Bulletin 140U Molded Case Circuit Breakers Overview Bulletin 140U Molded Case Circuit Breakers • • • • • • Product Selection 125 A H-Frame .............. 41 250 A J-Frame ............... 45 400 A K-Frame .............. 49 600 A Q-Frame .............. 53 800 A M-Frame .............. 57 1200 A N-Frame ............ 61 15…1200 A Molded Case Circuit Breakers Thermal-Magnetic 15…800 A Electronic 70…1200 A -LS — Long Time/Short Time -LSI — Long Time/Short Time/High Instantaneous -LSG — Long Time/Short Time/Ground Fault -LSIG — Long Time/Short Time/High Instantaneous/Ground Fault Molded Case Switches 125…1200 A Factory- or field-installed accessories Flex cable operating mechanisms Rotary variable-depth operating mechanisms High interrupting ratings in compact dimensions Globally rated and approved product line for worldwide application Conformity to Standards UL 489 CSA 22.2, No. 5 IEC 60947-2 Approvals UL Listed CSA Certified CE KEMA-KEUR Product Line Overview Frame Reference Max. Current In Current Range Thermal Magnetic Electronic: LS LSI LSG LSIG Interrupting Ratings: 380…415V (Icu) 480V 600V 690V (Icu) Molded Case Switches Flex Cable Operators Rotary Operators Internal Control Modules (Field installed) Standards Compliance UL 498 CSA 22.2, No. 5 IEC 60947-2 CE KEMA-KEUR 38 H-Frame 125 A 15…125 A ✓ — — — — — 25 25 18 3 40 35 22 4 ✓ ✓ ✓ 70 65 25 6 J-Frame 250 A 70…250 A ✓ ✓ ✓ ✓ ✓ ✓ 25 25 18 6 40 35 18 6 ✓ ✓ ✓ 70 65 25 7 K-Frame 400 A 100…400 A ✓ ✓ ✓ ✓ ✓ ✓ 40 35 25 10 65 65 35 13 ✓ ✓ ✓ 100 100 50 18 Q-Frame 600 A 300…600 A ✓ ✓ ✓ ✓ ✓ ✓ 45 35 25 20 70 65 35 25 M-Frame 800 A 300…800 A ✓ ✓ ✓ ✓ ✓ ✓ 50 50 25 20 70 65 35 25 N-Frame 1200 A 600…1200 A — ✓ ✓ ✓ ✓ ✓ 50 50 25 20 ✓ ✓ ✓ ✓ ✓ ✓ 70 65 35 25 ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ — — ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ 100 100 50 30 Bulletin 140U Molded Case Circuit Breakers Catalog Number Explanation Examples given in this section are for reference purposes. This basic explanation should not be used for product selection; not all combinations will produce a valid cat. no. Refer to the tables on the following pages for descriptions of options. Complete Circuit Breaker Assemblies 140U - H 6 C 3 – C50 – H ⊗ Bulletin No. Voltage Code Code Description 140U Molded Case Circuit Breaker See the following pages for voltage code descriptions: Frame/Rating H-Frame Page 41 J-Frame Page 45 K-Frame Page 49 Page 53 Code Description Q-Frame H 125 A M-Frame Page 57 J 250 A N-Frame Page 61 K 400 A Q 600 A M 800 A N 1200 A Internal Control Modules Code Description A 1 Auxiliary contact B 2 Auxiliary contacts Interrupting Rating/Breaking Capacity (based on Ic at 480V) D 1 Alarm contact Code Description F 1 Auxiliary + 1 Alarm contact 2 20…29 kA G Undervoltage release only 3 30…39 kA P Shunt trip only Control Module Combinations 5 50…59 kA 6 60…69 kA Code Description 8 80…89 kA H 1 Auxiliary contact + undervoltage release 0 ≥100 kA J 2 Auxiliary contacts + undervoltage release L 1 Auxiliary + 1 Alarm contact + undervoltage release N 1 Alarm contact + undervoltage release Protection Type Q 1 Auxiliary contact + shunt trip R 2 Auxiliary contacts + shunt trip Code Description C Fixed Thermal/Fixed Magnetic T 1 Auxiliary + 1 Alarm contact + shunt trip D Fixed Thermal/Adjust Magnetic V 1 Alarm contact + shunt trip E Adjust Thermal/Fixed Magnetic F Adjust Thermal/Adjust Magnetic G Electronic (LSG) — Long, short, ground fault H Electronic (LSI) — Long, short, high instant I Electronic (LSIG) — Long, short, high instant, ground fault Code L Electronic (LS) — Long and Short time C 10 rr. A S Molded Case Switch (Isolator) D 100 rr0 A E 1000 rr00 A Current Range Description Poles Code Description 3 3 poles 39 Bulletin 140U Molded Case Circuit Breakers Catalog Number Explanation Examples given in this section are for reference purposes. This basic explanation should not be used for product selection; not all combinations will produce a valid cat. no. Refer to the tables on the following pages for descriptions of options. Frames 140U - J 3 X 3 Bulletin No. Poles Code Description Code Description 140U Molded Case Circuit Breaker 3 3 poles Frame/Rating Interrupting Rating/Breaking Capacity (based on Ic at 480V) Code Description J 250 A Code Description K 400 A 2 20…29 kA L 600 A 3 30…39 kA M 800 A 5 50…59 kA 6 60…69 kA 8 80…89 kA 0 ≥100 kA Protection Type Code Description X Frame Only Trip Units 140U - J T F 3 – C50 Current Range Bulletin No. Code 140U Description Code Molded Case Circuit Breaker C Description 10 rr. A D 100 rr0 A E 1000 rr00 A Frame/Rating Code Description J 250 A K 400 A Q 600 A M 800 A Poles Interrupting Rating/Breaking Capacity (based on Ic at 480V) Code Description T Trip Unit Code Description 3 3 poles Protection Type 40 Code Description C Fixed Thermal/Fixed Magnetic D Fixed Thermal/Adjust Magnetic E Adjust Thermal/Fixed Magnetic F Adjust Thermal/Adjust Magnetic G Electronic (LSG) — Long, short, ground fault H Electronic (LSI) — Long, short, high instant I Electronic (LSIG) — Long, short, high instant, ground fault L Electronic (LS) — Long and Short time S Molded Case Switch (isolator) Bulletin 140U Molded Case Circuit Breakers Product Selection — 125 A, H-Frame • • • • • UL 489 CSA 22.2, No. 5 IEC 60947-2 CE KEMA-KEUR • Terminal box lugs provided as standard 25/25 kA, Thermal-Magnetic, Fixed Thermal-Fixed Magnetic Rated Current In [A] Thermal Trip [A] Ir = In (Fixed) Magnetic Trip [A] Im = 10 x In 15 20 25 30 35 40 45 50 60 70 80 90 100 110 125 15 20 25 30 35 40 45 50 60 70 80 90 100 110 125 500 500 500 500 500 500 500 500 600 700 800 900 1000 1100 1250 220…240V 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 Breaking Capacity (50 Hz) Icu /Ics [kA] 380…415V 500V 25 25 22 17 25 25 22 17 25 25 22 17 25 25 22 17 25 25 22 17 25 25 22 17 25 25 22 17 25 25 22 17 25 25 22 17 25 25 22 17 25 25 22 17 25 25 22 17 25 25 22 17 25 25 22 17 25 25 22 17 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Interrupting Rating (60 Hz) [kA] 240V 480V 600/347V 35 25 18 35 25 18 35 25 18 35 25 18 35 25 18 35 25 18 35 25 18 35 25 18 35 25 18 35 25 18 35 25 18 35 25 18 35 25 18 35 25 18 35 25 18 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Interrupting Rating (60 Hz) [kA] 240V 480V 600/347V 85 35 22 85 35 22 85 35 22 85 35 22 85 35 22 85 35 22 85 35 22 85 35 22 85 35 22 85 35 22 85 35 22 85 35 22 85 35 22 85 35 22 85 35 22 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Interrupting Rating (60 Hz) [kA] 240V 480V 600/347V 100 65 25 100 65 25 100 65 25 100 65 25 100 65 25 100 65 25 100 65 25 100 65 25 100 65 25 100 65 25 100 65 25 100 65 25 100 65 25 100 65 25 100 65 25 3 Interrupting Rating (60 Hz) [kA] 240V 480V 600/347V 100 65 25 690V 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Cat. No. 140U-H2C3-C15 140U-H2C3-C20 140U-H2C3-C25 140U-H2C3-C30 140U-H2C3-C35 140U-H2C3-C40 140U-H2C3-C45 140U-H2C3-C50 140U-H2C3-C60 140U-H2C3-C70 140U-H2C3-C80 140U-H2C3-C90 140U-H2C3-D10 140U-H2C3-D11 140U-H2C3-D12 40/35 kA, Thermal-Magnetic, Fixed Thermal-Fixed Magnetic Rated Current In [A] Thermal Trip [A] Ir = In (Fixed) Magnetic Trip [A] Im = 10 x In 15 20 25 30 35 40 45 50 60 70 80 90 100 110 125 15 20 25 30 35 40 45 50 60 70 80 90 100 110 125 500 500 500 500 500 500 500 500 600 700 800 900 1000 1100 1250 220…240V 85 43 85 43 85 43 85 43 85 43 85 43 85 43 85 43 85 43 85 43 85 43 85 43 85 43 85 43 85 43 Breaking Capacity (50 Hz) Icu /Ics [kA] 380…415V 500V 40 30 25 18 40 30 25 18 40 30 25 18 40 30 25 18 40 30 25 18 40 30 25 18 40 30 25 18 40 30 25 18 40 30 25 18 40 30 25 18 40 30 25 18 40 30 25 18 40 30 25 18 40 30 25 18 40 30 25 18 690V 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 Cat. No. 140U-H3C3-C15 140U-H3C3-C20 140U-H3C3-C25 140U-H3C3-C30 140U-H3C3-C35 140U-H3C3-C40 140U-H3C3-C45 140U-H3C3-C50 140U-H3C3-C60 140U-H3C3-C70 140U-H3C3-C80 140U-H3C3-C90 140U-H3C3-D10 140U-H3C3-D11 140U-H3C3-D12 70/65 kA, Thermal-Magnetic, Fixed Thermal-Fixed Magnetic l Rated Current In [A] Thermal Trip [A] Ir = In (Fixed) Magnetic Trip [A] Im = 10 x In 15 20 25 30 35 40 45 50 60 70 80 90 100 110 125 15 20 25 30 35 40 45 50 60 70 80 90 100 110 125 500 500 500 500 500 500 500 500 600 700 800 900 1000 1100 1250 220…240V 100 50 100 50 100 50 100 50 100 50 100 50 100 50 100 50 100 50 100 50 100 50 100 50 100 50 100 50 100 50 Breaking Capacity (50 Hz) Icu /Ics [kA] 380…415V 500V 70 35 35 18 70 35 35 18 70 35 35 18 70 35 35 18 70 35 35 18 70 35 35 18 70 35 35 18 70 35 35 18 70 35 35 18 70 35 35 18 70 35 35 18 70 35 35 18 70 35 35 18 70 35 35 18 70 35 35 18 220…240V 100 50 Breaking Capacity (50 Hz) Icu /Ics [kA] 380…415V 500V 70 35 35 18 690V 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 Cat. No. 140U-H6C3-C15 140U-H6C3-C20 140U-H6C3-C25 140U-H6C3-C30 140U-H6C3-C35 140U-H6C3-C40 140U-H6C3-C45 140U-H6C3-C50 140U-H6C3-C60 140U-H6C3-C70 140U-H6C3-C80 140U-H6C3-C90 140U-H6C3-D10 140U-H6C3-D11 140U-H6C3-D12 Molded Case Switch — UL 1087 Rated Current In [A] Thermal Trip Ir = In [A] Magnetic Trip [A] Im = 10 x In 125 None 1250 690V 6 Cat. No. 140U-H6S3-D12 41 Bulletin 140U Molded Case Circuit Breakers Accessories — 125 A, H-FrameInternal Control Modules — Field Installed Description Mounting Location Cat. No. Diagram (1) 1a-1b ON OFF Auxiliary Contact (AX) • Electrically indicates “ON/ OFF” status of breakers AX 1a 1b 1c 1c (2) 1a-1b 140U-H-EA1 TRIP 1a 1a 1b 1b 1c 140U-H-EA2 I> Right side only Alarm Contact (AL) • Electrically indicates when the breaker is in the “TRIPPED” state ON OFF (1) 1M (make)1B (break) M B AL TRIP M B 140U-H-ER1 M B I> 1c 1c 1c Right side only ON OFF Auxiliary/Alarm Contact (AX/AL) (1) 1a-1b Combination (1) 1M (make)• Combination of auxiliary 1B (break) contact and alarm contact AX AL 1b 1c 1a 1b M B 1c TRIP 1a 1b M B 1c 1a M B 140U-H-EA1R1 I> 1c 1c 1c Right side only 12…60V, 50/60/DC Shunt Trip (SNT) • Provides remote tripping of the circuit breaker • Undervoltage trip not available when shunt trip is used 110…240V, 50/60/DC Undervoltage Release (UVT) • Automatically trips breaker when voltage falls between preset value, 35…70% • Shunt trip is not available when undervoltage release is used 24V 50/60/DC 110…127V, 50/60 208…240V, 50/60 380…500V, 50/60 525…600V, 50/60 380…600V, 50/60 140U-H-SNJ S1 SNT 140U-H-SND S2 I> 140U-H-SNB Left side only 140U-H-UJ UVT U1 U> I> 140U-H-UD 140U-H-UA U2 140U-H-UB Left side only 140U-H-UC Internal Control Modules — Factory Installed Left side only Mounting Location (1) Shunt Trip (SNT) or (1) Undervoltage Release (UVT) Auxiliary and Alarm Contacts (1) AX (2) AX (1) AL (1) AX + (1) AL Suffix -A -B -D -F Shunt Trip Suffix Combinations (1) SNT only - P⊗ (1) AX + (1) SNT - Q⊗ (2) AX + (1) SNT - R⊗ (1) AX + (1) AL + (1) SNT - T⊗ - V⊗ (1) AL + (1) SNT ⊗ Standard Voltage Suffix Codes ➊ Voltage [V] 12…60 110…240 380…600 AC, J D B 50/60 Hz J D — DC ➊ For additional voltages, consult your local Allen-Bradley distributor. 42 Right side only (1) Auxiliary contact (AX) or (2) Auxiliary contacts (AX) or (1) Alarm contact (AL) or (1) Alarm contact (AL) + Auxiliary contact (AX) Undervoltage Release Suffix Combinations (1) UVT only - G⊗ (1) AX + (1) UVT - H⊗ (2) AX + (1) UVT - J⊗ (1) AX + (1) AL + (1) UVT - L⊗ (1) AL + (1) UVT - N⊗ ⊗ Standard Voltage Suffix Codes ➊ Voltage [V] 24 110…127 208…240 380…500 525…600 AC, J D A B C 50/60 Hz DC J — — — — Bulletin 140U Molded Case Circuit Breakers Accessories — 125 A, H-Frame, Continued External Accessories Description Cat. No. 0.25 in. (6.4 mm) Diameter Cable Entry Terminal End Cover 140U-H-TC2 Qty: 1 140U-H-TC4 0.41 in. (10.4 mm) Diameter Cable Entry Terminal Shields IP20 Ingress Protection Non-Metallic — Type 1/3/12/4/4X Flange-Mount Operating Handle Qty: 1 140U-H-TS 3 ft. (0.9 m) Cable 140U-H-FCX03 4 ft. (1.3 m) Cable 140U-H-FCX04 6 ft. (1.8 m) Cable 140U-H-FCX06 10 ft. (3.0 m) Cable 140U-H-FCX10 3 ft. (0.9 m) Cable 140U-H-FCS03 4 ft. (1.3 m) Cable 140U-H-FCS04 Flex-Cable Operating Mechanism Stainless Steel — Type 4/4X Flange-Mount Operating Handle Rotary, Variable-Depth Operating Mechanism Rotary, Direct Couple Operating Mechanism 6 ft. (1.8 m) Cable 140U-H-FCS06 10 ft. (3.0 m) Cable 140U-H-FCS10 Black Handle 140U-H-RM12B Red/Yellow Handle 140U-H-RM12R Black Handle 140U-H-RCB Red/Yellow Handle 140U-H-RCR Rotary Handle — Type 1/12 12 in. (305 mm) operating rod Rotary Handle — Type 1 Breaker Mounted End Cap Kit Provides 3-phase connections for terminal or bolt-on connections Metric Hardware provided Qty: 1 140U-H-ECM Phase Barriers Provides additional phase clearance when special connections are required Qty: 2 140U-H-PB Padlock Kit Padlocking Hasp Lock-OFF only Qty: 1 140U-H-PL DIN Rail Adapter Allows H-frame MCCB to mount to 35 mm DIN Rail Qty: 1 140U-H-DRA 43 Bulletin 140U Molded Case Circuit Breakers Approximate Dimensions — 125 A, H-Frame Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes. 4 Ð .17 (4.32) x .19 (4.83) Dia. Slot for #6 Mounting Screws Line End .50 .50 (12.70) (12.70) .45 (11.43) .78 (19.81) .09 (2.29) 6 Ð .35 (8.90) Dia. .56 (14.22) .58 (14.73) .22 (5.59) Attachment Leads Side Exit Point 5.50 (139.70) Push to Trip Button 3.81 (96.78) 3.03 (76.96) 1.73 (43.94) Handle R2.13 .17 (4.32) .15 (3.81) 1.38 (35.05) E .17 (4.32) D A 2.18 (55.37) .22 (5.59) B 1.08 (27.43) .72 (18.29) .57 (14.48) .55 (13.97) .09 (2.29) .20 (5.08) Dia. Thru Conductors 1.00 (25.40) 1.00 (25.40) C L 1.21 (30.73) .77 (19.56) 1.42 (36.07) .03 (0.76) 2.77 (70.36) 2.93 2.99 (74.42) (75.95) C 3.00 (76.20) 1.50 (38.10) .94 (23.88) Breaker Status .44 (11.18) .47 (11.94) Attachment Leads Rear Exit Point 1.44 (36.58) .67 (17.02) 44 Dimension A B C D E On 2.71 (68.83) 2.53 (64.26) 3.46 (87.88) 2.83 (71.88) 2.75 (69.85) Off 1.54 (39.12) 1.62 (41.15) 3.46 (87.88) 1.66 (42.16) 1.84 (46.74) Tripped 2.33 (59.18) 2.23 (56.64) 3.54 (89.92) 2.46 (67.48) 2.45 (62.23) Reset 1.39 (35.31) 1.49 (37.85) 3.42 (86.87) 1.52 (38.61) 1.70 (43.18) Bulletin 140U Molded Case Circuit Breakers Product Selection — 250 A, J-Frame • • • • • UL 489 CSA 22.2, No. 5 IEC 60947-2 CE KEMA-KEUR (Pending) • Terminal box lugs must be ordered separately. See page 47 Breaker Frames Rated Current In [A] 250 Breaking Capacity (50 Hz) Icu /Ics [kA] 380…415V 500V 25 25 20 12 40 40 35 20 70 70 42 20 220…240V 65 65 85 85 100 100 Interrupting Rating (60 Hz) [kA] 690V 6 6 7 240V 65 85 100 3 3 3 480V 25 35 65 600V 18 18 25 Cat. No. 140U-J2X3 140U-J3X3 140U-J6X3 Trip Units Rated Current In [A] 90 100 125 150 175 200 225 250 Thermal-Magnetic Adjustment Range [A] Thermal Trip [A] Magnetic Trip Ir = In (Fixed) Im = 5…10 x In 90 450…900 100 500…1000 125 600…1250 150 750…1500 175 875…1750 200 1000…2000 225 1125…2250 250 1250…2500 Cat. No. Rated Current In [A] 140U-JTD3-C90 140U-JTD3-D10 140U-JTD3-D12 140U-JTD3-D15 140U-JTD3-D17 140U-JTD3-D20 140U-JTD3-D22 140U-JTD3-D25 50 50 100 100 160 160 250 250 Electronic Adjustment Range [A] Thermal Trip Magnetic Trip Ir = 0.4…1.0 x In Im = 2…14 x In 20…50 40…700 20…50 40…700 40…100 80…1400 40…100 80…1400 63…160 126…2240 63…160 126…2240 100…250 200…3500 100…250 200…3500 Protection Type Cat. No. LS LSI LS LSI LS LSI LS LSI 140U-JTL3-C50 140U-JTH3-C50 140U-JTL3-D10 140U-JTH3-D10 140U-JTL3-D16 140U-JTH3-D16 140U-JTL3-D25 140U-JTH3-D25 Assembled Circuit Breakers, Thermal-Magnetic Trip Units 400/480V [kA] 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 Rated Current In [A] 90 100 125 150 175 200 225 250 Cat. No. 140U-J2D3-C90 140U-J2D3-D10 140U-J2D3-D12 140U-J2D3-D15 140U-J2D3-D17 140U-J2D3-D20 140U-J2D3-D22 140U-J2D3-D25 400/480V [kA] 40/35 40/35 40/35 40/35 40/35 40/35 40/35 40/35 Cat. No. 140U-J3D3-C90 140U-J3D3-D10 140U-J3D3-D12 140U-J3D3-D15 140U-J3D3-D17 140U-J3D3-D20 140U-J3D3-D22 140U-J3D3-D25 400/480V [kA] 70/65 70/65 70/65 70/65 70/65 70/65 70/65 70/65 Cat. No. 140U-J6D3-C90 140U-J6D3-D10 140U-J6D3-D12 140U-J6D3-D15 140U-J6D3-D17 140U-J6D3-D20 140U-J6D3-D22 140U-J6D3-D25 Assembled Circuit Breakers, Electronic Trip Units Rated Current In [A] 50 50 100 100 160 160 250 250 Protection Type LS LSI LS LSI LS LSI LS LSI 400/480V [kA] 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 Cat. No. 140U-J2L3-C50 140U-J2H3-C50 140U-J2L3-D10 140U-J2H3-D10 140U-J2L3-D16 140U-J2H3-D16 140U-J2L3-D25 140U-J2H3-D25 400/480V [kA] 40/35 40/35 40/35 40/35 40/35 40/35 40/35 40/35 Cat. No. 140U-J3L3-C50 140U-J3H3-C50 140U-J3L3-D10 140U-J3H3-D10 140U-J3L3-D16 140U-J3H3-D16 140U-J3L3-D25 140U-J3H3-D25 400/480V [kA] 70/65 70/65 70/65 70/65 70/65 70/65 70/65 70/65 Cat. No. 140U-J6L3-C50 140U-J6H3-C50 140U-J6L3-D10 140U-J6H3-D10 140U-J6L3-D16 140U-J6H3-D16 140U-J6L3-D25 140U-J6H3-D25 Molded Case Switch — UL 1087 Rated Current In [A] Thermal Trip Ir = In [A] Magnetic Trip [A] Im = 10 x In 250 None 2500 220…240V 100 100 Breaking Capacity (50 Hz) Icu /Ics [kA] 380…415V 500V 70 70 42 20 Interrupting Rating (60 Hz) [kA] 690V 7 3 240V 100 480V 65 600V 25 Cat. No. 140U-J6S3-D25 45 Bulletin 140U Molded Case Circuit Breakers Accessories — 250 A, J-Frame Internal Control Modules — Field Installed Description Mounting Location Cat. No. Diagram (1) 1a-1b ON OFF Auxiliary Contact (AX) • Electrically indicates “ON/ OFF” status of breakers AX 1a 1b 1c 1c (2) 1a-1b 140U-H-EA1 TRIP 1a 1a 1b 1b 1c 140U-H-EA2 I> Left AND Right side Alarm Contact (AL) • Electrically indicates when the breaker is in the “TRIPPED” state ON OFF (1) 1M (make)1B (break) M B AL TRIP M B 140U-J-ER1 M B I> 1c 1c 1c Right side only ON OFF Auxiliary/Alarm Contact (AX/AL) (1) 1a-1b Combination (1) 1M (make)• Combination of auxiliary 1B (break) contact and alarm contact AX AL 1b 1c 1a 1b M B 1c TRIP 1a 1b M B 1c 1a M B 140U-J-EA1R1 I> 1c 1c 1c Right side only Shunt Trip (SNT) • Provides remote tripping of the circuit breaker • Undervoltage trip not available when shunt trip is used 12…60V, 50/60/DC 140U-H-SNJ SNT 110…240V, 50/ 60/DC 380…600V, 50/ 60 24V 50/60/DC Undervoltage Release (UVT) 110…127V, 50/ • Automatically trips breaker 60 when voltage falls between 208…240V, 50/ preset value, 35…70% 60 • Shunt trip is not available 380…500V, 50/ when undervoltage release is 60 used 525…600V, 50/ 60 S1 140U-H-SND S2 I> 140U-H-SNB Left side only 140U-H-UJ 140U-H-UD UVT U1 U> I> U2 140U-H-UA 140U-H-UB Left side only 140U-H-UC Internal Control Modules — Factory Installed Left side only Mounting Location (1) Shunt Trip (SNT) or (1) Undervoltage Release (UVT) Auxiliary and Alarm Contacts Suffix (1) AX (2) AX (1) AL (1) AX + (1) AL -A -B -D -F Shunt Trip Suffix Combinations (1) SNT only - P⊗ (1) AX + (1) SNT - Q⊗ (2) AX + (1) SNT - R⊗ (1) AX + (1) AL + (1) SNT - T⊗ (1) AL + (1) SNT - V⊗ ⊗ Standard Voltage Suffix Codes ➊ Voltage [V] 12…60 110…240 380…600 AC, J D B 50/60 Hz DC J D — ➊ For additional voltages, consult your local Allen-Bradley distributor. 46 Right side only (1) Auxiliary contact (AX) or (2) Auxiliary contacts (AX) or (1) Alarm contact (AL) or (1) Alarm contact (AL) + Auxiliary contact (AX) Undervoltage Release Suffix Combinations (1) UVT only - G⊗ (1) AX + (1) UVT - H⊗ (2) AX + (1) UVT - J⊗ (1) AX + (1) AL + (1) UVT - L⊗ (1) AL + (1) UVT - N⊗ ⊗ Standard Voltage Suffix Codes ➊ Voltage [V] 24 110…127 208…240 380…500 525…600 AC, J D A B C 50/60 Hz DC J — — — — Bulletin 140U Molded Case Circuit Breakers Accessories — 250 A, J-Frame, Continued External Accessories Description Terminal Shields IP20 Ingress Protection Non-Metallic — Type 1/3/12/4/4X Flange-Mount Operating Handle Cat. No. Qty — 2 140U-J-TS 3 ft. (0.9 m) Cable 140U-J-FCX03 4 ft. (1.3 m) Cable 140U-J-FCX04 6 ft. (1.8 m) Cable 140U-J-FCX06 10 ft. (3.0 m) Cable 140U-J-FCX10 3 ft. (0.9 m) Cable 140U-J-FCS03 4 ft. (1.3 m) Cable 140U-J-FCS04 6 ft. (1.8 m) Cable 140U-J-FCS06 10 ft. (3.0 m) Cable 140U-J-FCS10 Black Handle 140U-J-RM12B Red/Yellow Handle 140U-J-RM12R Black Handle 140U-J-RCB Red/Yellow Handle 140U-J-RCR Flex-Cable Operating Mechanism Stainless Steel — Type 4/4X Flange-Mount Operating Handle Rotary, Variable-Depth Operating Mechanism Rotary, Direct Couple Operating Mechanism Rotary Handle — Type 1/12 12 in. (305 mm) operating rod Rotary Handle — Type 1 Breaker Mounted Phase Barriers Provides additional phase clearance when special connections are required Qty: 2 140U-J-PB Padlock Kit Padlocking Hasp Lock-OFF only Qty: 1 140U-J-PL Stainless Steel Box Lugs Copper wire only (1) 4/0…350MCM Qty: 1 140U-J-TLS1 Aluminum Lugs Aluminum or copper wire (1) 4/0…350MCM (1) 25…185 mm2 Qty: 1 140U-J-TLA1 Provides 3-phase connections for terminal or bolt-on connections Metric Hardware Qty:1 140U-J-ECM Terminal Lugs End Cap Kit 47 Bulletin 140U Molded Case Circuit Breakers Approximate Dimensions — 250 A, J-Frame Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes. 5.048 .170 4.125 6.000 2.062 4.453 #8-32 TAP 4 HOLES 5.642 1.541 .281 THERMAL ADJUSTMENT 5.500 .256 3.922 .110 X .310 DEEP R TYP(4) Ø.145 7.000 5.500 4 HOLES BREAKER H HANDLE .688 2.750 4.125 1.375 .664 2.062 .688 .203 1.375 FRONT CONNECTED DRILL PLAN GNETIC ADJUST PUSH TO TRIP 2.906 .897 Ø.650 TYP(6) 4.125 3.978 .500 2.062 Ø.625 6 HOLES ˚ 1.188 TRIP .594 R2.656 4.0˚ .500 7.000 ˚ BREAKER HANDLE 6.000 4.427 3.570 3.440 3.344 1.375 3.344 3.194 1.906 REF 2.750 .187 .188 REAR CONNECTED STUDS 1.771 .624 2.062 .125 Ø.198 .625 .625 1.000 .125 7.000 R.188 1.875 3.922 .173 .949 4.938 BREAKER K HANDLE .859 1.062 .949 .500 .281 2.000 4.000 .260 48 Bulletin 140U Molded Case Circuit Breakers Product Selection — 400 A, K-Frame • • • • UL 489 CSA 22.2, No. 5 IEC 157-1 KEMA-KEUR • Terminal box lugs must be ordered separately. See page 51 Breaker Frames Rated Current In [A] Breaking Capacity (50 Hz) Icu /Ics [kA] 380…415V 500V 40 40 30 30 65 65 50 38 100 100 65 49 220…240V 65 65 100 100 200 200 400 Interrupting Rating (60 Hz) [kA] 240V 480V 600V 65 35 25 100 65 35 200 100 50 690V 10 13 18 5 6 9 Cat. No. 140U-K3X3 140U-K6X3 140U-K0X3 Trip Units and Rating Plugs Thermal-Magnetic Adjustment Range [A] Rated Current Thermal Trip [A] Magnetic Trip In [A] Ir = In (Fixed) Im = 5…10 x In 100 100 500…1000 125 125 625…1250 150 150 750…1500 175 175 895…1750 200 200 1000…2000 225 225 1125…2250 250 250 1250…2500 300 300 1500…3000 350 350 1750…3500 400 400 2000…4000 Rated Current In [A] Cat. No. 140U-KTD3-D10 140U-KTD3-D12 140U-KTD3-D15 140U-KTD3-D17 140U-KTD3-D20 140U-KTD3-D22 140U-KTD3-D25 140U-KTD3-D30 140U-KTD3-D35 140U-KTD3-D40 400 Electronic Adjustment Range [A] Cat. No. Thermal Trip Magnetic Trip Protection Type Ir = 1.0 x In Im = 2…8 x In LS 140U-KTL3-D40 LSI 140U-KTH3-D40 200…400 ➊ 400…3200 LSG 140U-KTG3-D40 Rating Plugs Thermal Trip Cat. No. In [A] Thermal Trip In [A] 200 225 250 140U-KRP3-D20 140U-KRP3-D22 140U-KRP3-D25 300 350 400 Cat. No. 140U-KRP3-D30 140U-KRP3-D35 140U-KRP3-D40 Assembled Circuit Breakers, Thermal-Magnetic Trip Units Rated Current In [A] 100 125 150 175 200 225 250 300 350 400 400/480V [kA] 40/35 40/35 40/35 40/35 40/35 40/35 40/35 40/35 40/35 40/35 Cat. No. 140U-K3D3-D10 140U-K3D3-D12 140U-K3D3-D15 140U-K3D3-D17 140U-K3D3-D20 140U-K3D3-D22 140U-K3D3-D25 140U-K3D3-D30 140U-K3D3-D35 140U-K3D3-D40 400/480V [kA] 65/65 65/65 65/65 65/65 65/65 65/65 65/65 65/65 65/65 65/65 Cat. No. 140U-K6D3-D10 140U-K6D3-D12 140U-K6D3-D15 140U-K6D3-D17 140U-K6D3-D20 140U-K6D3-D22 140U-K6D3-D25 140U-K6D3-D30 140U-K6D3-D35 140U-K6D3-D40 400/480V [kA] 100/100 100/100 100/100 100/100 100/100 100/100 100/100 100/100 100/100 100/100 Cat. No. 140U-K0D3-D10 140U-K0D3-D12 140U-K0D3-D15 140U-K0D3-D17 140U-K0D3-D20 140U-K0D3-D22 140U-K0D3-D25 140U-K0D3-D30 140U-K0D3-D35 140U-K0D3-D40 Assembled Circuit Breakers, Electronic Trip Units Rated Current In [A] Thermal Trip 400/480V Protection Type Ir = 0.5…1.0 x In [kA] LS 40/35 100…400 ➊ LSI 40/35 LSG 40/35 400 400/480V [kA] 65/65 65/65 65/65 Cat. No. 140U-K3L3-D40 140U-K3H3-D40 140U-K3G3-D40 Cat. No. 140U-K6L3-D40 140U-K6H3-D40 140U-K6G3-D40 400/480V [kA] 100/100 100/100 100/100 Cat. No. 140U-K0L3-D40 140U-K0H3-D40 140U-K0G3-D40 ➊ Select proper rating plug to cover thermal trip requirement. Molded Case Switch — UL 1087 Rated Current In [A] Magnetic Trip 10 x In 400 4000 220…240V 100 100 Breaking Capacity (50 Hz) Icu /Ics [kA] 380…415V 500V 65 65 50 38 Interrupting Rating (60 Hz) [kA] 690V 13 6 240V 100 480V 65 600V 35 Cat. No. 140U-K6S3-D40 49 Bulletin 140U Molded Case Circuit Breakers Accessories — 400 A, K-Frame Internal Control Modules — Field Installed Description Mounting Location Cat. No. Diagram (1) 1a-1b ON OFF Auxiliary Contact (AX) • Electrically indicates “ON/ OFF” status of breakers AX 1a 1b 1c 1c (2) 1a-1b 140U-K-EA1 TRIP 1a 1a 1b 1b 1c 140U-K-EA2 I> Left AND Right side Alarm Contact (AL) • Electrically indicates when the breaker is in the “TRIPPED” state ON OFF (1) 1M (make)1B (break) M B AL TRIP M B 140U-K-ER1 M B I> 1c 1c 1c Right side ONLY \ ON OFF Auxiliary/Alarm Contact (AX/AL) (1) 1a-1b Combination (1) 1M (make)• Combination of auxiliary 1B (break) contact and alarm contact AX AL 1b 1c 1a 1b M B 1c TRIP 1a 1b M B 1c 1a M B 140U-K-EA1R1 I> 1c 1c 1c Right side ONLY 12…24V, 50/60/DC Shunt Trip (SNT) • Provides remote tripping of the circuit breaker • Undervoltage trip not available when shunt trip is used 140U-K-SNJ 110…240V AC, 110…125V DC 380…440V AC, 220…250V DC SNT S1 140U-K-SND S2 I> 480…600V, 50/ 60 Hz 24V, 50/60 Undervoltage Release (UVT) • Automatically trips breaker 110…127V, 50/ when voltage falls between 60 preset value, 35…70% 208…240V, 50/ • Shunt trip is not available 60 when undervoltage release is used 380…500V, 50/ 60 140U-K-SNN Left side ONLY 140U-K-SNB 140U-K-UJ UVT I> U1 140U-K-UD U> U2 Left side ONLY 140U-K-UA 140U-K-UB Internal Control Modules — Factory Installed Left side only (1) Shunt Trip (SNT) or (1) Undervoltage Release (UVT) Auxiliary and Alarm Contacts Suffix (1) AX (2) AX (1) AL (1) AX + (1) AL -A -B -D -F Right side only (1) Auxiliary contact (AX) or (2) Auxiliary contacts (AX) or (1) Alarm contact (AL) or (1) Alarm contact (AL) + Auxiliary contact (AX) Shunt Trip Suffix Combinations (1) SNT only - P⊗ (1) AX + (1) SNT - Q⊗ (2) AX + (1) SNT - R⊗ (1) AX + (1) AL + (1) SNT - T⊗ - V⊗ (1) AL + (1) SNT ⊗ Standard Voltage Suffix Codes ➊ Voltage [V] 12…24 110…240 380…440 480…600 AC J D N B 50/60 Hz Voltage [V] 12…24 110…125 220…250 — DC J D N — ➊ For additional voltages, consult your local Allen-Bradley distributor. 50 Mounting Location Undervoltage Release Suffix Combinations (1) UVT only - G⊗ (1) AX + (1) UVT - H⊗ (2) AX + (1) UVT - J⊗ (1) AX + (1) AL + (1) UVT - L⊗ (1) AL + (1) UVT - N⊗ ⊗ Standard Voltage Suffix Codes ➊ Voltage [V] 24 110…127 208…240 380…480 AC J D A B 50/60 Hz Voltage [V] — — — — DC — — — — Bulletin 140U Molded Case Circuit Breakers Accessories — 400 A, K-Frame, Continued External Accessories Description Terminal Shields IP20 Ingress Protection Non-Metallic — Type 1/3/12/4/4X Flange-Mount Operating Handle Cat. No. Qty: 1 140U-K-TS 3 ft. (0.9 m) Cable 140U-K-FCX03 4 ft. (1.3 m) Cable 140U-K-FCX04 6 ft. (1.8 m) Cable 140U-K-FCX06 10 ft. (3.0 m) Cable 140U-K-FCX10 3 ft. (0.9 m) Cable 140U-K-FCS03 4 ft. (1.3 m) Cable 140U-K-FCS04 6 ft. (1.8 m) Cable 140U-K-FCS06 10 ft. (3.0 m) Cable 140U-K-FCS10 Black Handle 140U-K-RM12B Red/Yellow Handle 140U-K-RM12R Black Handle 140U-K-RCB Red/Yellow Handle 140U-K-RCR Flex-Cable Operating Mechanism Stainless Steel — Type 4/4X Flange-Mount Operating Handle Rotary, Variable-Depth Operating Mechanism Rotary, Direct Couple Operating Mechanism Rotary Handle — Type 1/12 12 in. (305 mm) operating rod Rotary Handle — Type 1 Breaker Mounted Operating Handle Extension Provides handle extension for ease of operation Qty: 1 140U-K-OHE Phase Barriers Provides additional phase clearance when special connections are required Qty: 2 140U-K-PB Padlock Kit Padlocking Hasp Lock-OFF only — 140U-K-PL Qty: 1 140U-K-TLC1 Terminal Lugs Copper lug Copper wire only (1) 250…500 MCM (1) 120…240 mm2 Copper lug Copper wire only (1) 3/0…250 MCM (1) 95…120 mm2 Aluminum lug Aluminum or copper wire (1) 250…500 MCM (1) 120…240 mm2 Qty: 3 140U-K-TLC2 Qty: 1 140U-K-TLA1 Qty: 1 140U-K-ECM End Cap Kit Provides 3-phase connections for terminal or bolt-on connections Metric Hardware 51 Bulletin 140U Molded Case Circuit Breakers Approximate Dimensions — 400 A, K-Frame Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes. Front View Side View 5.490(139.43) .844 (21.44) Line End .625 (15.88) 2.813 (71.45) 1.719 (43.66) .188 (4.77) Dia. C'Bore x .031 (.79) DP .147 (12.7) Dia. Hole x .500 DP to Accept #8 (M4) Thread Cutting Screws (8 Places) .860 (21.84) 2.063 (52.39) .125 (3.18) 4.125 (104.78) .093 R (2.36) R 3.75 (9.52) ON .375 (9.52) Contact Position Indicators Red/1 - On Green/O - Off White - T rip 2.438 (61.89) .750 (19.05) CL 10.125 (257.18) 3.875 R (98.42) R Handle .500 (12.70) 1.219 (30.96) 1.625 (41.28) 1.625 (41.28) D .250 (6.35) .063 (1.60) 1.063 (27.00) .500 (12.70) 8.438 (214.33) 8.875 (225.43) OFF .250 R (6.35) R 1.250 (31.75) 43û .062 (1.57) 4.000 (101.60) 3.563 (90.50) 1.000 (25.40) 3.813 (96.85) .125 (3.18) Wide x .750 (19.05) Slots for Attachment Leads .188 (4.77) R 7.406 (112.70) .694 (17.63) 5.000(127.00) 2.563 (12.70) 4.437 (65.10) .500 (12.70) Trough for Attachment Leads C B .209 (5.31) .188 (4.77) A 1.734 (44.04) 2.391 (60.73) 39û 4.782(121.46) .698 .547 (13.89) (17.73) .188 R (4.77) R .500 (12.70) 1.160 (29.49) .063 (1.60) .937 (23.80) Dimensions for Extended Terminals and Barrier Style Nos. 4212B60G02, 4212B61G02 and 1492D24H01 .875 (22.25) .438 (11.13) .250 (6.35) R 1.063 (27.00) .750 (19.05) Wide Conductor with .391 (9.93) Dia Hole Line and Load End 3.812 (96.82) .188 (4.77) .766 (19.46) 52 2.375 (60.33) .500 (12.70) Load End .281 (7.14) Dia. Mounting Holes 4 Holes for .250-20 (M6) x 1.50 (38) Mounting Screws .500 (12.70) Dia. C'Bore from T op 2.875 (73.03) Deep Load End 2.625 (66.68) Deep Line End .438 (11.13) Dia C'Bore .750 (10.05) Deep from Bottom .062 (1.57) 4.062 (103.17) E F Breaker Status Dimensions Handle Force➀ A B C D E F On 5.39 (136.9) 5.20 (132.1) 5.69 (144.5) 5.61 (142.5) 4.72 (119.9) 4.77 (121.2) 30 lbs. (13.61 kgs.) Tripped 4.77 (121.2) 4.69 (119.1) 5.08 (129.0) 5.11 (129.8) 4.89 (124.2) 4.89 (124.2) N/A Off 4.16 (105.7) 4.21 (106.9) 4.46 (113.3) 4.64 (117.9) 4.95 (125.7) 4.91 (124.7) 25 lbs. (11.34 kgs.) Reset 4.07 (103.4) 4.14 (105.2) 4.57 (116.1) 4.56 (115.8) 4.95 (125.7) 4.90 (124.5) 35 lbs. (15.87 kgs.) ➀ All handle forces measured approximately 0.125 (3.17) from top of handle. 5.966(151.54) 1.719 (43.66) 5.766 (146.46) .500 (12.70) 4.313 (109.55) .110 (2.79) Dia. x .297 (7.54) Deep, 4 Holes Accept #6 (M3) Thread Cutting Screws 3.438 (87.32) .625 (15.88) 6 Holes Bulletin 140U Molded Case Circuit Breakers Product Selection — 600 A, Q-Frame • • • • • UL 489 CSA 22.2, No. 5 IEC 60947-2 CE KEMA-KEUR • Terminal box lugs must be ordered separately. See page 55 Breaker Frames Rated Current In [A] 600 220…240V 85 85 100 100 Breaking Capacity (50 Hz) Icu /Ics [kA] 380…415V 500V 45 45 30 30 70 70 50 38 Interrupting Rating (60 Hz) [kA] 690V 20 25 240V 65 100 10 13 480V 35 65 Cat. No. 600V 25 35 140U-Q3X3 140U-Q6X3 Trip Units and Rating Plugs Thermal-Magnetic Adjustment Range [A] Rated Current In Thermal Trip Magnetic Trip [A] Ir = In (Fixed) Im = 5…10 x In 300 300 1500…3000 350 350 1750…3500 400 400 2000…4000 450 450 2250…4500 500 500 2500…5000 600 600 3000…6000 Electronic Adjustment Range [A] Rated Current Thermal Trip Magnetic Trip In [A] Ir = 0.5…1.0 x In Im = 2…8 x In Cat. No. 140U-QTD3-D30 140U-QTD3-D35 140U-QTD3-D40 140U-QTD3-D45 140U-QTD3-D50 140U-QTD3-D60 600 400…600 ➊ Protection Type Cat. No. LS LSI LSG 140U-QTL3-D60 140U-QTH3-D60 140U-QTG3-D60 800…4800 Rating Plugs Thermal Trip Cat. No. In [A] 400 500 600 140U-QRP3-D40 140U-QRP3-D50 140U-QRP3-D60 Assembled Circuit Breakers, Thermal-Magnetic Trip Units Thermal Trip Ir = In 300 350 400 450 500 600 Rated Current In [A] 300 350 400 450 500 600 400/480V [kA] 45/35 45/35 45/35 45/35 45/35 45/35 Cat. No. 140U-Q3D3-D30 140U-Q3D3-D35 140U-Q3D3-D40 140U-Q3D3-D45 140U-Q3D3-D50 140U-Q3D3-D60 400/480V [kA] 70/65 70/65 70/65 70/65 70/65 70/65 Cat. No. 140U-Q6D3-D30 140U-Q6D3-D35 140U-Q6D3-D40 140U-Q6D3-D45 140U-Q6D3-D50 140U-Q6D3-D60 Assembled Circuit Breakers, Electronic Trip Units Rated Current In [A] Thermal Trip Ir = 0.5…1.0 x In Protection Type 600 200…600 ➊ LS LSI LSG 400/480V [kA] 45/35 45/35 45/35 Cat. No. 140U-Q3L3-D60 140U-Q3H3-D60 140U-Q3G3-D60 400/480V [kA] 70/65 70/65 70/65 Cat. No. 140U-Q6L3-D60 140U-Q6H3-D60 140U-Q6G3-D60 ➊ Select proper rating plug to cover thermal trip requirement. Molded Case Switch — UL 1087 Rated Current In [A] Magnetic Trip Im = 10 x In 600 6000 220…240V 100 100 Breaking Capacity (50 Hz) Icu /Ics [kA] 380…415V 500V 70 70 50 38 690V 25 13 Interrupting Rating (60 Hz) [kA] 240V 480V 600V 100 65 35 Cat. No. 140U-Q6S3-D60 53 Bulletin 140U Molded Case Circuit Breakers Accessories — 600 A, Q-Frame Internal Control Modules — Field Installed Description Mounting Location Cat. No. Diagram (1) 1a-1b ON OFF Auxiliary Contact (AX) • Electrically indicates “ON/ OFF” status of breakers AX 1a 1b 1c 1c (2) 1a-1b 140U-M-EA1 TRIP 1a 1a 1b 1b 1c 140U-M-EA2 I> Left AND Right side Alarm Contact (AL) • Electrically indicates when the breaker is in the “TRIPPED” state ON OFF (1) 1M (make)1B (break) M B AL TRIP M B 140U-M-ER1 M B I> 1c 1c 1c Right side ONLY \ ON OFF AX Auxiliary/Alarm Contact (AX/AL) (1) 1a-1b Combination (1) 1M (make)• Combination of auxiliary 1B (break) contact and alarm contact AL 1b 1c 1a 1b M B 1c TRIP 1a 1b M B 1c 1a M B I> 1c 1c 1c 140U-M-EA1R1 Right side ONLY 12…24V, 50/60/DC Shunt Trip (SNT) • Provides remote tripping of the circuit breaker • Undervoltage trip not available when shunt trip is used Undervoltage Release (UVT) • Automatically trips breaker when voltage falls between preset value, 35…70% • Shunt trip is not available when undervoltage release is used 140U-M-SNJ 110…240V AC, 110…125V DC 380…440V AC, 220…250V DC S1 SNT 140U-M-SND S2 I> 140U-M-SNN Left side ONLY 480…600V, 50/60 Hz 140U-M-SNB 24V, 50/60 Hz 140U-M-UJ 110…127V, 50/60 Hz UVT 208…240V, 50/60 Hz 380…500V, 50/60 Hz U1 140U-M-UD U> I> U2 Left side ONLY 140U-M-UA 140U-M-UB Internal Control Modules — Factory Installed Left side only (1) Shunt Trip (SNT) or (1) Undervoltage Release (UVT) Auxiliary and Alarm Contacts Suffix (1) AX (2) AX (1) AL (1) AX + (1) AL -A -B -D -F Right side only (1) Auxiliary contact (AX) or (2) Auxiliary contacts (AX) or (1) Alarm contact (AL) or (1) Alarm contact (AL) + Auxiliary contact (AX) Shunt Trip Suffix Combinations (1) SNT only - P⊗ (1) AX + (1) SNT - Q⊗ (2) AX + (1) SNT - R⊗ (1) AX + (1) AL + (1) SNT - T⊗ - V⊗ (1) AL + (1) SNT ⊗ Standard Voltage Suffix Codes ➊ Voltage [V] 12…24 110…240 380…440 480…600 AC J D N B 50/60 Hz Voltage [V] 12…24 110…125 220…250 — DC J D N — ➊ For additional voltages, consult your local Allen-Bradley distributor. 54 Mounting Location Undervoltage Release Suffix Combinations (1) UVT only - G⊗ (1) AX + (1) UVT - H⊗ (2) AX + (1) UVT - J⊗ (1) AX + (1) AL + (1) UVT - L⊗ (1) AL + (1) UVT - N⊗ ⊗ Standard Voltage Suffix Codes ➊ Voltage [V] 24 110…127 208…240 380…480 AC J D A B 50/60 Hz Voltage [V] — — — — DC — — — — Bulletin 140U Molded Case Circuit Breakers Accessories — 600 A, Q-Frame, Continued External Accessories Description Non-Metallic — Type 1/3/12/4/4X Flange-Mount Operating Handle Cat. No. 4 ft. (1.3 m) Cable 140U-M-FCX04 6 ft. (1.8 m) Cable 140U-M-FCX06 10 ft. (3.0 m) Cable 140U-M-FCX10 Flex-Cable Operating Mechanism Stainless Steel — Type 4/4X Flange-Mount Operating Handle Rotary, Variable-Depth Operating Mechanism 4 ft. (1.3 m) Cable 140U-M-FSX04 6 ft. (1.8 m) Cable 140U-M-FSX06 10 ft. (3.0 m) Cable 140U-M-FSX10 Black Handle 140U-M-RM12B Red/Yellow Handle 140U-M-RM12R Rotary Handle — Type 1/12 12 in. (305 mm) operating rod Phase Barriers Provides additional phase clearance when special connections are required Qty:2 140U-M-PB Padlock Kit Padlocking Hasp Lock-OFF only — 140U-M-PL Operating Handle Extension Provides handle extension for ease of operation Qty: 1 140U-M-OHE Copper lug Copper wire only (2) 250…350 MCM (2) 120…250 mm2 Qty: 1 140U-Q-TLC2 Aluminum lug Aluminum or Copper wire (2) 3/0…350 MCM (2) 95…150 mm2 Qty:1 140U-Q-TLA2 Terminal Lugs 55 Bulletin 140U Molded Case Circuit Breakers Approximate Dimensions — 600 A, Q-Frame Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes. Front View Side View .375 (9.52) .531 (13.49) Trough For Attachment Leads Off/O Off/O 1.232 (31.29) .188 R (4.77) R Trip Unit May Be Either Thermal/Magnetic Or Electronic 1.500 (38.10) .500 (12.70) .80 )R CL Handle 19.2û 24.2û 0.2û Tripped .420 (10.67) Off .482 (12.24) Reset .500 (12.70) 8.213 (208.61) (88 6.688 (169.87) .61 .44 6 (15 2 ( .65 11 ) .23 ) 5.614 (142.59) 96 .1.151 45û (29.23) 5.136 (130.45) .750 (19.05) .375 (9.52) 3.4 On B CL Handle 45û 3.622 (92.00) 1.000(25.40) R x 1.906 (48.41) Wide .219 (5.56) 14.7û A 1.142 (29.00) 10.750 (273.05) 5.083 (129.10) .297 (7.54) 4.000 (101.60) .250 (6.35) 9.594 (243.68) CL / CL Standard T erminals On/I On/I 1.594 (40.49) .375 (9.52) 1.126 (28.60) 3.094 (78.59) 2.281 (57.94) .250(6.35) R .156(3.96) R 2.292 (58.22) 4.864 (123.54) 1.125 (28.57) 3.019 (76.68) 3.812 (96.82) .125(3.17) Wide x .750 (19.05) Slots For Attachment Leads .250(6.35) R 4.260 (108.20) 9.531 (242.09) CL / CL Mounting Holes 5.052 (128.32) 6.489 (164.82) .438 (11.12) 11.344 (288.14) CL / CL Extended T erminals 5.958 (151.33) 4.062 (103.17) Line End .147(3.73) Dia Hole .500(12.70) Deep To Accept #8 Thread Cutting Screws 8 Places .875 (22.22) 12.500 (317.50) Overall Extended Length 4.375 (111.12) Removable T erminal Cover Must Be in Place While in Service 4.327 (109.90) .516 (13.11) Hex .406 (10.31) .250 (6.35) Deep Dia. .250-20(6.35) .328 (8.33) Dia. Tap Hole 12 Holes Terminal Barrier Used with Extended T erminals Only (TA603LD) 0.062 R (1.57) R .800 (20.32) 2.750 (69.85) .016 (0.41) 2.062 (52.37) .110(2.79) Dia Hole .312(7.92) Deep To Accept #6 Thread Cutting Screws 6 Places 2.750 (69.85) .313 (7.95) Dia. Mounting Holes (4) for .250 (6.35) - 20 x 1.50 (38.10) Mounting Screws .531 (13.49) Dia C'Bore from Top 2.625 (66.67) Deep Line End (2) 2.875 (73.02) Deep Load End (2) .531 (13.49) Dia. C'Bore .875 (22.22) from Bottom 4.125 (104.77) 5.500 (139.70) 3.641 (92.48) 7.281 (184.94) 4.125 (104.77) 8.250 (209.55) 3.250 (82.55) 2.750 (69.85) .812 (20.62) 1.625 (41.27) 1.906 (48.41) .062 (1.57) .531 (13.49) .375 (9.52) 1.265 (32.13) 2.047 (51.99) Handle Forces ➀ On Off Reset 1.625 (41.27) 1.875 (47.62) Wide Conductor with .406 (10.31) Dia. Hole Line and Load Ends (Current Carrying Parts Omitted in Center Pole for 2-Pole Breaker) 56 Load End CLHandle Contact Position Indicators Red/I - On Green/O - Off White - T rip 1.000(25.40) R x 1.906(48.41) Wide .313 R (7.95) R 1.375 (34.92) ➀ Measurements taken approximately 3/16 in. from end of handle. 1.906 (48.41) 3.218 (81.74) 45 lbs. 50 lbs. 60 lbs. Bulletin 140U Molded Case Circuit Breakers Product Selection — 800 A, M-Frame • • • • • • UL 489 CSA 22.2, No. 5 IEC 60947-2 CE KEMA-KEUR Terminal box lugs must be ordered separately. See page 59 Breaker Frames Rated Current In [A] Breaking Capacity (50 Hz) Icu /Ics [kA] 380…415V 500V 50 50 50 25 70 70 70 50 220…240V 65 65 100 100 800 Interrupting Rating (60 Hz) [kA] 690V 20 25 240V 65 100 10 13 480V 50 65 Cat. No. 600V 25 35 140U-M5X3 140U-M6X3 Trip Units and Rating Plugs Rated Current In [A] 300 350 400 450 500 600 700 800 Thermal-Magnetic Adjustment Range [A] Thermal Trip Magnetic Trip Ir = In Im = 5…10 x In 300 1500…3000 350 1750…3500 400 2000…4000 450 2250…4500 500 2500…5000 600 3000…6000 700 3500…7000 800 4000…8000 Cat. No. Rated Current In [A] 140U-MTD3-D30 140U-MTD3-D35 140U-MTD3-D40 140U-MTD3-D45 140U-MTD3-D50 140U-MTD3-D60 140U-MTD3-D70 140U-MTD3-D80 800 Electronic Adjustment Range [A] Thermal Trip Magnetic Trip Ir = 1.0 x In Im = 2…8 x In 400…800 ➊ 800…6400 Thermal Trip In [A] Cat. No. 400 500 600 140U-MRP3-D40 140U-MRP3-D50 140U-MRP3-D60 Protection Type Cat. No. LS LSI LSG 140U-MTL3-D80 140U-MTH3-D80 140U-MTG3-D80 Rating Plugs Thermal Trip In [A] 700 800 Cat. No. 140U-MRP3-D70 140U-MRP3-D80 Assembled Circuit Breakers, Thermal-Magnetic Trip Units Thermal Trip Ir = In 300 350 400 450 500 600 700 800 Rated Current In [A] 300 350 400 450 500 600 700 800 400/480V [kA] 50/50 50/50 50/50 50/50 50/50 50/50 50/50 50/50 400/480V [kA] 70/65 70/65 70/65 70/65 70/65 70/65 70/65 70/65 Cat. No. 140U-M5D3-D30 140U-M5D3-D35 140U-M5D3-D40 140U-M5D3-D45 140U-M5D3-D50 140U-M5D3-D60 140U-M5D3-D70 140U-M5D3-D80 Cat. No. 140U-M6D3-D30 140U-M6D3-D35 140U-M6D3-D40 140U-M6D3-D45 140U-M6D3-D50 140U-M6D3-D60 140U-M6D3-D70 140U-M6D3-D80 Assembled Circuit Breakers, Electronic Trip Units Rated Current In [A] Thermal Trip Ir = 0.5…1.0 x In Protection Type 200…800 ➊ LS LSI LSG 800 400/480V [kA] 50/50 50/50 50/50 Cat. No. 140U-M5L3-D80 140U-M5H3-D80 140U-M5G3-D80 400/480V [kA] 70/65 70/65 70/65 Cat. No. 140U-M6L3-D80 140U-M6H3-D80 140U-M6G3-D80 ➊ Select proper rating plug to cover thermal trip requirement. Molded Case Switch — UL 1087 Rated Current In [A] Magnetic Trip Im = 10 x In 800 8000 220…240V 100 100 Breaking Capacity (50 Hz) Icu /Ics [kA] 380…415V 500V 70 70 70 50 Interrupting Rating (60 Hz) [kA] 690V 25 13 240V 100 480V 65 600V 35 Cat. No. 140U-M6S3-D80 57 Bulletin 140U Molded Case Circuit Breakers Accessories — 800 A, M-Frame Internal Control Modules — Field Installed Description Mounting Location Cat. No. Diagram (1) 1a-1b ON OFF Auxiliary Contact (AX) • Electrically indicates “ON/ OFF” status of breakers AX 1a 1b 1c 1c (2) 1a-1b 140U-M-EA1 TRIP 1a 1a 1b 1b 1c 140U-M-EA2 I> Left AND Right side Alarm Contact (AL) • Electrically indicates when the breaker is in the “TRIPPED” state ON OFF (1) 1M (make)1B (break) M B AL TRIP M B 140U-M-ER1 M B I> 1c 1c 1c Right side ONLY \ ON OFF Auxiliary/Alarm Contact (AX/AL) (1) 1a-1b Combination (1) 1M (make)• Combination of auxiliary 1B (break) contact and alarm contact AX AL 1b 1c 1a 1b M B 1c TRIP 1a 1b M B 1c 1a M B 140U-M-EA1R1 I> 1c 1c 1c Right side ONLY 12…24V, 50/60/DC Shunt Trip (SNT) • Provides remote tripping of the circuit breaker • Undervoltage trip not available when shunt trip is used 140U-M-SNJ 110…240V AC, 110…125V DC 380…440V AC, 220…250V DC SNT S1 140U-M-SND S2 140U-M-SNN I> Left side ONLY 480…600V, 50/60 Hz 24V AC, 50/60 Hz Undervoltage Release (UVT) • Automatically trips breaker 110…127V AC, when voltage falls between 50/60 Hz preset value, 35…70% 208…240V AC, • Shunt trip is not available 50/60 Hz when undervoltage release is used 380…500V AC, 50/60 Hz 140U-M-SNB 140U-M-UJ UVT I> Left side ONLY U1 140U-M-UD U> U2 140U-M-UA 140U-M-UB Internal Control Modules — Factory Installed Left side only (1) Shunt Trip (SNT) or (1) Undervoltage Release (UVT) Auxiliary and Alarm Contacts Suffix (1) AX (2) AX (1) AL (1) AX + (1) AL -A -B -D -F Right side only (1) Auxiliary contact (AX) or (2) Auxiliary contacts (AX) or (1) Alarm contact (AL) or (1) Alarm contact (AL) + Auxiliary contact (AX) Shunt Trip Suffix Combinations (1) SNT only - P⊗ (1) AX + (1) SNT - Q⊗ (2) AX + (1) SNT - R⊗ (1) AX + (1) AL + (1) SNT - T⊗ (1) AL + (1) SNT - V⊗ ⊗ Standard Voltage Suffix Codes ➊ Voltage [V] 12…24 110…240 380…440 480…600 AC, J D N B 50/60 Hz Voltage [V] 12…24 110…125 220…250 — DC J D N — ➊ For additional voltages, consult your local Allen-Bradley distributor. 58 Mounting Location Undervoltage Release Suffix Combinations (1) UVT only - G⊗ (1) AX + (1) UVT - H⊗ (2) AX + (1) UVT - J⊗ (1) AX + (1) AL + (1) UVT - L⊗ (1) AL + (1) UVT - N⊗ ⊗ Standard Voltage Suffix Codes ➊ Voltage [V] 24 110…127 208…240 380…480 AC, J D A B 50/60 Hz Voltage [V] — — — — DC — — — — Bulletin 140U Molded Case Circuit Breakers Accessories — 800 A, M-Frame, Continued External Accessories Description Non-Metallic — Type 1/3/12/4/4X Flange-Mount Operating Handle Cat. No. 4 ft. (1.3 m) Cable 140U-M-FCX04 6 ft. (1.8 m) Cable 140U-M-FCX06 10 ft. (3.0 m) Cable 140U-M-FCX10 Flex-Cable Operating Mechanism 4 ft. (1.3 m) Cable 140U-M-FSX04 6 ft. (1.8 m) Cable 140U-M-FSX06 10 ft. (3.0 m) Cable 140U-M-FSX10 Black Handle 140U-M-RM12B Red/Yellow Handle 140U-M-RM12R Copper lug Copper wire only (3) 3/0…300MCM (3) 95…135 mm2 Qty: 1 140U-M-TLC3 Aluminum lug Aluminum or Copper wire (3) 3/0…400MCM (3) 95…185 mm2 Qty: 1 140U-M-TLA3 Phase Barriers Provides additional phase clearance when special connections are required Qty: 2 140U-M-PB Padlock Kit Padlocking Hasp Lock-OFF only — 140U-M-PL Operating Handle Extension Provides handle extension for ease of operation Qty: 1 140U-M-OHE Stainless Steel — Type 4/4X Flange-Mount Operating Handle Rotary, Variable-Depth Operating Mechanism Terminal Lugs Rotary Handle — Type 1/12 12 in. (305 mm) operating rod 59 Bulletin 140U Molded Case Circuit Breakers Approximate Dimensions — 800 A, M-Frame Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes. C L Handle Pivot Line End 2.018 (51.26) .375 (9.53) Dia. 4-Holes for .312 (7.92) 16 (406.40) x 1.75 (44.45) Large Mounting Screws. 8.302 (210.87) .500 (12.70) 1.411 (35.84) Max. .547 (13.89) 7.677 (195.00) 6.052 (153.72) On/I .415 (10.54) Tripped 0.2˚ 11.500 (292.10) On/I On 14.7˚ C L Handle Pivot Off 19.2˚ Off/O Off/O 14.750 (374.65) Reset 24.2˚ 16.000 (406.40) Dim. B 1.375 (34.93) Dim. A .500 (12.70) - 13 Tap Thru. .500 (12.70) 2.750 (69.85) .531 (13.49) 2.531 (64.29) 4.062 (103.17) 2.750 (69.85) 5.500 (139.70) 4.375 (111.13) 4.250 (107.95) 8.250 (209.55) Load End 3.250 (82.55) 1.625 (41.28) 1.625 (41.28) .813 (20.65) 1.874 (47.60) 60 Breaker Status Dimension A Dimension B On 8.72 (221.49) 9.17 (232.92) Off 6.72 (170.69) 7.14 (181.36) Tripped 7.86 (199.64) 8.30 (210.82) Reset 6.44 (163.58) 6.84 (173.74) Bulletin 140U Molded Case Circuit Breakers Product Selection — 1200 A, N-Frame • • • • • UL 489 CSA 22.2, No. 5 IEC 60947-2 CE KEMA-KEUR • Terminal box lugs must be ordered separately. See page 63 Assembled Circuit Breakers, Electronic Trip Units Adjustment Range Ir [A] Rated Protection Current Magnetic Trip Thermal Trip Type In [A] Ir = 0.5…1.0 x In Im = 2…8 x In 1200 600…1200 ➊ 1200…10,600 1200 600…1200 ➊ 1200…10,600 1200 600…1200 ➊ 1200…10,600 LS LS LSI LSG LS LSI LSG 220…240V 85 85 100 100 100 100 100 100 200 100 200 100 200 100 Breaking Capacity (50 Hz) Icu /Ics [kA] 380…415V 500V 50 50 40 20 70 50 50 25 70 50 50 25 70 50 50 25 100 50 65 33 100 50 65 33 100 50 65 33 Interrupting Rating (60 Hz) [kA] 690V 20 10 25 13 25 13 25 13 35 18 35 18 35 18 240V 65 100 100 100 200 200 200 480V 50 65 65 65 100 100 100 Cat. No. 600V 25 35 35 35 50 50 50 140U-N5L3-E12 140U-N6L3-E12 140U-N6H3-E12 140U-N6G3-E12 140U-N0L3-E12 140U-N0H3-E12 140U-N0G3-E12 ➊ Select proper rating plug to cover thermal trip requirement. Rating Plugs Rated Current In [A] 600 700 800 Cat. No. 140U-NRP3-D60 140U-NRP3-D70 140U-NRP3-D80 Rated Current In [A] 900 1000 1200 Cat. No. 140U-NRP3-D90 140U-NRP3-E10 140U-NRP3-E12 Molded Case Switch — UL 1087 Rated Current In [A] Magnetic Trip 10 x In 1200 12,000 220…240V 100 100 Breaking Capacity (50 Hz) Icu /Ics [kA] 380…415V 500V 70 50 50 25 690V 25 13 Interrupting Rating (60 Hz) [kA] 240V 480V 600V 100 65 35 Cat. No. 140U-N6S3-E12 61 Bulletin 140U Molded Case Circuit Breakers Accessories — 1200 A, N-Frame Internal Control Modules — Field Installed Description Mounting Location Cat. No. Diagram (1) 1a-1b ON OFF Auxiliary Contact (AX) • Electrically indicates “ON/ OFF” status of breakers AX 1a 1b 1c 1c (2) 1a-1b 140U-N-EA1 TRIP 1a 1a 1b 1b 1c 140U-N-EA2 I> Left AND Right side Alarm Contact (AL) • Electrically indicates when the breaker is in the “TRIPPED” state ON OFF (1) 1M (make)1B (break) M B AL TRIP M B 140U-N-ER1 M B I> 1c 1c 1c Right side ONLY ON OFF AX Auxiliary/Alarm Contact (AX/AL) (1) 1a-1b Combination (1) 1M (make)• Combination of auxiliary 1B (break) contact and alarm contact AL 1b 1c 1a 1b M B 1c TRIP 1a 1b M B 1c 1a M B I> 1c 1c 1c 140U-N-EA1R1 Right side ONLY 12…24V, 50/60/DC Shunt Trip (SNT) • Provides remote tripping of the circuit breaker • Undervoltage trip not available when shunt trip is used 140U-N-SNJ 110…240V AC, 110…125V DC 380…440V AC, 220…250V DC SNT S1 140U-N-SND S2 I> 480…600V, 50/60 Hz 24V AC, 50/60 Hz Undervoltage Release (UVT) 110…127V AC, • Automatically trips breaker 50/60 Hz when voltage falls between 208…240V AC, preset value, 35…70% 50/60 Hz • Shunt trip is not available when undervoltage release is used 380…500V AC, 50/60 Hz 140U-N-SNN Left side ONLY 140U-N-SNB 140U-N-UJ 140U-N-UD UVT Left side ONLY I> U1 U> 140U-N-UA U2 140U-N-UB Internal Control Modules — Factory Installed Left side only (1) Shunt Trip (SNT) or (1) Undervoltage Release (UVT) Auxiliary and Alarm Contacts Suffix (1) AX (2) AX (1) AL (1) AX/ (1) AL -A -B -D -F Right side only (1) Auxiliary contact (AX) or (2) Auxiliary contacts (AX) or (1) Alarm contact (AL) or (1) Alarm contact (AL) + Auxiliary contact (AX) Shunt Trip Suffix Combinations (1) SNT only - P⊗ (1) AX + (1) SNT - Q⊗ (2) AX + (1) SNT - R⊗ (1) AX + (1) AL + (1) SNT - T⊗ (1) AL + (1) SNT - V⊗ ⊗ Standard Voltage Suffix Codes ➊ Voltage [V] 12…24 110…240 380…440 480…600 AC, J D N B 50/60 Hz Voltage [V] 12…24 110…125 220…250 — J D N — DC ➊ For additional voltages, consult your local Allen-Bradley distributor. 62 Mounting Location Undervoltage Release Suffix Combinations (1) UVT only - G⊗ (1) AX + (1) UVT - H⊗ (2) AX + (1) UVT - J⊗ (1) AX + (1) AL + (1) UVT - L⊗ (1) AL + (1) UVT - N⊗ ⊗ Standard Voltage Suffix Codes ➊ Voltage [V] 24 110…127 208…240 380…480 AC, J D A B 50/60 Hz Voltage [V] — — — — DC — — — — Bulletin 140U Molded Case Circuit Breakers Accessories — 1200 A, N-Frame, Continued External Accessories Description Flex-Cable Operating Mechanism Non-Metallic — Type 1/3/12/4/4X Flange-Mount Operating Handle Cat. No. 4 ft. (1.3 m) Cable 140U-N-FCX04 6 ft. (1.8 m) Cable 140U-N-FCX06 10 ft. (3.0 m) Cable 140U-N-FCX10 Rotary, Variable-Depth Operating Mechanism Rotary Handle — Type 1/12 12 in. (305 mm) operating rod Black Handle 140U-N-RM12B Phase Barriers Provides additional phase clearance when special connections are required Qty: 2 140U-N-PB Padlock Kit Padlocking Hasp Lock-OFF only Qty: 1 140U-N-PL Qty: 1 140U-N-TLC4 Terminal Lugs Copper lug Copper wire only (4) 3/0…400MCM (4) 95…185 mm2 Aluminum lug Aluminum or Copper wire (4) 4/0…500MCM (4) 120…300 mm2 Qty:1 140U-N-TLA4 63 Bulletin 140U Molded Case Circuit Breakers Approximate Dimensions — 1200 A, N-Frame Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes. Removable T erminal Cover Must Be in Place While in Service .344(8.738) Dia. Mounting Holes .703(17.856) Dia. C'Bore 4.453(113.106) Deep from Top .594(15.088) Dia C'Bore .359(9.119) Deep from Bottom 1.062(26.987) .531 (13.481) 1.157(29.388) .532(13.513) .500-13 (12 X 1.75) Tap 12-Holes .062(1.575) Line End 3.236 (82.194) Trough for Attachment Lead .250R (6.350)R 7.000(177.774) 9.250(234.950) 14.750(374.650) 8.625(219.075) 115.00(292.075) 11.431 (290.348) .125 X .750 (3.175 X 19.050) Slots for Attachment Leads .062R (1.575)R .094R (2.388)R .297 (7.544) 3.850R 21û±2û ON/I ON .353 (6.331) 0û±2û TRIPPED OFF/O .188R (4.762)R 2.511 (63.786) 1.375 (34.925) 2.750 (69.850) 2.344 3.187 (59.541) (80.950) 6.375 (161.925) 4.124 (104.750) .062 (1.588) R 2.750 Ref. (69.850) Ref. 2.000 (50.800) 1.000 (25.400) 5.188(131.769) 5.500(139.687) Breaker Status 6.000(152.400) A B On 7.90 (200.66) 8.30 (210.82) Tripped 6.50 (165.10) 6.90 (175.26) Off 5.70 (144.78) 6.10 (154.94) Reset 5.60 (142.24) 6.00 (152.40) 7.132 (181.146) Handle Forces (At Handle C)L 3.906 (99.187) On 130 lbs. (58.97 kgs.) Off 105 lbs. (47.63 kgs.) Reset 160 lbs. (72.57 kgs.) 1.500 Ref (38.100) Ref 3.819 (96.723) 4.875 (123.799) .062 (1.575) 64 1.095(27.813) 3.344(84.938) Dimensions .781 (19.844) .062 (1.588) R .062(1.575) .532(13.513) 5.248(133.293) 1.688 (42.863) 1.562 (39.687) Load End Removable Terminal Cover Must Be in Place While in Service 3.375 (85.725) 2.000 (50.800) 1.034 (33.281) Handle Pivot Contact Position Indicator Red-I/ON Green-O/OFF White-TRIPPED 8.250 (209.550) For 2-Pole Breaker Omit Current Carrying Parts from Center Pole 2.982 (75.743) B A .147 (3.734) Dia. Hole .500 (12.70) Deep to Accept a #8Thread Cutting Screw 6-Places 3.808 (96.723) 2.798 (71.057) .375 (9.525) RESET 1.500 (38.100) .312R (7.925)R 13û±2ûOFF 15û±2û .750 (19.050) .375 (9.525) CL Push To Trip 16.000(406.401) CL Handle .946 (24.022) 2.493 (63.792) 6.375 Ref (161.925) Ref