IEC Terminal Blocks

Bulletin 1492
IEC Terminal Blocks
Fuse Blocks
2.0" (50.7 mm)
Specifications
Maximum Current
Wire Range (Rated Cross Section)
Indicator Type
2.0" (50.7 mm)
0.31"
(8 mm)
Single-circuit fuse block with LED
blown fuse indicator.
CSA
IEC
300V
AC/DC
500V
AC/DC
15 A
15 A
15 A ➊
#22…
#12 AWG
#22…
#12 AWG
0.5…
4 mm2
300V
AC/DC
1.55" (39.4 mm)
0.31"
(8 mm)
Single-circuit fuse block.
Approvals
Voltage Rating
1492-WFB4250
1.55" (39.4 mm)
Note: Height dimension is measured
from top of rail to top of
terminal block.
1492-WFB424
1.55" (39.4 mm)
1492-WFB4
Dimensions are not intended to
be used for manufacturing
purposes.
CSA
IEC
300V
AC/DC
500V
AC/DC
15 A
15 A
15 A ➊
#22…
#12 AWG
#22…
#12 AWG
0.5…
4 mm2
300V
AC/DC
2.0" (50.7 mm)
0.31"
(8 mm)
Single-circuit fuse block with neon
blown fuse indicator.
CSA
IEC
300V
AC/DC
500V
AC/DC
15 A
15 A
15 A ➊
#22…
#12 AWG
#22…
#12 AWG
0.5…
4 mm 2
300V
AC/DC
Non-Indicating
LED
Neon
Leakage Current
—
2mA @ 24V
1mA @ 264V
Working Voltage
Per Fuse Rating
10-57V AC/DC
85-264V AC
5 x 20 mm
5 x 20 mm
5 x 20 mm
0.31" (8 mm)
0.31" (8 mm)
0.31" (8 mm)
5.0…5.6 lb-in. (0.6 Nm)
5.0…5.6 lb-in. (0.6 Nm)
5.0…5.6 lb-in. (0.6 Nm)
38 pcs./ft (125/m)
38 pcs./ft (125/m)
38 pcs./ft (125/m)
–40…+195°F (–40…+90°C)
–40…+195°F (–40…+90°C)
–40…+195°F (–40…+90°C)
Fuse Size (Not Supplied)
Wire Strip Length
Recommended Tightening Torque
Density
Insulation Temperature Range
Terminal Blocks
Terminal Block
Accessories (page 185)
Mounting Rails:
1 m Symmetrical DIN (Steel)
Pcs./
Pkg.
Cat. No.
1492-WFB4
50
Cat. No.
Pcs./
Pkg.
Cat. No.
Pcs./
Pkg.
Cat. No.
Pcs./
Pkg.
1492-WFB424
50
1492-WFB4250
50
Cat. No.
Pcs./
Pkg.
Cat. No.
Pcs./
Pkg.
199-DR1
5
199-DR1
5
199-DR1
5
1 m Symmetrical DIN (Aluminum)
1492-DR5
5
1492-DR5
5
1492-DR5
5
1 m Hi-Rise Sym. DIN (Aluminum)
1492-DR6
2
1492-DR6
2
1492-DR6
2
1 m Angled Hi-Rise Sym. DIN (Steel)
1492-DR7
2
1492-DR7
2
1492-DR7
2
Not Required
—
Not Required
—
Not Required
—
End Anchors:
DIN Rail — Normal Duty
1492-EA35
50
1492-EA35
50
1492-EA35
50
DIN Rail — Heavy Duty
1492-EAH35
10
1492-EAH35
10
1492-EAH35
10
1492-SJFB8-10
10
1492-SJFB8-10
10
1492-SJFB8-10
10
1492-PPSL3
50
1492-PPSL3
50
1492-PPSL3
50
1492-GM35
10
1492-GM35
10
1492-GM35
10
1492-SM8X12
5
1492-SM8X12
5
1492-SM8X12
5
1492-SM6X9
5
1492-SM6X9
5
1492-SM6X9
5
1492-MP ➋
10
1492-MP ➋
10
1492-MP ➋
10
End Barrier
Jumpers:
Side Jumper — 10-pole Insulated
Other Accessories:
Partition Plate
Group Marking Carrier
Marking Systems:
Snap-in Marker Card — For Base Block
For Handle
Individual Marker Tabs (single char.)
➊ IEC standards for 5 x 20 mm fuses do not include ratings above 6.3 A.
Accessories — Page 185
32
Bulletin 1492
IEC Terminal Blocks
Fuse Blocks, Continued
3.20" (81.3 mm)
Specifications
300V
AC/DC
Maximum Current
Wire Range (Rated Cross Section)
Indicator Type
1.85" (47 mm)
0.36"
(9.1 mm)
3.20" (81.3 mm)
0.36"
(9.1 mm)
Single-circuit fusible terminal block with Single-circuit fusible terminal block with
neon blown fuse indicator.
LED blown fuse indicator.
Approvals
Voltage Rating
1492-H6
1.85" (47 mm)
Note: Height dimension is measured
from top of rail to top of
terminal block.
1492-H5
1.85" (47 mm)
1492-H4
Dimensions are not intended to
be used for manufacturing
purposes.
CSA
IEC
300V
AC/DC
500V
AC/DC
300V
AC/DC
CSA
IEC
300V
AC/DC
500V
AC/DC
3.20" (81.3 mm)
Single-circuit fusible terminal block
without a blown fuse indicator.
300V
AC/DC
CSA
IEC
300V
AC/DC
500V
AC/DC
12 A
12 A
12 A
12 A
12 A
12 A
12 A
12 A
12 A
#30…
#12 AWG
#30…
#12 AWG
0.05…
4 mm2
#30…
#12 AWG
#30…
#12 AWG
0.05…
4 mm2
#30…
#12 AWG
#30…
#12 AWG
0.05…
4 mm 2
Neon
LED
Leakage Current
2 mA @ 300V
2 mA @ 24V
—
Working Voltage
100…300V AC
10…57V AC/DC
Per Fuse Rating
Fuse Size (Not Supplied)
Wire Strip Length
Recommended Tightening Torque
Density
Insulation Temperature Range
1/4" x 1-1/4"
1/4" x 1-1/4"
1/4" x 1-1/4"
0.38" (9.7 mm)
0.38" (9.7 mm)
3…7 lb-in. (0.3…0.8 Nm)
3…7 lb-in. (0.3…0.8 Nm)
3…7 lb-in. (0.3…0.8 Nm)
33 pcs./ft (109/m)
33 pcs./ft (109/m)
33 pcs./ft (109/m)
–40…+221°F (–40…+105°C)
–40…+221°F (–40…+105°C)
–40…+221°F (–40…+105°C)
Pcs./
Pkg.
Cat. No.
1492-H4
25
Cat. No.
Pcs./
Pkg.
Cat. No.
Terminal Block
(page 185)
Mounting Rails:
1 m Symmetrical DIN (Steel)
Non-Indicating
0.38" (9.7 mm)
Terminal Blocks
Accessories
0.36"
(9.1 mm)
Pcs./
Pkg.
Cat. No.
Pcs./
Pkg.
1492-H5
25
1492-H6
25
Cat. No.
Pcs./
Pkg.
Cat. No.
Pcs./
Pkg.
199-DR1
10
199-DR1
10
199-DR1
10
1 m Symmetrical DIN (Aluminum)
1492-DR5
10
1492-DR5
10
1492-DR5
10
1 m Hi-Rise Sym. DIN (Aluminum)
1492-DR6
2
1492-DR6
2
1492-DR6
2
1 m Angled Hi-Rise Sym. DIN (Steel)
1492-DR7
2
1492-DR7
2
1492-DR7
2
1492-N37
50
1492-N37
50
1492-N37
50
End Barrier
End Anchors:
DIN Rail — Normal Duty
1492-EA35
50
1492-EA35
50
1492-EA35
50
DIN Rail — Heavy Duty
1492-EAH35
10
1492-EAH35
10
1492-EAH35
10
1492-N49
10
1492-N49
10
1492-N49
10
1492-SJS
10
1492-SJS
10
1492-SJS
10
1492-GM35
10
1492-GM35
10
1492-GM35
10
1492-SM8X12
5
1492-SM8X12
5
1492-SM8X12
5
Jumpers:
Side Jumper — 10-pole Uninsulated
Side Jumper — Insulating Sleeve
Other Accessories:
Group Marking Carrier
Marking Systems:
Snap-in Marker Card
Accessories — Page 185
33
Bulletin 1492
IEC Terminal Blocks
Fuse Blocks, Continued
1492-W4P
Dimensions are not intended to
be used for manufacturing
purposes.
Note: Height dimension is measured
➊
from top of rail to top of
terminal block.
1.78" (45.3 mm)
Specifications
0.24"
(6 mm)
Pluggable terminal block.
Approvals
600V
AC/DC
Voltage Rating
Maximum Current
Wire Range (Rated Cross Section)
CSA
IEC
600V
AC/DC
800V
AC/DC
20 A
20 A
32 A
#22…
#12 AWG
#22…
#12 AWG
0.5…
2.5 mm2
Indicator Type
—
Wire Strip Length
0.35" (9 mm)
Recommended Tightening Torque
5.0…5.6 lb-in. (0.6 Nm)
Density
50 pcs./ft (166/m)
Insulation Temperature Range
–40…+195°F (–40…+90°C)
Working Voltage
—
Fuse Size (Not Supplied)
5 x 20 mm
Terminal Blocks
Cat. No.
Color:
Pcs./
Pkg.
Gray
1492-W4P
50
Red
1492-W4P-RE
50
Disconnect Plug
1492-DP4
50
Component Plug
1492-CP4 ➋
50
1492-FP4 ➌➍
50
Inserts:
Fuse Plug
Fuse Plug w/LED Blown Fuse Indication 1492-FP424 ➌➍ (shown)
Fuse Plug w/Neon Blown Fuse Indication
Accessories (page 185)
Mounting Rails:
1 m Symmetrical DIN (Steel)
50
1492-FP4250 ➌➍
50
Cat. No.
Pcs./
Pkg.
199-DR1
10
1 m Symmetrical DIN (Aluminum)
1492-DR5
10
1 m Hi-Rise Sym. DIN (Aluminum)
1492-DR6
2
1 m Angled Hi-Rise Sym. DIN (Steel)
1492-DR7
2
1492-EB3
50
End Anchors:
DIN Rail — Normal Duty
1492-EA35
50
DIN Rail — Heavy Duty
1492-EAH35
10
1492-N42 (2-pole)
1492-SJ6-10 (10-pole)
50
10
1492-PP3
50
End Barrier
Jumpers:
Insulated Side Jumper
Other Accessories:
Partition Plate
Marking Systems:
Snap-in Marker Card
Individual Marker Tabs (single char.)
1492-SM6X12
5
1492-MP ➎
10
➊ Overall height varies with plug-in component. For 1492-DP4, use 1.8" (45 mm); for 1492-CP4, use 2.2" (55.5 mm); and for 1492-FP4…, use 2.4"
(60.0 mm).
➋ Maximum current and voltage rating of component plug is 1 A @ 600V. Maximum current rating for the base terminal block is listed under
Specifications.
➌ Maximum current and voltage ratings for the fuse plug are 10 A and 250V,respectively. Maximum ratings for the base blocks are listed under
Specifications.
➍ See page 216 for Fuse Plug Specifications.
➎ Cat. no. is not complete. See page 186.
34