0-10 Volt Analog Output Representing Output Frequency of Drive I/O Terminal Block 1 Parmeters that need to be reprogrammed 2 File E / Utility Goup - Drive Memory 3 196 (Param Access Lvl) = 1 (Advanced) 4 5 6 0-10 Volts Out PowerFlex 70 7 24V Common 8 Digital In Common 9 +24V 22 - 23 + U V W Parameters that need to be reprogrammed Motor File J / Inputs & Outputs Group - Analog Outputs 342 (Analog Out1 Sel1) = 0 (Output Freq) 341 (Anlg Out Absolut) = Nibble 1 = XXX0 0 = 0 volts 5 volts 10 volts Reverse Max Speed Forward Max Speed Parameter 341 (Anlg Out Absolut) Default 0 means Disabled Disabled (0) = About 5 volts at 0Hz About 0 volts at Max Speed Reverse About 10 volts at Max Speed Forward 0 Hz 1 = 0 volts 10 volts Maximun Speed Minimun Speed Note: Forward or Reverse Enabled (1) = 0 to 10 volts Minimun to Maximun Speed for Forward or Reverse