User Data Sheet

Drive Application Software
Application Set
Application Set Title
Drive Product
File Name for (AS)
Date / Firmware Rev.
Analog Speed Ref with Reverse
PowerFlex 700S AC Drive Phase II
AS_PF700SII_AnalogSpdRefwRev_A.dno
02/03/06
3.01
Attention:
This document and related file(s) are designed to
supplement configuration of the listed drive product. The
information provided does not replace the drive products
user manual and is intended for qualified personnel only.
Description:
Analog speed reference with 3Wire Start/Stop Control and reverse.
Limitations:
Options &
Notes:
1. See option in the parameter table.
2. Default configuration for 3Wire Control through digital inputs may be changed to 2Wire
Control or for operation through 20-COMM-x module.
Drive Input & Output Connections:
Inputs
Function
DI 1
DI 2
DI 3
Reverse
DI 4
Start
DI 5
Stop
DI 6
HW Enable
AI 1
Speed Reference
AI 2
AI 3
Outputs
Function
DO 1
DO 2
DO 3
AO 1
AO 2
AO 3
AS_PF700SII_AnalogSpdRefwRev_A.doc
Form Revision – A
Page 1 of 2
Description
0-10v
Description
Drive Application Software
Application Set
Parameter Configurations
Changes from Default Parameter Settings
Par
Name
Value
b0 = 0
153
Control Options
b6 = 1
b8 = 1
27
Speed Ref A Sel
Speed Ref 1
10
Speed Ref 1
11
32
33
827
828
829
802
804
805
808
810
811
Spd Ref1 Divide
Accel Time
Decel Time
DigIn3 Sel
DigIn4 Sel
DigIn5 Sel
Anlg In1 Scale
AI 1 Filt Gain
Anlg In1 BW
Anlg In2 Scale
AI 2 Filt Gain
Anlg In2 BW
100
10
10
Reverse
Start
Normal Stop
10
0.25
50
10
0.25
50
30
Min Spd Ref Lim
Dflt= -2170
31
Max Spd Ref Lim
Dflt= 2170
Link
800
AS_PF700SII_AnalogSpdRefwRev_A.doc
Form Revision – A
Page 2 of 2
Description
Bipolar SRef
Stop in Torq – Stop function if in torque control mode
3Wire Control
Base Speed reference
0 to 100% of Motor base speed
Scales the Speed Reference to a per unit value
Set per application requirements
Set per application requirements
Reverse Reference Input
Start input for 3Wire Control
Stop input for 3Wire Control
Scale AI1 for 0 to 10v = 0 to 100 (% Speed)
Light filtering
Light filtering
Scale AI1 for 0 to 10v = 0 to 100%
Light filtering
Light filtering
Adjust as need to allow required speed – should be
within 10% of max speed required
Adjust as need to allow required speed – should be
within 10% of max speed required