PowerFlex 70 0-10 Volt Analog Output Representing Output

0-10 Volt Analog Output
Representing Output Frequency of Drive
I/O Terminal Block
1
Parmeters that need to be reprogrammed
2
File E / Utility
Goup - Drive Memory
3
196 (Param Access Lvl) = 1 (Advanced)
4
5
6
0-10 Volts
Out
PowerFlex 70
7
24V Common
8
Digital In Common
9
+24V
22
-
23
+
U
V
W
Parameters that need to be reprogrammed
Motor
File J / Inputs & Outputs
Group - Analog Outputs
342 (Analog Out1 Sel1) = 0 (Output Freq)
341 (Anlg Out Absolut) = Nibble 1 = XXX0
0 = 0 volts
5 volts
10 volts
Reverse
Max Speed
Forward
Max Speed
Parameter 341 (Anlg Out Absolut) Default 0 means Disabled
Disabled (0) = About 5 volts at 0Hz
About 0 volts at Max Speed Reverse
About 10 volts at Max Speed Forward
0 Hz
1 = 0 volts
10 volts
Maximun
Speed
Minimun
Speed
Note: Forward or Reverse
Enabled (1) = 0 to 10 volts Minimun to Maximun Speed for
Forward or Reverse