Bulletin 700-FS Timing Relays Overview/Product Selection Bulletin 700-FS Table Of Contents • • • • • Product Selection . . . . . . . 120 Accessories . . . . . . . . . . . . 122 Connection Diagrams . . . . 123 Specifications . . . . . . . . . . 126 Adjustable Function and Timing Range Timing Relays DIN Rail Mounted without Cost of Socket 22.5 mm Wide Multifunction or Single Functions Available as SPDT or DPDT Contact Output, 8 A Timing Ranges From 0.05s…60h Catalog Number Explanation 700 – FS H 3 U U23 First Position Bulletin Number Sixth Position Supply Voltages Second Position Type of Relay Fifth Position Fourth Position Time Ranges Assembly of Contacts Third Position Function Single-Function (With SPDT 1 C/O contacts) 700-FS A 3 A U23 Function Contact Outputs Time Ranges Supply Voltages A On-delay ➊ B Off-delay ➊ C On- and off-delay ➊ D One shot ➊ E Fleeting off-delay ➊ F Flasher (repeat cycle starts with pulse) ➊ G Flasher (repeat cycle starts with pause) ➊ I On-delay pulse generator ➊ J On-delay (pulse controlled) ➊ K One shot / watch dog (pulse controlled) ➊ L Pulse converter ➊ All functions: 3 1 Changeover contact (SPDT) 1 C/O A 0.05…1 s B 0.15…3 s C 0.5…10 s D 1.5…30 s E 0.05…1 min F 0.15…3 min G 0.5…10 min H 1.5…30 min I 0.05…1 h J 0.15…3 h K 0.5…10 h L 3.0…60 h U 0.05 s…60 h ➋ Z12 12V DC U23 24…48V DC 24…240V AC 50/60 Hz . Single Function (With 2PDT 2 C/O contacts) Functions Available Contact Outputs ON-Delay (DPDT) 2 C/O ON-Delay (DPDT) 2 C/O OFF-Delay (DPDT) 2 C/O OFF-Delay (DPDT) 2 C/O Time Ranges 0.05 s…60 h ➌ Supply Voltages 12V DC 24…48V DC 24…240V AC 50/60 Hz 12V DC 24…48V DC 24…240V AC 50/60 Hz ➊ Factory-stocked item. ➋ Valid for functions "A" and "B" only. ➌ The time range of "0.05 s…60 h" is selectable in 12 smaller ranges plus an ON and OFF function for maintenance needs. 120 Cat. No. Factorystocked Item 700-FSA4UZ12 700-FSA4UU23 ✔ 700-FSB4UZ12 700-FSB4UU23 ✔ Bulletin 700-FS Timing Relays Product Selection, Continued Multi-Function (This device offers you the flexibility of selecting one of 8 single timing functions.) Functions Available Contact Outputs M Multi-function timing relays 8 Single-functions: A, B, C, D, E, F, I, and L ON and OFF function additional (for installation and maintenance) note: See next page for function description. Time Ranges (SPDT) 1 C/O (SPDT) 1 C/O 0.05 s…60 h ➊ (DPDT) 2 C/O (DPDT) 2 C/O Supply Voltages 12V DC 24…48V DC 24…240V AC 50/60 Hz 12V DC 24…48V DC 24…240V AC 50/60 Hz Cat. No. Factorystocked Item 700-FSM3UZ12 ✔ 700-FSM3UU23 700-FSM4UZ12 ✔ 700-FSM4UU23 Special Function Functions Available Contact Outputs Time Ranges 0.05 s…60 h ➊ Flasher (Repeat cycle starting with pulse or pause) SPDT (1 C/O) 2 x0.05 s…60 h (2 ranges) OFF-delay without supply voltages (True OFF-delay)➌ SPDT (1 C/O) DPDT (2 C/O) 0.15 s…10 m ➋ 0.5 s…10 s 1.5…30 s 2 N.O. + 1 common 0.05 s…1 min. 0.15…3 min. 0.5…10 min. Star-Delta Supply Voltages 12V DC 24…48V DC 24…240V AC 50/60 Hz 12V DC 24…48V DC 24…240V AC 50/60 Hz 24…240V DC 24…240V AC 50/60 Hz 24…48V DC 24…240V AC 50/60 Hz Factorystocked Item Cat. No. 700-FSH3UZ12 700-FSHUU23 700-FSH3VZ12 700-FSH3VU23 ✔ 700-FSQ3QU18 ✔ 700-FSQ4QU18 ✔ 700-FSY2CU23 700-FSY2DU23 700-FSY2EU23 700-FSY2FU23 700-FSY2GU23 ➊ The time range of "0.05 s…60 h" is selectable in 12 smaller ranges plus an ON and OFF function for maintenance needs. ➋ This time range is selectable in four smaller ranges: 0.15 s…2.5 s, 0.5 s…10 s,4 s…80 s, 30 s…10 min. ➌ Due to shock during shipment, the state of the contacts should be verified before initial use. Multi-Function Timing Relay Function and Time Range Settings Description Up Down 700-FSM4 Multi-function timing relays 700-FSM3U includes 10 setting functions: (A)On-delay (B)Off-delay A (C)On- and off-delay (D)One shot (E)Fleeting off-delay (F)Flasher (repeat cycle starts with pulse) (I)On-delay pulse generator (L)Pulse converter (On)ON-Function * (Off)OFF-Function * * (for installation and maintenance) Note: Switch ⊗ is on DPDT relays only. When switch is down, one contact is instantaneous and one is timed. When switch is up, both contacts are timed. SPDT DPDT Multi-Time Setting Range 0.05 s…60 h (1 s)0.05…1 s (3 s)0.15…3 s (10 s)0.5…10 s (1 min)0.05…1 min (3 min)0.15…3 min (10 min)0.5…10 min (1 h)0.05…1 h (3 h)0.15…3 h (10 h)0.5…10 h 10h (60 h)3.…60 h 121 Bulletin 700-FS Timing Relays Accessories Qty. Cat. No. Setting Knob with Scale (for time setting without tools) 10 700-FSK Panel Mounting Adapter For surface mounting according to drilling plan EN 50 002 5 199-FSA Labeling Sheet: 10 sheets with 105 self-adhesive paper labels each, 6 x 17 mm 10 100-FMS Marking Tag Sheet: 10 sheets with 160 perforated paper labels each, 6 x 17 mm 10 100-FMP Transparent Cover: To be used with marking tag sheets 100 100-FMC 100 100-FMA2 ➊ Description Marking Tag Carrier: To be used with label strip System Bulletin 1492-W ➊ Cat. No. 100-FMA2 is only a marking tag carrier. Please refer to the Terminal Block Accessories section, page 12-174 of publication A113 for appropriate marker cards to be used with this carrier. 122 Bulletin 700-FS Timing Relays 700-FS Function and Connection Diagrams (A) On-Delay (B) Off-Delay (Min. Pulse AC 50 ms…DC 30 ms) ➊ 1c/o (SPST) Output 1c/o (SPST) Output ➊ 2 c/o (DPDT) Output 1 2 c/o (DPDT) Output 1 Output 2 Output 2 Output 2 ➋ ➋ Output 2 ➌ ➋ (C) On- and Off-Delay ➌ ➋ (D) One Shot ➊ Output Output ➌ ➌ (E) Fleeting Off-Delay (Min. Pulse AC 50 ms…DC 30 ms) (F) Flasher (Repeat Cycle Starts with Pulse) ➊ Output Output ➌ ➌ (G) Flasher (Repeat Cycle Starts with Pause) Output (I) On-Delay Pulse Generator Output ➌ (J) On-Delay (Pulse Controlled) (K) One Shot/ Watch Dog (Pulse Controlled) ➊ ➊ Output Output (Off) OFF-Function (On) ON-Function (L) Pulse Converter (Min. Pulse AC 50 ms…DC 30 ms) ➊ Output 1 Output 1 Output 2 Output 2 Output ➌ Cleverly Designed Function Display LED (Green) Output in rest position, no timing Output in rest position, time running Output in operation position, no timing Output in operation position, time running ➊ A voltage other than the supply voltage can be used at B1, but must be within voltages specified on timer. ➋ Output 2 is selectable as instantaneous contact with sliding switch (⊗) on front panel (instantaneous when switch is down, timed when switch is up). ➌ Available on multifunction "M," and single function "A" or "B" option timing relays along with code "4" (2PDT contacts). Bridge or potentiometer 10 kΩ, min. 0.25 W (low voltage) for external time setting. Set timer dial to 0.0. 123 Bulletin 700-FS Timing Relays Connection Diagrams, Continued Special Function Flasher (Repeat Cycle Starting with Pulse or Pause) Timing Relays Description t2 Setting Up Switch Down 1 Range Setting Separate Range Settings t1 Setting 700-FSH3U 700-FSH3V Supply Voltages (A1/A2) Z12 12V DC U23 24…48V DC, 24…240V AC, 50/60 Hz Function Diagram / Connection Diagram (H) Flasher (Repeat Cycle Starting with Pulse or Pause) The repeat cycle timer permits different settings for on and off times. The following operating modes are possible: • Oscillating mode; repeat cycle starts with voltage applied at A1 and B1, and continues to repeat until voltage is off. • One cycle mode; started by energizing B1 with voltage on A1 and A2. • Output starts with pulse or pause (switch ⊗ Up or Down). • 700-FSH3U provides (1) range setting for t1 and t2. 700-FSH3V provides (2) range settings for t1 and t2. Supply Voltage Controlled, Oscillating Mode Starting with Pause — Switch ⊗ is Up Output Supply Voltage Controlled, Oscillating Mode Starting with Pulse — Switch ⊗ is Down Output Pulse Controlled, Output Starts With Pause (Min. Pulse AC 50 ms — DC 30 ms) — Switch ⊗ is Up One Cycle Mode — Voltage Supplied at A1 and A2, then Pulsing “s” to Energize B1 will Initiate One Cycle. Output Pulse Controlled, Output Starts with Pulse (Min. Pulse AC 50 ms — DC 30 ms) — Switch ⊗ is Down One Cycle Mode — Voltage Supplied at A1 and A2, then Pulsing “s” to Energize B1 will Initiate One Cycle. Output Note: If B1 is pulsed, a one full time cycle consisting of t1 and t2 is completed. LED Operation Chart — Green LED Output at Shelf State, No Timing _ LED Off Output at Shelf State, Time is Running _ LED Flashing Output NO Contact is Closed, No Timing _ LED On Output NO Contact is Closed, Time is Running _ LED Long Flashing 124 Bulletin 700-FS Timing Relays Connection Diagrams, Continued Function Diagram/Connection Diagram (Q) Off-Delay without Supply Voltage (True Off-Delay) — When input power is turned on, the output contact changes state. When the power is removed, the time delay begins. The output contact returns to shelf state at the end of the time delay. Note: Min. pulse (t) required: 24V DC: 200 ms 24V AC: 325 ms 240V DC: 200 ms 240V AC: 175 ms Output Output 1 Output 2 LED A1/A2 18 15 16 28 25 26 (Y) Star-Delta Timing Relay — When power is applied, the output contact 17/18(Y) changes state. After the time setting, the output contact 17/18(Y) returns to shelf state. After the fixed time (50… 60 ms), the output contact 17/28∆ changes state. Both output contacts return to shelf state whenever the power is removed. 125 Bulletin 700-FS Timing Relays Specifications ➊ Time Characteristics (according to VDE 0435, Part 2021) Setting Accuracy Repeatability Tolerance ±5% of full scale ±0.2% of the setting values Voltage: ±0.001%/%∆U Temperature: ±0.025%/°C Supply Supply Voltages Voltage Tolerance Power Consumption Time Energized Reset Time Voltage Interruption Cable Length (Supply Voltage Control) Cable Length Vibration Resistance Shock Resistance Protection Class 24…48V DC and 24…240V AC, 50/60 Hz (multi voltage) –20…+20% (DC), –15…+10% (AC) 0.5 W at 24V DC, 5 VA at 240V AC 100% 50 ms ≤ 20 ms without reset (supply voltage) Weight Approval Ambient Temperature Max. 250 m (800 ft) Terminals Pulse Control (B1) Pulse Duration Input Voltage Input Current Max. Leakage Current Climatic Withstand ≥ 50 ms (AC), ≥ 30 ms (DC) Supply voltage range 1 mA 400 micro Amps Max. 250 m (800 ft) without parallel load between B1 and A2 Max. 50 m (160 ft) with load (<3 kΩ) between B1 and A2 Mounting Disposal Outputs Contact Type Switching Capacity Short-Circuit Resistance Life State Indicator Relay as changeover switch Voltage: 440V AC Current Ith (AC-1): 8 A (5 A for 700-FSQ) Power: 2000 VA According to IEC 947-5-1: 3 A/440V AC (inductive load, AC 14) 3 A/250V AC (inductive load, AC 15) 1 A/24V DC (inductive load, DC 13) According to UL 508: 1.5 A/250V AC (B300) 3 A/120V AC (B300) 10 A gL Mechanical: 30 million operations Electrical operations: 4 Mil. at 1 A/250V AC, cos ϕ = 1 0.2 Mil. at 6 A/250V AC, cos ϕ = 1 1.5 Mil. at 1 A/250V AC, cos ϕ = 0.3 0.3 Mil. at 3 A/250V AC, cos ϕ = 0.3 0.5 Mil. at 6 A/24V DC, resistive 2 Mil. at 4 A/24V DC, resistive 2 Mil. at 0.2 A/230V DC, resistive 1 Mil. at 0.4 A/24V DC, L/R = 20 ms 1 Mil. at 0.2 A/110V DC, L/R = 20 ms 1 Mil. at 0.1 A/230V DC, L/R = 20 ms 1 LED, combination signal General Data 2 kVAC/50 Hz test voltage according to VDE 0435 and 6 kV 1.2/50 µs surge voltage according to IEC 947-1 between all inputs and outputs Performance of following requirements: Surge capacity of the supply voltage according to IEC 1000-4-5: 4 kV 1.2/50 µs Burst according to IEC 1000-4-4: EMC/Interference Immunity 6 kV 6/50 ns ESD discharge according to IEC 1000-4-2: Contact 8 kV, air 8 kV Electromagnetic HF field according to IEC 8013 and conducted electromagnetic HF signal according to IEC 801-6: Level 3 Electromagnetic fields according to EN 55 022: EMC/Emission class B Safe Isolation According to VDE 106, part 101 Insulation Characteristics ➊ Performance Data — See page Important-2, publication A113. 126 Certifications Standards 56 Cycles (24 h) at 25…40°C and 95% relative humidity according to IEC 68-2-30 and IEC 68-2-3 4 g in 3 axes at 10…500 Hz, test FC according to IEC 68-2-6 50 g according to IEC 68-2-27 Enclosure:IP 40 IP 30 (Single-function) Terminal:IP 20 according to IEC 947-1 100 g UL, C-UL Open: –25…+60°C Enclosed: –25…+45°C Storage: –40…+85°C Screw terminal M3.5 for Number 2 Posidrive, Philips, and slotted screws. Suitable for power screwdriver. Rated tightening torque 8.8 lb.-in. (0.8 N•m, max. 1.2 N•m). Dual-chamber system for terminal cross-sections of 1 x 0.5 mm2…2 x 2.5 mm2 (solid) or stranded 2 x 2.5 mm2 (flexible with sleeve), #20…14 AWG. Finger protection according to VDE 0106. Front mounting; For snap-on mounting on 35 mm DIN Rail or screw fixing by adapter and 2 screws (M4 type) Synthetic material without dioxin according to EC/ EFTA notification Number 93/0141/D electrical contacts with cadmium cUL Recognized, File E14840, cULus Listed, File E14840,Guide NKCR,CE Marked (per EU Low Voltage Directive 73/23 EEC 93/68 EEC: per Electromagnetic Compatibility Directive 89/336 EEC 92/31 EEC 93/681 EEC) EN 60947-1,EN 60947-5-1, EN 50081-1, IEC 947, UL 508, CSA 22.2