ETC G3NA-225B

Solid State Relay
G3NA
A Wide Range of Models with 5- to 40-A
Output Currents and Up to
480-VAC/200-VDC Output Voltages
■
■
■
■
■
■
All models feature the same compact dimensions
to provide a uniform mounting pitch
Built-in MOV effectively absorbs external surges
Operation indicator (red LED) enables monitoring
operation
Protective cover for greater safety
Standard models approved by UL/CSA
AC and DC input versions available
Ordering Information
To Order: Select the part number and add the desired rated input voltage, (e.g., G3NA-240B-100 to 120 VAC).
Isolation
Phototriac
Photocoupler
Zero cross
function
Yes
Indicator
Yes
Rated output load
(Applicable output load)
5 A at 24 to 240 VAC*
(19 to 264 VAC)
10 A at 24 to 240 VAC*
(19 to 264 VAC)
Photocoupler
Yes
Yes
—
Phototriac
Yes
Photocoupler
Yes
Yes
Photocoupler
Yes
Yes
Phototriac
Yes
Yes
Photocoupler
Yes
Yes
10 A at 200 to 480 VAC*
(180 to 528 VAC)
10 A at 5 to 200 VDC*
(4 to 220 VDC)
20 A at 24 to 240 VAC*
(19 to 264 VAC)
20 A at 200 to 480 VAC*
(180 to 528 VAC)
25 A at 24 to 240 VAC*
(19 to 264 VAC)
25 A at 200 to 480 VAC*
(180 to 528 VAC)
40 A at 24 to 240 VAC*
(19 to 264 VAC)
40 A at 200 to 480 VAC*
(180 to 528 VAC)
Rated input voltage
Part number
5 to 24 VDC
100 to 120 VAC
200 to 240 VAC
5 to 24 VDC
100 to 120 VAC
200 to 240 VAC
5 to 24 VDC
100 to 240 VAC
5 to 24 VDC
100 to 240 VAC
5 to 24 VDC
100 to 120 VAC
200 to 240 VAC
5 to 24 VDC
100 to 240 VAC
5 to 24 VDC
100 to 120 VAC
200 to 240 VAC
5 to 24 VDC
100 to 240 VAC
5 to 24 VDC
100 to 120 VAC
200 to 240 VAC
5 to 24 VDC
100 to 240 VAC
G3NA-205B
* Loss time increases under 75 VAC.
NOTE:
When ordering a TÜV-approved model, add “-UTU” to the model number as shown below:
Example: G3NA-210B-UTU
G3NA-210B
G3NA-410B
G3NA-D210B
G3NA-220B
G3NA-420B
G3NA-225B
G3NA-425B
G3NA-240B
G3NA-440B
G3NA
G3NA
■ ACCESSORIES
Heat Sinks
Types
Standard mount
Track mount
Applicable solid-state relays
G3NA-205B, G3NA-210B, G3NA-D210B, G3NA-220B, G3NA-410B, G3NA-420B
G3NA-225B, G3NA-240B, G3NA-425B, G3NA-440B
G3NA-440B
G3NA-205B, G3NA-210B, G3NA-D210B, G3NA-410B
G3NA-220B, G3NA-420B
G3NA-225B, G3NA-240B, G3NA-425B, G3NA-440B
Part number
Y92B-A100
Y92B-A150N
Y92B-A250
Y92B-N50
Y92B-N100
Y92B-N150
Mounting Track and Accessories
Description
Mounting bracket for G3NA-240B. Changes pitch to 56 mm (2.21 in.) from 47.5 mm (1.73 in.),
the same pitch as G3N-240B.
DIN Rail Track, 50 cm (1.64 feet) length; use with Y92B-N■
■ ■ ■ heat sinks
DIN Rail Track, 1 m (3.28 feet) length; use with Y92B-N■
■ ■ ■ heat sinks
Spacer
End cap
Part number
R99-11
PFP-50M
PFP-100M
PFP-S
PFP-M
Specifications
■ INPUT RATINGS
(Ambient temperature: 25°C [77°F])
Type
G3NA-2■
■ ■B
■
G3NA-4■
■ ■B
■
G3NA-D210B
Rated
voltage
Operating
voltage range
Impedance
5 to 24 VDC
100 to 120 VAC
200 to 240 VAC
5 to 24 VDC
100 to 240 VAC
5 to 24 VDC
100 to 240 VAC
4 to 32 VDC
75 to 132 VAC
150 to 264 VAC
4 to 32 VDC
75 to 132 VAC
4 to 32 VDC
75 to 132 VAC
7 mA max. (see note 2)
36 kΩ ±20%
72 kΩ ±20%
5 mA max. (see note 2)
72 kΩ ±20%
5 mA max. (see note 2)
72 kΩ ±20%
Voltage Level
Must operate voltage
4 VDC max.
75 VAC, max. (see note 3)
150 VAC max. (see note 3)
4 VDC max.
75 VAC max.
4 VDC max.
75 VAC max.
Must release voltage
1 VDC min.
20 VAC min. (see note 3)
40 VAC min. (see note 3)
1 VDC min.
20 VAC min.
1 VDC min.
20 VAC min.
Note: 1. The input impedance is measured at the maximum value of the rated supply voltage (for example, with the model rated at
100 to 120 VAC, the input impedance is measured at 120 VAC).
2. With constant current input circuit system.
3. Refer to the "Characteristic Data" for further details.
■ OUTPUT RATINGS
Type
Applicable load
Rated
load voltage
Load
voltage range
G3NA-205B
G3NA-210B
G3NA-410B
G3NA-220B
G3NA-420B
G3NA-225B
G3NA-425B
G3NA-240B
G3NA-440B
G3NA-D210B
24 to 240 VAC
24 to 240 VAC
200 to 480 VAC
24 to 240 VAC
200 to 480 VAC
24 to 240 VAC
200 to 480 VAC
24 to 240 VAC
200 to 480 VAC
5 to 200 VDC
19 to 264 VAC
19 to 264 VAC
180 to 528 VAC
19 to 264 VAC
180 to 528 VAC
19 to 264 VAC
180 to 528 VAC
19 to 264 VAC
180 to 528 VAC
4 to 220 VDC
*When the appropriate size OMRON heat sink is used.
2
Load current
With heat sink*
0.1 to 5 A
0.1 to 10 A
0.2 to 10 A
0.1 to 20 A
0.2 to 20 A
0.1 to 25 A
0.1 to 25 A
0.1 to 40 A
0.2 to 40 A
0.1 to 10 A
Without heat sink
0.1 to 3 A
0.1 to 4 A
0.2 to 4 A
0.1 to 4 A
0.2 to 4 A
0.1 to 4 A
0.1 to 4 A
0.1 to 6 A
0.2 to 6 A
0.1 to 4 A
Surge current
60 A (60 Hz, 1 cycle)
150 A (60 Hz, 1 cycle)
150 A (60 Hz, 1 cycle)
220 A (60 Hz, 1 cycle)
220 A (60 Hz, 1 cycle)
220 A (60 Hz, 1 cycle)
220 A (60 Hz, 1 cycle)
440 A (60 Hz, 1 cycle)
440 A (60 Hz, 1 cycle)
20 A (10 ms)
G3NA
G3NA
■ CHARACTERISTICS
Type
Operate time
Release time
DC input
AC input
DC input
AC input
Output ON voltage drop
Leakage current
Insulation resistance
Dielectric strength
Vibration
Shock
Ambient temperature
Malfunction
Malfunction
Operating
Storage
Humidity
Weight
G3NA-205B, -210B,
-220B, -225B
G3NA-240B
1/2 of load power source cycle + 1 ms max.
1 1/2 of load power source cycle + 1 ms max.
1/2 of load power source cycle + 1 ms max.
1 1/2 of load power source cycle + 1 ms max.
1.6 V (RMS) max.
1.6 V (RMS) max.
5 mA max. at 100 VAC
10 mA max. at 200 VAC
100 MΩ min at 500 VDC
2,500 VAC, 50/60 Hz for 1 minute
10 to 55 Hz, 1.5 mm double amplitude
1,000 m/s2 (approx. 100G)
-30° to 80°C (-22° to 176°F) with no icing
-30° to 100°C (-22° to 212°F) with no icing
45% to 85% RH
Approx. 60 g (2.1 oz.)
Approx. 70 g (2.5 oz.)
G3NA-410B, -420B,
-425B, -440B
G3NA-D210B
1 ms max.
30 ms max.
5 ms max.
30 ms max.
1.8 V (RMS max.)
1.5 V max.
10 mA max.
5 mA max.
at 200 VAC
at 200 VDC
20 mA max. at 400 VAC
Approx. 80 g (2.8 oz.)
Approx. 70 g (2.5 oz.)
Note: Data shown are of initial value.
■ CHARACTERISTIC DATA
Load Current vs. Ambient Temperature Characteristics
G3NA-210B
G3NA-410B
G3NA-220B
G3NA-420B
Ambient temperature (°C)
G3NA-225B
G3NA-425B
Load current (A)
Load current (A)
Load current (A)
G3NA-205B
Ambient temperature (°C)
G3NA-440B
Ambient temperature (°C)
Load current (A)
Load current (A)
Load current (A)
G3NA-240B
Ambient temperature (°C)
Ambient temperature (°C)
Ambient temperature (°C)
3
G3NA
G3NA
■ CHARACTERISTIC DATA (continued)
Load Current vs. Ambient Temperature Characteristics
Load current (A)
G3NA-D210B
Ambient temperature (°C)
Surge Current Resistivity
G3NA-210B
G3NA-410B
Energizing time (ms)
G3NA-240B
G3NA-440B
Inrush current (A), peak
Energizing time (ms)
Inrush current (A), peak
Inrush current (A), peak
G3NA-D210B
Energizing time (ms)
4
G3NA-220B, G3NA-225B,
G3NA-420B, G3NA-425B
Inrush current (A), peak
Inrush current (A), peak
G3NA-205B
Energizing time (ms)
Energizing time (ms)
G3NA
G3NA
Heat sink size (cm2)
Heat Sink Size vs. Load Current
G3NA-220B
Load current (A)
Note: The heat sink size refers to the combined area of the sides of the heat sink that radiate heat. For example, when a current of
18 A is allowed to flow through the SSR at 40°C, the graph shows that the heat sink size is about 450 cm2. Therefore, if the
heat sink is square, one side of the heat sink must be 15 cm (152 x 2 = 450) or longer.
Dimensions
In the case of surface mounting, a 30% derating of load current is required.
Unit: mm (inch)
■ SOLID-STATE RELAYS
G3NA-205B, G3NA-210B, G3NA-220B,
G3NA-225B, G3NA-410B,
G3NA-420B, G3NA-425B
4.5 (0.18) dia.
58
(2.28)
max.
Terminal arrangement/
Internal connections
(Top view)
Four M4 x 10 (0.39)
44
(1.73)
Two,
4.4 (0.17) dia. or M4
Load
47.5
(1.87)
Mounting holes
(Bottom view)
Load
power
supply
Load
Operation
indicator
4.5 (0.18)
13.8 (0.54)
25 (0.98)
1
2
(-)
4
(+)
3
Input
47.6 ± 0.2
(1.87 ± 0.01)
25 (0.98) max.
43 (1.69) max.
27 (1.06) max.
G3NA-240B, G3NA-440B
4.5 (0.18) dia.
Terminal arrangement/
Internal connections
(Top view)
Two,
M5 x 12 (0.47)
Mounting holes
(Bottom view)
Two,
4.4 (0.17) dia. or M4
58
(2.28)
min.
Load
Load
power
supply
44
(1.73)
47.5
(1.87)
Load
1
Operation
indicator
4.5 (0.18)
25 (0.98)
43 (1.69) max.
Two,
M4 x 10
(0.39)
13.8 (0.54)
2
(-)
4
Input
47.6 ± 0.2
(1.87 ± 0.01)
(+)
3
25 (0.98) max.
27 (1.06) max.
5
G3NA
G3NA
Unit: mm (inch)
■ SOLID-STATE RELAYS (continued)
G3NA-D210B
4.5 (0.18) dia.
Terminal arrangement/
Internal connections
(Top view)
Four,
M4 x 10 (0.39)
Load
58
(2.28)
max.
44
(1.73)
47.5
(1.87)
Mounting holes
(Bottom view)
Two,
4.4 (0.17) dia. or M4
Load
power
supply
Load
Operation
indicator
1
-
2
+
(-)
4
(+)
3
Input
4.5 (0.18)
13.8 (0.54)
25 (0.98)
25 (0.98) max.
43 (1.69) max.
27 (1.06) max.
47.6 ± 0.2
(1.87 ± 0.01)
■ HEAT SINKS
Track Mount Heat Sink – Y92B-N50
Two, M3 holes
Two, M4 holes
4.6 (0.18) dia.
47
(1.85)
max.
44
30
(1.73)
max. (1.18)
35
(1.38)
30.5 ± 0.3
(1.20 ± 0.01)
47.6 (1.87)
Mounting holes
(Top view)
Two, 3.2 (0.13) dia. holes
5.6
(0.22)
5
(0.20)
77 (3.03) max.
Two, 4.4 (0.17) dia.
or M4 holes
4.5 (0.18)
6 (0.24)
35 ± 0.2
(1.38 ± 0.01)
90 ± 0.4
(3.54 ± 0.02)
51 (2.01) max.
90 ± 0.3 (3.54 ± 0.01)
Weight: approx. 200 g (7 oz.)
100 (3.94) max.
Track Mount Heat Sink – Y92B-N100
4.6 (0.18) dia.
Two, M3 holes
Two, M4 holes
71
(2.80)
max. 30 (1.18)
35
(1.38)
Mounting holes
(Top view)
Two, 3.2 (0.13) dia. holes
35 ± 0.2
(1.38 ± 0.01)
30.5 ± 0.3
(1.20 ± 0.01)
47.6 (1.87)
77 (3.03) max.
90 ± 0.3 (3.54 ± 0.01)
100 (3.94) max.
6
Two, 4.4 (0.17) dia.
or M4 holes
74
(2.91)
max.
5.6
(0.22)
28
(1.10)
5 (0.20)
4.5 (0.18)
13 (0.51)
90 ± 0.4
(3.54 ± 0.02)
100 (3.94) max.
Weight: approx. 400 g (14 oz.)
G3NA
G3NA
Track Mount Heat Sink – Y92B-N150
47.6
(1.87)
Mounting holes
(Top view)
Two, 3.2 (0.13) dia. holes
Two,
M4 holes
4.6 (0.18) dia.
100
(3.94)
max.
35
(1.38)
30 (1.18)
56 ± 0.3
(2.21 ± 0.01)
28
(1.10)
5.6
(0.22)
77 (3.03) max.
Two, 4.4 (0.17) dia.
or M4 holes
104
(4.09)
max.
35 ± 0.2
(1.38 ± 0.01)
90 ± 0.4
(3.54 ± 0.02)
5 (0.20)
13 (0.51)
4.5 (0.18)
100 (3.94) max.
Weight: approx. 560 g (20 oz.)
90 ± 0.3 (3.54 ± 0.01)
100 (3.94) max.
Standard Mount Heat Sinks
Y92B-A100
Y92B-A150
Mounting holes
Y92B-A100, Y92B-A150N
Y92B-A250
Three, M4 holes
Two, M4 holes
90 ± 0.1
(3.54 ± 0.004)
90 ± 0.1
(3.54 ± 0.004)
Four, 4.4 (0.17) dia.
or M4 holes
80.5
(3.17)
max.
R2.2
(0.09)
1.5
(0.06)
100.5
(3.94)
max.
47.6 (1.87)
90 ± 0.1
(3.54 ± 0.004)
9.6 (0.38)
2 (0.08)
47.6 (1.87)
50 ± 0.1 (1.97 ± 0.004)
50 ± 0.1 (1.97 ± 0.004)
56 ± 0.5 (2.21 ± 0.02)
100 (3.93) max.
1.5
(0.06)
30 (1.18)
50 ± 0.1
(1.97 ± 0.004)
45.5 (1.79) max.
150 (5.91) max.
Standard Mount Heat Sinks
Y92B-A250
Mounting holes
Three, M4 holes
90 ± 0.1
(3.54 ± 0.004)
Four, 4.4 (0.17) dia.
or M4 holes
80.5
(3.17)
max.
R2.2
(0.09)
1.5
(0.06)
47.6 (1.87)
100.5
(3.94)
max.
90 ± 0.1
(3.54 ± 0.004)
9.6 (0.38)
2 (0.08)
1.5
(0.06)
50 ± 0.1 (1.97 ± 0.004)
56 ± 0.5 (2.21 ± 0.02)
250 (9.84) max.
50 ± 0.1
(1.97 ± 0.004)
30 (1.18)
45.5 (1.79) max.
R99-11 Mounting Bracket for G3NA-240B
16 (0.63)
12.5
(0.49)
8 (0.32)
5
(0.20)
21
(0.83)
4 (0.16)
4.6 (0.18)
56
(2.21)
Note: Use mounting bracket R99-11 to mount the
G3NA-240B with a pitch of 56 mm (2.21 in)
instead of 47.5 mm (1.87 in) to match the pitch
of G3N-240B.
7
G3NA
G3NA
■ APPROVALS
UL (File No. E64562)/CSA (File No. LR35535)
SSR type
G3NA-205B
G3NA-210B
Input voltage
5 to 24 VDC
100 to 120 VAC
200 to 240 VAC
G3NA-220B
G3NA-225B
G3NA-240B
G3NA-410B
5 to 24 VDC
100 to 240 VAC
G3NA-420B
G3NA-425B
G3NA-440B
G3NA-D210B
Load type
General use/Tungsten
Motor
General use/Tungsten
Motor
General use/Tungsten
Motor
General use/Tungsten
Motor
General use/Tungsten
Motor
General use/Tungsten
Motor
Contact ratings
Without heat sink
3 A, 240 VAC
2.5 FLA, 15 LRA, 240 VAC
4 A, 240 VAC
2.5 FLA, 15 LRA, 240 VAC
4 A, 240 VAC
2.5 FLA, 15 LRA, 240 VAC
4 A, 240 VAC
2.5 FLA, 15 LRA, 240 VAC
6 A, 240 VAC
5 FLA, 30 LRA, 240 VAC
4 A, 480 VAC
2.5 FLA, 15 LRA, 480 VAC
With heat sink (see note 1)
5 A, 240 VAC
2.5 FLA, 15 LRA, 240 VAC
10 A, 240 VAC
5 FLA, 30 LRA, 240 VAC
20 A, 240 VAC
10 FLA, 60 LRA, 240 VAC
25 A, 240 VAC
12 FLA, 72 LRA, 240 VAC
40 A, 240 VAC
20 FLA, 120 LRA, 240 VAC
10 A, 480 VAC
5 FLA, 30 LRA, 480 VAC
General use/Tungsten
Motor
General use/Tungsten
Motor
General use/Tungsten
Motor
General use
4 A, 480 VAC
2.5 FLA, 15 LRA, 480 VAC
4 A, 480 VAC
2.5 FLA, 15 LRA, 480 VAC
6 A, 480 VAC
5 FLA, 30 LRA, 480 VAC
4 A, 200 VDC
20 A, 480 VAC
10 FLA, 60 LRA, 480 VAC
25 A, 480 VAC
12 FLA, 72 LRA, 480 VAC
40 A, 480 VAC
20 FLA, 120 LRA, 480 VAC
10 A, 200 VDC
Note: 1. When used with the proper OMRON heat sink part number or an appropriately dimensioned equivalent.
2. The rated values approved by each of the safety standards (e.g., UL, CSA, and TUV) may be different from the performance
characteristics individually defined in this catalog.
3. In the interest of product improvement, specifications are subject to change.
Precautions
See General Information Section near the front of this catalog for Solid State Precautions.
NOTE: DIMENSIONS ARE SHOWN IN MILLIMETERS. To convert millimeters to inches divide by 25.4.
OMRON ELECTRONICS, INC.
OMRON CANADA, INC.
One East Commerce Drive
Schaumburg, IL 60173
885 Milner Avenue
Scarborough, Ontario M1B 5V8
1-800-55-OMRON
416-286-6465
Cat. No. GC RLY7
8
01/00
Specifications subject to change without notice.