1 2 Abbreviations ................................................................................................... 6 General .................................................................................................. 7 2.1 Product information......................................................................................... 7 2.2 Product description and intended use .......................................................... 7 2.3 Conformity statement ...................................................................................... 7 2.4 Certification according to EN ISO 9001:2008 ................................................ 7 2.5 Bihl+Wiedemann hotline ................................................................................. 8 3 Safety..................................................................................................... 9 3.1 Intended use..................................................................................................... 9 3.2 No user-serviceable parts ............................................................................... 9 3.3 General safety information ............................................................................. 9 3.4 Safety Guidelines for Hazardous Locations.................................................. 9 3.4.1 3.5 4 Special Conditions for Hazardous Locations Use in Europe ................................... 10 Disposal .......................................................................................................... 10 Technical Specifications.................................................................... 11 4.1 Data sheet....................................................................................................... 11 4.2 Instructions for cleaning ............................................................................... 12 5 Description .......................................................................................... 13 5.1 LED Indicators................................................................................................ 13 5.2 Connection of the AS-i Master...................................................................... 13 5.2.1 5.3 6 Issue date: 16.4.2015 Symbol catalog ..................................................................................... 6 Connection samples for the AS-i power supply ........................................................ 13 Display and Operating Elements .................................................................. 14 Configuration ...................................................................................... 15 6.1 I/O Data Interpretation ................................................................................... 15 6.2 Output/Input Data Image ............................................................................... 15 6.3 Analog Output/Input Data Image .................................................................. 16 Subject to technical modifications; no responsibility is accepted for the accuracy of this information Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim © Bihl+Wiedemann GmbH phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399 3 C-Series AS-i Master Module Table of contents 6.3.1 6.3.2 7 Execution Control Flags (EC-Flags) ............................................................................ 16 Slave Lists ...................................................................................................................... 16 Operating the AS-i.............................................................................. 17 7.1 Master Start-Up............................................................................................... 17 7.2 Configuration Mode ....................................................................................... 17 7.3 Examples of address assignment ................................................................ 19 7.3.1 7.3.2 Example of automatic address assignment................................................................ 19 Example of manual address assignment .................................................................... 19 7.4 Abbreviations used within the Status List Control ..................................... 20 7.5 Protected Operating Mode ............................................................................ 20 Appendix: Codes indicated by the Display...................................... 21 9 Your opinion is important to us!....................................................... 22 Issue date: 16.4.2015 8 4 Subject to technical modifications; no responsibility is accepted for the accuracy of this information Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim © Bihl+Wiedemann GmbH phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399 C-Series AS-i Master Module EC Declaration of Conformity Issue date: 16.4.2015 EC Declaration of Conformity Subject to technical modifications; no responsibility is accepted for the accuracy of this information Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim © Bihl+Wiedemann GmbH phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399 5 C-Series AS-i Master Module Symbol catalog 1. Symbol catalog Information! This symbol indicates important information. Attention! This symbol warns of a potential failure. Non-compliance may lead to interruptions of the device, the connected peripheral systems, or plant, potentially leading to total malfunctioning. Warning! This symbol warns of an imminent danger. Non-compliance may lead to personal injuries that could be fatal or result in material damages and destruction. 1.1 Abbreviations Information! Issue date: 16.4.2015 Additional information can be found in section <Glossary>. 6 Subject to technical modifications; no responsibility is accepted for the accuracy of this information Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim © Bihl+Wiedemann GmbH phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399 C-Series AS-i Master Module General 2. General 2.1 Product information This system manual applies to the following Bihl+Wiedemann GmbH equipment: C-Series AS-i Master Module BW3023 AS-i master module for compactRIO Tab. 2-1. 2.2 Product description and intended use The BW3023 is an AS-interface master according to specification 3.0. It is also backward compatible because previous specifications (2.0 and 2.1) are supported as well. It enables configuration, control and diagnosis of up to 31 single slaves or 62 A/B slaves via LabVIEW. Fast changing data such as I/O data or execution control flags is directly located in the SPI frame while slower changing data and data which is only needed in special situations is located in the command interface. The LEDs located on the module indicate the current module status, configuration errors or peripheral faults and the activity on AS-i. Diagnostics, which go far beyond the standard diagnostics facilitate the simple detection of the occasionally occurring configuration errors and further irritations towards the AS-i communication. So in case of an error the down time of machines can be minimized or you can initiate preventive maintenance. The BW3023 is suitable for use in Class I, Div. 2, Groups A, B, C, D, T4 hazardous locations; Class I, Zone 2, AEx nA IIC T4, and Ex nA IIC T4 hazardous locations; and nonhazardous locations only. 2.3 Conformity statement The C-Series AS-i Master Module has been developed and manufactured in accordance with the applicable european standards and directives. Information! The corresponding conformity statement can be found at the very beginning of this system manual. 2.4 Certification according to EN ISO 9001:2008 Issue date: 16.4.2015 The manufacturer of the product possesses a certified quality assurance system in accordance with ISO 9001. Information! The current certificate can be viewed in internet: http://www.bihl-wiedemann.de Subject to technical modifications; no responsibility is accepted for the accuracy of this information Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim © Bihl+Wiedemann GmbH phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399 7 C-Series AS-i Master Module General 2.5 Bihl+Wiedemann hotline If problems or faults occur which you cannot rectify yourself and which are not described in this user‘s manual, please contact the Bihl+Wiedemann GmbH service hotline. Phone: +49 (0) 621-33 996-0 (Central) Fax: +49 (0) 621-33 92 22 39 mail: [email protected] web: www.bihl-wiedemann.com Please make a note (see lateral label) of the following details before calling Bihl+Wiedemann GmbH: Device type: Art.-no.: Ident.-no.: Issue date: 16.4.2015 Date of delivery: 8 Subject to technical modifications; no responsibility is accepted for the accuracy of this information Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim © Bihl+Wiedemann GmbH phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399 C-Series AS-i Master Module Safety 3. Safety 3.1 Intended use Warning! This symbol warns of a possible danger. The protection of operating personnel and the system against possible danger is not guaranteed if the control interface unit is not operated in accordance to its intended use. Warning! If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired! 3.2 No user-serviceable parts Warning! No user serviceable parts inside. Do not open! 3.3 General safety information Warning! Safety and correct functioning of the device cannot be guaranteed if any operation other than described in this operation manual is performed. Connecting the equipment and conducting any maintenance work under power must exclusively be performed by appropriately qualified personnel. In case a failure cannot be eliminated, the device must be taken out of operation and inadvertently operation must be prevented. Repair work must be performed by the manufacturer only. Additions or modifications to the equipment are not permitted and will void the warranty. Information! The operator is responsible for the observation of local safety standards. 3.4 Safety Guidelines for Hazardous Locations Issue date: 16.4.2015 The BW3023 is suitable for use in Class I, Division 2, Groups A, B, C, D, T4 hazardous locations; Class I, Zone 2, AEx nA IIC T4, and Ex nA IIC T4 hazardous locations; and nonhazardous locations only. Follow these guidelines if you are installing the BW3023 in a potentially explosive environment. Not following these guidelines may result in serious injury or death. Subject to technical modifications; no responsibility is accepted for the accuracy of this information Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim © Bihl+Wiedemann GmbH phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399 9 C-Series AS-i Master Module Safety Caution: 3.4.1 • Do not disconnect I/O-side wires or connectors unless power has been switched off or the area is known to be nonhazardous. • Do not remove modules unless power has been switched off or the area is known to be nonhazardous. • Substitution of components may impair suitability for Class I, Division 2. • For Zone 2 applications, install the system in an enclosure rated to at least IP54 as defined by IEC 60529 and EN 60529. Special Conditions for Hazardous Locations Use in Europe This equipment has been evaluated as equip- ment under DEMKO Certificate No. 14 ATEX 1413X and IECEx Certificate No. IECEx UL 14.0112X. Each module is marked II 3G and is suitable for use in Zone 2 hazardous locations. If you are using the BW3023 in Gas Group IIC hazardous locations or in ambient temperatures of – 40 °C Ta 70 °C, you must use the device in a chassis that has been evaluated as EEx nA IIC T4, Ex nA IIC T4, or Ex nL IIC T4 equipment. 3.5 Disposal Information! Electronic waste is hazardous waste. Please comply with all local ordinances when disposing this product! Issue date: 16.4.2015 The device does not contain batteries that need to be removed before disposing it. 10 Subject to technical modifications; no responsibility is accepted for the accuracy of this information Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim © Bihl+Wiedemann GmbH phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399 C-Series AS-i Master Module Technical Specifications 4. Technical Specifications 4.1 Data sheet Article No. BW3023: AS-i 3.0 Master for Compact RIO and Labview Function AS-i Scope AS-i I/O data and status information is mapped into the PLC processor‘s I/O data. Diagnostics, which go far beyond the standard diagnostics facilitate the simple detection of the occasionally occurring configuration errors and further irritations towards the AS-i communication. So in case of an error the down time of machines can be minimized or you can initiate preventive maintenance. Article No. BW3023 AS-i Operating current approx. 40 mA out of AS-i approx. 50 mA out of the backplane Operating voltage AS-i voltage 29,5 … 31,6 VDC AS-i cycle time 150 ȝs * (number of slaves + 2) Total power dissipation max. 1,5 W Display LED AS-i powered (green) on: AS-i voltage O.K. LED AS-i active (green) AS-i normal operation active LED prj mode (yellow) configuration mode active LED config error (red) on: at least 1 configured AS-i slave is missing, or at least 1 detected AS-i Slave is not configured, or for at least 1 configured and detected AS-i slave the actual configuration data does not match the nominal configuration data, or the master is in the startup process flashing: peripheral fault Environment Applied standards EN 61000-6-2 : 2005 EN 61000-6-4 : 2007 + A1:2011 IEC 60079-0, 6th edition IEC 60079-15, 4th edition EN 60079-0 : 2012 + A11:2013 EN 60079-15: 2010 ISA 12.12.01 : 2013 UL 60079-0 : 6th Edition UL 60079-15 : 4th Edition CSA C22.2, No 223 : 1987 (R2013) Operating temperature -40 °C … +70 °C Storage temperature -40 °C … +85°C Intended environment for indoor use only Maximum altitude for use 5000 m Maximum relative humidity 90%, non condensing Pollution degree of the intended II environment Protection category acc. EN 60529 Voltage of insulation housing IP20 (only suitable for use in electrical operating rooms/cabinets with IP54 minimum protection rating) AS-i to compactRIO: t 500 V 60 VDC CAT I Ch-to-Earth Isolation Article No. BW3023 420 g Dimensions (W / H / D in mm) 23 / 71 / 89 Issue date: 16.4.2015 Weight Subject to technical modifications; no responsibility is accepted for the accuracy of this information Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim © Bihl+Wiedemann GmbH phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399 11 C-Series AS-i Master Module Technical Specifications Attention! Provision shall be made to prevent the rated voltage being exceeded by the transient disturbance of more than 140% of the peak rated voltage. The system shall be mounted in an ATEX/IECEx certified enclosure with a minimum ingress protection rating of at least IP54 as defined in IEC/EN60529 and used in an environment of not more than pollution degree 2. The enclosure must have a door or cover accessible only by the use of a tool. 4.2 Instructions for cleaning Issue date: 16.4.2015 If you need to clean the module, wipe it with a dry towel. 12 Subject to technical modifications; no responsibility is accepted for the accuracy of this information Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim © Bihl+Wiedemann GmbH phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399 C-Series AS-i Master Module Description 5. Description 5.1 LED Indicators Indicator Color AS-i powered Green Description AS-i Master power Peripheral fault AS-i active Green Normal operation active prj mode Yellow Configuration state config error Red Config error occurred Tab. 5-2. 5.2 Connection of the AS-i Master 5.2.1 Connection samples for the AS-i power supply AS-i Master AS-i Master max. 5 A AS-i - power PELV according to EN + supply 50178 (Protective extra low voltage) - AS-i Slave + - AS-i Slave + - AS-i Slave + max. 8 A AS-i PELV according to EN 50178 - power + supply (Protective extra low voltage) - AS-i Slave + Attention! In the wiring schemes above the current through the AS-i master must not exceed 5 A. 10 2 0,2 ... 2,5 mm 10 0,2 ... 2,5 mm2 AWG 24 ... 12 Torque 0,5 ... 0,6 Nm Issue date: 16.4.2015 Temperature rating for cable 105 oC Use copper conductors only Subject to technical modifications; no responsibility is accepted for the accuracy of this information Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim © Bihl+Wiedemann GmbH phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399 13 C-Series AS-i Master Module Description 5.3 Display and Operating Elements PINs 0/1 AS-i +/AS-i- 2/3 AS-i PWR +/AS-i PWR - 4 FE Connection AS-i circuit Supply voltage AS-i circuit Functional earth LEDs 3 config error Configuration error At least one configured slave is missing, at least one detected slave is not projected or for at least one projected and detected slave the actual configuration data does not match the nominal configuration data. 0 AS-i powered The AS-i circuit is sufficiently powered. 1 AS-i active Normal operation active. 2 prj mode Issue date: 16.4.2015 The AS-i master is in configuration mode. 14 Subject to technical modifications; no responsibility is accepted for the accuracy of this information Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim © Bihl+Wiedemann GmbH phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399 C-Series AS-i Master Module Configuration 6. Configuration 6.1 I/O Data Interpretation Fast changing data is directly located in the SPI frame while slower changing data and data which is only needed in special situations is located in the Command Interface. Index Length [Byte] Direction Carrier to Module Direction Carrier from Module Reserved 0 16 Reserved 16 32 Output Data Image (ODI) Input Data Image (IDI) 48 256 Analogue Output Data Image (AODI) Analogue Input Data Image (AIDI) 304 2 Reserved Execution Control Flags (EC-Flags) 306 2 Reserved Reflected HI-Flags 308 8 Reserved List of active slaves LAS 316 8 Reserved List of detected slaves LDS 324 8 Reserved List of projected slaves LPS 332 8 Reserved List of peripheral faults LPF 340 40 Command Interface Command Interface 380 4 Checksum Checksum = 384 Tab. 6-3. 6.2 Output/Input Data Image ODI, IDI Adresse 215 214 213 212 211 210 29 + 0x00 Slave 3 Slave 2 + 0x02 Slave 7 Slave 6 : + 0x10 27 26 25 24 23 22 21 Slave 1 Slave 0 Slave 5 Slave 4 Slave 1b Slave 0b Slave 29b Slave 28b 20 : Slave 3b Slave 2b : + 0x1E 28 : Slave 31b Slave 30b Issue date: 16.4.2015 Tab. 6-4. Subject to technical modifications; no responsibility is accepted for the accuracy of this information Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim © Bihl+Wiedemann GmbH phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399 15 C-Series AS-i Master Module Configuration 6.3 Analog Output/Input Data Image AODI, AIDI Adresse 215 214 213 212 211 210 29 28 27 26 + 0x00 Slave 0 1st Channel + 0x02 Slave 0 2nd Channel : : + 0x7E Slave 15 4th Channel : : + 0xFE Slave 31 4th Channel 25 24 23 22 21 20 Tab. 6-5. 6.3.1 Execution Control Flags (EC-Flags) EC - Flags Address 215 214 213 212 211 210 29 + 0x0 28 27 26 25 Pok OR APF NA 24 23 22 CA AAv AAs 21 20 S0 Cok Tab. 6-6. Cok: ConfigOk S0: LDS.0 AAs: AutoAddressAssign AAv: AutoAddressAvailable CA: ConfigurationActive NA: NormalOperationActive APF: APF OR: OfflineReady Pok: PeriperyOk 6.3.2 Slave Lists LAS, LDS, LPS, LPF Address 215 214 213 212 211 210 29 28 27 26 25 24 23 22 21 20 + 0x0 s15 s14 s13 s12 s11 s10 s9 s8 s7 s6 s5 s4 s3 s2 s1 s0 + 0x2 s31 s30 s29 s28 s27 s26 s25 s24 s23 s22 s21 s20 s19 s18 s17 s16 + 0x4 s15b s14b s13b s12b s11b s10b s9b s8b s7b s6b s5b s4b s3b s2b s1b s0b + 0x6 s31b s30b s29b s28b s27b s26b s25b s24b s23b s22b s21b s20b s19b s18b s17b s16b Issue date: 16.4.2015 Tab. 6-7. 16 Subject to technical modifications; no responsibility is accepted for the accuracy of this information Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim © Bihl+Wiedemann GmbH phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399 C-Series AS-i Master Module Operating the AS-i 7. Operating the AS-i The LabVIEW API ships with two examples "AS-i RT Basic.lvproj" and "AS-i FPGA Basic.lvproj" referenced throughout the rest of this Manual. The examples can be located by the following steps: 7.1 1. Open LabVIEW if not already opened. 2. 3. 4. In LabVIEW click Help > Find Examples and then search for "AS-i". Open the AS-i RT Basic or AS-i FPGA Basic project. For addition help, click Help > Bihl-Wiedemann in LabVIEW to open the user manual. Master Start-Up Connect the AS-i module as described in section <Connection samples for the AS-i power supply> and plug the AS-i module into one slot of your powered cRIO chassis. All LEDs of the module should be Off. Then if you run the example “BW-3023 AS-i Commissioning.vi” as described in section <Configuration Mode> some LED’s should turn ON, depending on the state of master. 1. If the AS-i network is not sufficiently powered. AS-i powered AS-i active prj mode config error Off Off On If configuration mode is active, LED is ’on’. Otherwise ’off’. Tab. 7-8. 2. If the AS-i network is sufficiently powered. AS-i powered AS-i active prj mode config error On On If there is config error, LED is ’on’. Otherwise, ’off’. If configuration mode is active, LED is ’on’. Otherwise ’off’. Tab. 7-9. 7.2 On the VI Frontpanel press the the “Operation Mode” switch and notice your modules being marked in the address table, then press the “Store Actual Configuration” button, to turn OFF the Config Error LED. Configuration Mode All slaves, except the slave with zero address, that are members of the list of detected slaves (LDS) shall be automatically detected and activated in the above mentioned way according to AS-i specification. Issue date: 16.4.2015 Configuration mode is demonstrated in both shipping examples referenced in section <Examples of address assignment>. The AS-i C-Series module can be placed into configuration mode by completing the following steps: 1. Connect the AS-i C-Series module as described in section <Connection of the AS-i Master>. 2. Open the “AS-i RT Basic.lvproj” example. Subject to technical modifications; no responsibility is accepted for the accuracy of this information Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim © Bihl+Wiedemann GmbH phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399 17 C-Series AS-i Master Module Operating the AS-i 3. 4. Verify that your cRIO is connected properly by right clicking the target within your project and going to "Connect" Open the front panel of the "BW3023 AS-i Commissioning.vi" Assigning an AS-i Address in the Configuration Mode Assigning a Slave Address Connect a new slave in the AS-i network, the state of this slave is showed in the “Slave List” indicator. 2. 3. 4. 5. Select the devices old address within the “Old Address” control. Select the new address within the “New Address” control. Click the button “Change Slave Address”. If the indicator “Result Code” is 0, address assignment was successful. Issue date: 16.4.2015 1. 18 Subject to technical modifications; no responsibility is accepted for the accuracy of this information Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim © Bihl+Wiedemann GmbH phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399 C-Series AS-i Master Module Operating the AS-i Programming the Address in Case of Configuration Errors 1. Click the button “Store Actual Configuration” to store the current AS-i network configuration for all connected slaves, then repeat step 2 – 5 from above. Erasing the Slave Address 1. Remove a slave from the AS-i network 2. The status of this slave in “Slave List” indicator should change to P (Projected Only) Click the button “Store Actual Configuration” to delete the address from the module. 3. Automatic Address Assignment ( shall be processed only if): 1. the Master module execution control mode is the protected mode, 2. 3. the "Auto_Address_Enable” mode is ON the "Auto_Address_Assign" mode is set, and If one and only one configured slave is not detected. 7.3 Examples of address assignment 7.3.1 Example of automatic address assignment Select an existing Slave (e.g Slave1) within the “Old Address” control. 2. 3. Select Slave0 within the “New Address” control. Click the button “Change Slave Address”. The status List should change like this. 4. 5. 6. 7. Remove the slave from the AS-i network. Click button “Operation Mode” to change to protected mode Connect this slave back to the AS-i network Address 1 is assigned to this slave automatically. Example of manual address assignment 1. Connect a slave to the AS-i network. 2. If the slave address is zero, the status list should look like this. Issue date: 16.4.2015 7.3.2 1. Subject to technical modifications; no responsibility is accepted for the accuracy of this information Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim © Bihl+Wiedemann GmbH phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399 19 C-Series AS-i Master Module Operating the AS-i 3. 4. 5. 6. 7.4 7.5 Select Slave0 within the "Old Address" control. Select the new address (e.g. Slave2) within the "New Address" control. Click the button "Change Slave Address". If the indicator "Result Code" is 0, address assignment was successful. Abbreviations used within the Status List Control X (O.K.) The configuration data for the detected AS-i slave matches the stored configuration data. D (Detected Only) An AS-i slave is detected at this address, but it was not stored before. P (Projected Only) An AS-i slave was stored at this address, but it was not detected. C (Type Conflict) The configuration data for the detected AS-i slave does not match the stored configuration data. The actual exiting configuration of the connected AS-i slave is displayed. F (Periph. Fault) The AS-i slave has a peripheral error. A (Duplicate Addr.) Two AS-i slaves use the same address. Protected Operating Mode Only those slaves shall be activated which are both members of the list of detected slaves (LDS) and members of the list of projected slaves (LPS), and whose configuration data image (CDI) value equals the permanent configuration data (PCD) value for that specific slave. Follow steps 1-5 of section <Configuration Mode> to bring the AS-i network to Configuration mode 2. Click the "Operation Mode" control to change to "Protected Mode" Issue date: 16.4.2015 1. 20 Subject to technical modifications; no responsibility is accepted for the accuracy of this information Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim © Bihl+Wiedemann GmbH phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399 C-Series AS-i Master Module Appendix: Codes indicated by the Display 8. Appendix: Codes indicated by the Display Bihl+Wiedemann AS-i error codes and warnings are in the range: Range +/389000 to 389099. Errors explanations can be found with the NI LabVIEW environment by clicking Help "Explain Error". A list of error codes is shown below: Name Description -389000 asiErrorAnalogInvalidAddress Slave address for the analog read or write is invalid. Solution: Specify an address in the range of 0 to 31. -389001 asiErrorAnalogInvalidDataLength The data length of four 16-bit analog channel is out of range. Solution: Make sure the data length is within 8 bytes. -389002 asiErrorAnalogOperationTimeout Analog read or analog write timed out. Solution: Increase timeout and ensure "AS-i Commit.vi" has been called. -389003 asiErrorCommandInval- Command request size is out of range. Solution: idRequestLength Make sure the length of command request is smaller than 39 bytes. -389004 asiErrorCommandTimeout Timeout occurred waiting for the command response. Solution: Increase timeout and check hardware connection. -389005 asiErrorDigitalInvalidAddress Slave address for digital read or digital write is invalid. Solution: Specify an address which is in the range of 0 to 63. -389006 asiErrorDigitalInvalidData Digital data value is invalid. Solution: Specify a value in the range of 0 to 15. -389007 asiErrorDigitalInvalidDataImageLength Digital data image size is out of range. Solution: Make sure the length of digital data image is smaller than 33 bytes. -389008 asiErrorSpiFrameData- CRC check failed between backplane and modFault ule. SPI communication may be corrupted by electrical noise. Solution: Reduce noise and contact National Instruments if the error persists. Issue date: 16.4.2015 Code Subject to technical modifications; no responsibility is accepted for the accuracy of this information Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim © Bihl+Wiedemann GmbH phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399 21 C-Series AS-i Master Module Your opinion is important to us! 9. Your opinion is important to us! Please give us an opportunity to hear your suggestions, wishes and criticisms regarding this Manual. We read every note or comment, no matter how small, and incorporate them into the documentation whenever possible. Fill out the form on the following page and fax it to us or send your remarks, suggestions for improvement etc. to the following address: Bihl+Wiedemann GmbH Technical Support Floßwörthstr. 41 D - 68199 Mannheim Germany Phone: +49 (0) 621-33 99 6-0 Fax: +49 (0) 621-33 9 22 39 eMail: [email protected] Fax reply Bihl+Wiedemann GmbH Date: Technical Support Fax No. +49 (0) 621-33 9 22 39 eMail: [email protected] From: Firm Name: Street Position: City Tel.: Dept. Fax: eMail: Which manual are you using? Title Publication date: My opinion of the manual Design Yes Partly No Is the table of contents clearly laid out? Are the illustrations/graphics comprehensible/meaningful? Are the text explanations for the illustrations sufficient? Issue date: 16.4.2015 Does the quality of the images meet your expectations? Does the pagination encourage rapid finding of information? 22 Subject to technical modifications; no responsibility is accepted for the accuracy of this information Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim © Bihl+Wiedemann GmbH phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399 C-Series AS-i Master Module Your opinion is important to us! Yes Content Partly No Are the formulations/technical terms understandable? Are the examples relevant? Is the Manual easy to handle? Is there important information missing? If yes, explain. Issue date: 16.4.2015 Comments: Subject to technical modifications; no responsibility is accepted for the accuracy of this information Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim © Bihl+Wiedemann GmbH phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399 23