G3NE 2 - OMRON Industrial Automation

Solid State Relays
G3NE
CSM_G3NE_DS_E_3_2
Compact, Low-cost, SSR Switching 5 to 20 A
• Wide load voltage range: 75 to 264 VAC. Both 100-V and
200-V loads can be handled with the same model.
• Dedicated, compact aluminum PCB and power elements used.
• Built-in varistor effectively absorbs external surges.
• Quick-connect #110 input terminals and #250 output
connections. (#187 input terminals and #250 output
connections are available.)
• “-US” models certified by UL, CSA, and IEC/EN (TÜV).
Refer to Safety Precautions for All Solid State
Relays.
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
Model Number Structure
■ Model Number Legend
G3NE-@@@@-@-@
2 3 4 5 6
1
7
1. Basic Model Name
G3NE:
Solid State Relay
2. Rated Load Power Supply Voltage
2:
200 VAC
3. Rated Load Current
05:
5A
10:
10 A
20:
20 A
4. Terminal Type
T:
Quick-connect terminals
5. Zero Cross Function
Blank:
Equipped with zero cross function
L:
Not equipped with zero cross function
6. Special Specifications
Blank:
Standard models
2:
#187 input terminals
7. Certification
US:
Certified by UL, CSA, and TÜV
Ordering Information
■ List of Models
Isolation
Phototriac
Zero cross
function
Yes
Indicator
No
Rated output load
5 A at 100 to 240 VAC
10 A at 100 to 240 VAC
20 A at 100 to 240 VAC
No
5 A at 100 to 240 VAC
10 A at 100 to 240 VAC
20 A at 100 to 240 VAC
Rated input voltage
(See note 1.)
5, 12, 24 VDC
(See note 2.)
Model
G3NE-205T-US
G3NE-205T-2-US
G3NE-210T-US
G3NE-210T-2-US
G3NE-220T-US
G3NE-220T-2-US
G3NE-205TL-US
G3NE-205TL-2-US
G3NE-210TL-US
G3NE-210TL-2-US
G3NE-220TL-US
G3NE-220TL-2-US
Note: 1. The rated input voltage depends on the ambient temperature. For details, refer to Load Current vs. Ambient Temperature in Engineering
Data on page 3.
2. When ordering, specify the input voltage.
3. Refer to List of Certified Models for a list of products that comply with safety standards. When ordering a UL, CSA, and EN(TÜV) certified
model, add “-US” to the model number.
1
G3NE
■ Accessories (Order Separately)
Heat Sinks
The following heat sinks are thin and can be DIN-track mounted.
See Dimensions for details.
Model
Applicable SSR
Y92B-N50
G3NE-205T(L)(-2)-US/-210T(L)(-2)-US
Y92B-N100
G3NE-220T(L)(-2)-US
Specifications
■ Ratings (at an Ambient Temperature of 25°C)
Input
Rated voltage
Operating voltage
Voltage level
Must operate
Input impedance
Must release
With zero cross function Without zero cross function
5 VDC
4 to 6 VDC
4 VDC max.
250 Ω±20%
300 Ω±20%
12 VDC
9.6 to 14.4 VDC
9.6 VDC max.
600 Ω±20%
800 Ω±20%
24 VDC
19.2 to 28.8 VDC
19.2 VDC max.
1.6 kΩ±20%
1 VDC min.
Note: Each model has 5-VDC, 12-VDC, and 24-VDC input versions.
Output
Model
Applicable load
Rated load voltage Load voltage range
Load current
(See note 1.)
With heat sink
G3NE-205T(L)(-2)-US
100 to 240 VAC
75 to 264 VAC
Inrush current
Without heat sink
0.1 to 5 A at 40°C
0.1 to 5 A at 40°C
60 A (60 Hz, 1 cycle)
G3NE-210T(L)(-2)-US
0.1 to 10 A at 40°C
(See note 2.)
0.1 to 5 A at 40°C
150 A (60 Hz, 1 cycle)
G3NE-220T(L)(-2)-US
0.1 to 20 A at 40°C
(See note 2.)
0.1 to 5 A at 40°C
220 A (60 Hz, 1 cycle)
Note: 1. The load current varies depending on the ambient temperature. Refer to Load Current vs. Ambient Temperature under Engineering Data
for details on page 3.
2. These values apply when using a dedicated heat sink or a radiation plate of specified size.
■ Characteristics
Item
G3NE-2@@T(-2)-US
G3NE-2@@TL(-2)-US
Operate time
1/2 of load power source cycle + 1 ms max.
1 ms max.
Release time
1/2 of load power source cycle + 1 ms max.
Output ON voltage drop
1.6 V (RMS) max.
Leakage current
2 mA max. (at 100 VAC)
5 mA max. (at 200 VAC)
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min
Vibration resistance
Destruction: 10 to 55 to 10 Hz, 0.75-mm single amplitude
Shock resistance
Destruction: 1,000 m/s2
Ambient temperature
Operating: –30°C to 80°C (with no icing or condensation)
Storage: –30°C to 100°C (with no icing or condensation)
Ambient humidity
Operating: 45% to 85%
Certified standards
UL508 File No.E64562/CSA C22.2 (No.0, No.14) File No. LR35535
TÜV R9051064 (VDE0435) (EN60950)
EMC
Emission: EN55011 Group 1 Class B
Immunity: EN61000-6-2
Weight
Approx. 37 g
2
G3NE
Engineering Data
Load Current vs. Ambient Temperature
G3NE-205T(L)(-2)-US
G3NE-210T(L)(-2)-US
With standard heat sink (Y92B-N100) or
aluminum plate measuring 300 mm x
300 mm x t3 mm (W x H x D)
Load current (A)
Without heat sink
Load current (A)
With standard heat sink (Y92B-N50)
or aluminum plate measuring 100 mm
x 100 mm x t2 mm (W x H x D)
Without heat sink
Load current (A)
G3NE-220T(L)(-2)-US
Ambient temperature (°C)
Ambient temperature (°C)
Ambient temperature (°C)
Without heat sink
One Cycle Surge Current: Non-repetitive
Note: Keep the inrush current to half the rated value if it occurs repetitively.
Energized time (ms)
G3NE-220T(L)(-2)-US
Inrush current (A. Peak)
G3NE-210T(L)(-2)-US
Inrush current (A. Peak)
Inrush current (A. Peak)
G3NE-205T(L)(-2)-US
Energized time (ms)
Energized time (ms)
3
G3NE
Dimensions
Note: All units are in millimeters unless otherwise indicated.
G3NE-205T(L)/210T(L)/220T(L)(-2)-US
3.5 dia. hole
Terminal Arrangement/
Internal Connections
(Top View)
47.5
max.
37.5 max.
14.5
Input
voltage
Two #110 (t = 0.5) (Faston
tab or equivalent)*
7.1
2.9
6.5
Input
Two #250 (t = 0.8) (Faston
tab or equivalent)
Output
4−
Load
2
7.95
6
11.5 max.
3
Load power
supply
Mounting Holes
Two, 3.5-dia. or M3 holes
* G3NE-2@@T(L)-2-US: Two, #187 (t=0.5) (Faston tab or equivalent)
Heat Sink
Y92B-N50
1
3+
30+0.5
30±0.2
Mounting Holes
4.6 dia. hole
Two, M3 holes
Two, M4 holes
Two, 3.2-dia.
holes
44 max. 30
35 30.5±0.3
47.6
5.6
5
77 max.
90±0.3
100 max.
Y92B-N100
4.6 dia. hole
Two, M3 holes
47 max.
6
4.5
51 max.
Weight: approx. 200 g
35±0.2
Two, M4
holes
Two, 3.2-dia. holes
Mounting Holes
71 max. 30
35 30.5±0.3
90±0.4
Two, 4.4-dia.
or M4 holes
75 max.
90±0.4
47.6
77 max.
5
5.6
28
100 max.
13
4.5
Two, 4.4-dia.
or M4 holes
90±0.3
100 max.
35±0.2
Weight: approx. 400 g
Safety Precautions
■ Precautions for Correct Use
■ Thermal Resistance Rth (Back
of Junction SSR)
Please observe the following precautions to prevent failure to
operate, malfunction, or undesirable effect on product performance.
G3NE-205T (L) 2.72
Refer to Safety Precautions for All Solid State Relays.
Do not apply excessive force to the terminals. Be careful when
pulling or inserting the terminal clips for the Quick Connector (QC).
When attaching a heat sink to the G3NE, in order to facilitate heat
dissipation, apply heat-conductive grease on the heat sink.
For DIN Track mounting, use a separately sold Heat Sink. Refer to
information on the G3NA.
G3NE-210T(L): Y92B-N50
G3NE-220T(L): Y92B-N100
Tighten the mounting screws of the heat sink with a torque of 0.59 to
0.98 N·m.
Model
Thermal resistance (°C/W)
G3NE-210T (L) 2.12
G3NE-220T (L) 2.22
■ EMC Directive Compliance
The G3NE complies with EMC Directives under the following
conditions ("-US" models only).
10 m max.
Load
Input
G3NE-US
Output
Film capacitor:
• 1 µF, 250 VAC
• Connect a film capacitor to the load power supply.
• The input cable must be less than 10 m.
4
G3NE
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
In the interest of product improvement, specifications are subject to change without notice.
5
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
 Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
 Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
 Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
2012.8
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2012 All Right Reserved.